Step 3. Initializing a repeater (range extender) 

Skip this chapter, if you do not use a repeater. 

Wireless  systems  must  first 

“recognize”  each  other  if  they  are  to  communicate.  Initialization  of  the 

PlantControl unit with the repeater must therefore be carried out first. 

Commissioning of already initialized repeaters:

  

If the PlantControl unit and repeaters have been initialized already at the factory (would be labeled on 
PlantControl central unit), no initialization must be performed. 

Initializing  a repeater 

Initialize > Repeater > OK-button 

Before  you  begin  initializing  the  repeater,  you  should  create  a  simple  plan  with  the  position  of  the 
individual components. The plan should show the assignment of repeaters to the PlantControl respectively 
how the repeaters are assigned  between themselves. 

For  a  better  understanding  see  the  following  example  with  a  total  of  5  repeaters,  wherein  repeater  1  is 
directly assigned to the PlantControl and repeater 2 to 5 are connected with the PlantControl via repeater 
number 1. 

12 

 

 

The following display shows the settings (inputs) for the above example of repeater number 1. 

PlantControl  

Central unit 

Repeater  

Repeater  

Input 

Input 

Repeater  

Repeater  

Repeater  

Input 

Input 

Input 

1. Select Initialize > Repeater > OK-button.  

2. Before initializing a repeater, you must first make the following settings: 

Repeater Number: 

Here, number 1 is displayed as the first repeater. 

in direction of Controller: 

Enter here over which other repeater, a repeater is connected to the 

PlantControl central unit. As in the example above no other repeater is placed in direction to the 
PlantControl enter here the number zero (number 0 = Controller). Otherwise press the OK-button 
and enter the repeater number, which is between repeater 1 and the Plant Control.  

in direction Sensor: 

You can assign up to five other repeaters to a certain repeater. Therefore, you 

have to enter here which other repeaters are connected to the repeater number 1. In this example, 
the repeater number 2, 3, 4 and then 5 were entered. 

Place the repeater approximately at a distance of 1 meter from the controller and press the control 
button on the repeater for 5 seconds. Now release the button. Once the controller has detected a 
repeater, you label it with the repeater number assigned by the system. You can then initialize the 
next repeater. When the repeater has not been detected, “failed” will be displayed. In such a case, 
the procedure from point 1 must be repeated. 

Содержание PlantControl CX

Страница 1: ...er and Soil Moisture Sensors Operating Instructions Ver 3 46 P O Box 4 6987 ZG Giesbeek Nijverheidsstraat 30 6987 EM Giesbeek The Netherlands T 31 313 880200 F 31 313 880299 E info eijkelkamp com I ht...

Страница 2: ...mmissioning 11 Step 1 Switching on your PlantControl 11 Step 2 Configuring your PlantControl central unit 11 Step 3 Initializing a repeater 12 Step 4 Repeater settings 16 Step 5 Initializing the senso...

Страница 3: ...the display and analysis of the measured data Optional accessories Solar cell with cable connection to the Data Logger PlantControl D central unit External antenna for enhanced signal reception Plant...

Страница 4: ...e sensors require no maintenance and have no corrosion prone parts In developing the Plant Control D performance the ease of use and reliability were given the greatest priority General Features Up to...

Страница 5: ...Soil temperature 0 1 C Sensors for soil moisture measurements at soil temperature range between 2 C to 50 C on request 5 Quick start guide At the office 1 Connect cable for mains connection or solar c...

Страница 6: ...export functions via USB interface 11 Alarm LED 12 GPRS Terminal LED Flashes every 3 seconds when network connection is established 13 Busy LED Lights up when the central unit is busy operating panel...

Страница 7: ...icture above shows the connection terminals for the mains Besides the phase P and the neutral line N a ground wire has to be used The power cable is fed through one of the cable entries and connected...

Страница 8: ...l Switching on switching off checking power supply Please note that repeater are usually delivered with built in rechargeable batteries 8x AA 1 Unscrew the 4 screws and remove the front cover 2 Attach...

Страница 9: ...ately CAUTION When you remove the sensor cover take care to put it back on the same sensor Sensor operation Please note that the sensors are usually supplied without installed batteries Switching on s...

Страница 10: ...nsor has not been initialized yet LED stays on continuously Error The frequency band switch on the sensor has been changed and no longer matches the frequency band on the PlantControl unit switch off...

