EIPL BD75 Скачать руководство пользователя страница 3

 

 

 

 

Page 3 of 12 

Drawing   : - TPC478 
Issue 

: - 5 

Date 

: - 11/04/19 

 
 

SPECIFICATIONS

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

"This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. The 

refrigeration system is hermetically sealed. 

 

The Global Warming Potential (GWP) of refrigerants used in products manufactured by Ebac 

Industrial Products Ltd is as follows 

 

R134a – 1300 

R407c – 1610 

 

For type and weight of refrigerant contained in this unit, please refer to the product data label"

 

M

ODEL

10224GD-GB 

H

EIGHT

615 mm 

W

IDTH

382 mm 

D

EPTH

365 mm 

W

EIGHT

31 kg 

A

IRFLOW

185 M

3

/Hr 

P

OWER 

S

UPPLY

230V/ 50Hz/ 1 ph 

F

INISH

Rotational Moulded 
polyethylene 

O

PERATING 

R

ANGE

3°C – 35°C 

R

EFRIGERANT

R410a (140g) 

Содержание BD75

Страница 1: ...Page 1 of 12 Drawing TPC478 Issue 5 Date 11 04 19 BD75 DUAL VOLTAGE INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL www eipl co uk...

Страница 2: ...absolute humidity than that which entered Continuous circulation of air through the dehumidifier gradually reduces the relative humidity within the area The RM75DV dehumidifier is a rugged reliable d...

Страница 3: ...al GWP of refrigerants used in products manufactured by Ebac Industrial Products Ltd is as follows R134a 1300 R407c 1610 For type and weight of refrigerant contained in this unit please refer to the p...

Страница 4: ...cur CHECK DEHUMIDIFICATION PROCESS AS FOLLOWS 1 Place unit on a level surface 2 Start up unit by switching to I and humidistat fully clockwise 3 Check that the compressor is running 4 Leave the machin...

Страница 5: ...ng accompanied by frosting of the thin capillary tubes indicates loss of refrigerant gas or low charge 4 Check all wiring connections including mains cable for damage or loose connections 5 In order t...

Страница 6: ...the refrigerant compressor The charging stub should be crimped and rebrazed after servicing NEVER allow permanent service valves to be fitted to any part of the circuit Service valves may leak causing...

Страница 7: ...fault 3 Loss of refrigerant gas 1 Check all of the above 2 Contact the Factory Service Center 3 Contact the Factory Service Center Little or no defrost when required 1 Faulty timer 2 Faulty by pass va...

Страница 8: ...r 1019712 1 5 Capillary 3014254 1 64ft 6 Solenoid valve 3020836 1 7 Filter dryer 3020937 1 8 Solenoid coil 3030451 1 9 On Off switch 3035914 1 10 Fan Motor 3947012 1 11 Fan Blade 3947014 1 12 Castor 3...

Страница 9: ...to Protocol The refrigeration system is hermetically sealed The Global Warming Potential GWP of refrigerants used in products manufactured by Ebac Industrial Products Ltd is as follows R134a 1300 R407...

Страница 10: ...Page 10 of 12 Drawing TPC478 Issue 5 Date 11 04 19...

Страница 11: ...Page 11 of 12 Drawing TPC478 Issue 5 Date 11 04 19...

Страница 12: ...ww eipl co uk sales eipl co uk American Sales Office Ebac Industrial Products Inc 700 Thimble Shoals Blvd Suite 109 Newport News Virginia 23606 2575 USA Tel 01 757 873 6800 Fax 01 757 873 3632 www eba...