Страница 11: ...e network numbers allocated by the system Radio channel The factory setting for the radio channel is 5 Channels 2 3 4 and 5 can be selected The channel number should only be changed if there is radio...

Страница 12: ...unit Repeater 1 Repeater 2 Input 0 Input 2 Repeater 5 Repeater 4 Repeater 3 Input 3 Input 4 Input 5 1 Select Initialize Repeater OK button 2 Before initializing a repeater you must first make the foll...

Страница 13: ...with repeater number 6 Example repeater number 3 Enter under in direction of Controller the number 1 as repeater number 3 is connected with the PlantControl central unit via repeater number 1 Enter un...

Страница 14: ...ting removing repeater number 9 1 Switch off repeater number 9 by removing the battery connector from the battery holder It is not enough to just pull out the AC adapter or solar cell cable 2 Deactiva...

Страница 15: ...of repeater configurations 15 PlantControl Central unit Repeater 1 Repeater 3 Repeater 2 PlantControl Central unit Repeater 1 Repeater 2 PlantControl Central unit Repeater 1 Repeater 3 Repeater 2 Rep...

Страница 16: ...16 Step 4 Repeater settings Settings Repeater OK button Number of repeaters This is automatically assigned based on the number of initialized repeaters For this reason the figure should not be changed...

Страница 17: ...the system so that clear allocation is later guaranteed between the sensor and the data record You can then initialize the next sensor If a sensor is not recognized fail will appear in the display In...

Страница 18: ...sensor Deactivate OK button Use the cursor keys to move to the next or previous sensor and to deactivate another sensor If you want to initialize again a deactivated sensor proceed with steps 1 to 8 a...

Страница 19: ...OK key 3 Email send To test your settings or to manually initiate a transmission select Email send followed by the OK key only after entering all the parameters The GPRS Modem will immediately transm...

Страница 20: ...s PlantCare settings Data retrieval by SMS In addition to automatic data transmission the data required can also be sent to any e mail address by sending an SMS to the GPRS Modem Use the following pro...

Страница 21: ...ically remove the SIM Card from the GPRS Modem insert it in a mobile phone and make a phone call Some providers also accept an outgoing message as an outgoing call If this is the case with your provid...

Страница 22: ...nsor at least 1 yard from the controller and briefly press the sensor s On Off button After a few seconds the PlantControl unit s display will show the full identification of the corresponding sensor...

Страница 23: ...reset so that the sensors will not require initializing again Initialize Code Input OK button Enter here the code obtained from the manufacturer for the activation of additional functions Alarm text D...

Страница 24: ...s Areas of shade should be avoided To avoid erroneous measuring results caused by water logging the sensor should not be positioned in dips in the ground If a sprinkler system is used ensure that the...

Страница 25: ...sensor tip yellow part in water felt must be wet 4 Insert the sensor cautiously Never rotate the sensor when inserting or pulling out as this may unscrew the yellow sensor tip 5 Water the area around...

Страница 26: ...advisable to use several dripper with a correspondingly lower water outlet per plant in order to achieve a better distribution of water Plants are very adaptive and the roots will grow into those are...

Страница 27: ...wireless sensor the radio link between the sensor and Plant Control D CX or FA central unit should not be disturbed Since the radio transmission can be disturbed by the water in the leaves or any oth...

Страница 28: ...ber endings H n m n m t K 1 1 1 1 1 Standard soils from the Agricultural Research Institute LUFA Speyer n m 1 1 28 Standard Soils Analyses Data Sheet 9 11 Mean values of different batch analyses stand...

Страница 29: ...ard soils 5 1 6 2 3 fine textured soils medium textured soils coarse sand 4 European Union soil texture pyramid classification German soil texture pyramid classification FAO soil texture pyramid class...

Страница 30: ...inserted into the USB port of the PlantControl central unit By selecting the command Firmware update the firmware is automatically installed This can take up to 10 minutes Firmware Update GPRS If a n...

Страница 31: ...6 Troubleshooting The numbers and values used in this table are only examples Content coming soon 31...

Страница 32: ...signed matches the number on the sensor cover 8 Warranty Your dealer will issue a two year warranty for this product from date of purchase This warranty covers all substantial defects of the unit that...

Отзывы: