2.6  APPLY POWER 

Once the air conditioner is mounted, check the serial label and confirm the voltage required 
and then apply appropriate power as outlined below. 
 
120 VAC units – plug into standard 120 volt, grounded outlet. 
 
220  –  240  VAC  units  –  this  unit  will  not have  a  plug  on  the  end.    Connect  the  wires  to  an 
appropriate power source using standard safe wiring methods as follows: 

 

Wire colors are as follows: 
  

 

Black or Brown – line 

  

 

White or Blue – line/neutral 

 

 

 

Green or Green/Yellow – ground 

 
 

Amperage for 120 VAC unit is 11.8 amps 

 

Amperage for 220 VAC unit is 6.3 amps 

 
 

Upon applying power to the air conditioner the fans on the cold side (inside the enclosure) will 

come  on.    The  hot  side  fans  (outside  the  enclosure)  may  also  run  depending  on  where  the 
thermostat  is  set.    The  cold  side  fans  always  run  to  circulate  air  within  your  enclosure  thereby 
eliminating any “hot spots”.  The hot side fans will only run when the air conditioner is cooling – 
they are “pumping” the heat from the inside of your enclosure to the outside air. 

Содержание AAC-151B Series

Страница 1: ...lectric Air conditioner installation and operation manual FOR 2500 Btu MODEL S AAC 151B 4XT AAC 151B 4XT HC AAC 151B XXXXX Cooling Solutions for Cooling Solutions for Cooling Solutions for Cooling Solutions for Mission Mission Mission Mission Critical Electronics Critical Electronics Critical Electronics Critical Electronics ...

Страница 2: ...7 2 6 APPLY POWER 8 3 OPERATION 3 1 THERMOSTAT SET POINTS AND HEATING COOLING UNITS 9 3 2 MAINTENANCE 9 4 SPECIFICATIONS 4 1 STANDARD SPECIFICATIONS 10 5 APPENDIX A STANDARD CUTOUT 11 B EXTENSION FRAME CUTOUT 12 EIC SOLUTIONS INC EIC SOLUTIONS INC EIC SOLUTIONS INC EIC SOLUTIONS INC 700 VETERANS WAY SUITE 200 WARMINSTER PA 18974 PHONE 1 215 443 5190 or 1 800 497 4524 FAX 215 443 9564 EMAIL info ei...

Страница 3: ...e practical for real world applications and are now found in everything from consumer goods to spacecraft Your EIC Solutions Thermoelectric Air Conditioner operates on this principle so there is no compressor and no expensive ozone depleting CFC s EIC s air conditioners use Thermoelectric modules sandwiched between high performance aluminum heat sinks high CFM axial fans and a patented electronic ...

Страница 4: ...osure See Figure 2 1 and 2 2 Vertically mounted mounted on the side of an enclosure 2500 Btu units are always mounted with the exposed heatsink fins facing left and right Fig 2 1 The unit cannot be mounted vertically and turned 90 degrees with the exposed heatsink fins at the top and bottom The AAC 151 4XT is equipped with a built in vertical condensate drip pan Once installed the drain hoses must...

Страница 5: ...AL INSTALLATIONOF 2500 BTUUNITWITH INTERNALLYMOUNTEDDP 151HDRIP PANANDDRAINTUBE ENCLOSURE HOT SIDE OF AC OUTSIDE OF ENCLOSURE COLD SIDE OF AC INSIDE OF ENCLOSURE DRAIN TUBE COLD SIDE FANS HOTSIDE FANS COLD SIDE HEATSINK FINS HOTSIDE HEAT SINKS HOTSIDE HEAT SINKS COLD SIDE HEATSINK FINS ...

Страница 6: ...stallation manual 4 Using a pencil center punch or other method mark the exact center point of each mounting hole on the enclosure 5 Using the jigsaw cut the opening in the enclosure 6 Using the appropriate drill bit drill a hole at each of the marks you made earlier 7 Using the 8 32 tap tap each of the holes you have drilled Non Extension Frame Only 2 4 INSTALLING THE AIR CONDITIONER INSTALL THE ...

Страница 7: ...ded with the AC unit Review the Fig 2 3 below for suggested drain line configurations FIG 2 3 YOU MUST USE THE FACTORY INSTALLED HORIZONTAL DRIP PAN IF YOU INSTALL THE AIR CONDITIONER HORIZONTALLY FIG 2 2 ON THE TOP OF YOUR ENCLOSURE FAILURE TO DO SO MAY ALLOW CONDENSATE TO DRIP IN AN UNCONTROLLED MANNER CAUSING DAMAGE TO YOUR EQUIPMENT ...

Страница 8: ... Wire colors are as follows Black or Brown line White or Blue line neutral Green or Green Yellow ground Amperage for 120 VAC unit is 11 8 amps Amperage for 220 VAC unit is 6 3 amps Upon applying power to the air conditioner the fans on the cold side inside the enclosure will come on The hot side fans outside the enclosure may also run depending on where the thermostat is set The cold side fans alw...

Страница 9: ...Thermoelectric Air Conditioners are virtually maintenance free The only time maintenance is required is when a unit is installed in an extremely dirty environment In these cases the hot side heat sinks outside the enclosure should be inspected regularly for a build up of dust or dirt If a build up is present on the heat sink fins it can be easily removed as follows 1 Disconnect the power from the ...

Страница 10: ...t Voltage Range 100 264 V Current 11 8 6 3 A Heating Capability HC Units Only 2700 BTU hr 800 W Weight 33 kg 72 lbs NEMA Rating 4X Cold Side Airflow 180 cfm 305 m3 hr Hot Side Airflow 250 cfm 425 m3 hr Sound Level at 1 meter 75 dBA Operating Temperature Range 4 to 140 F 20 to 60 C Storage Temperature Range 4 to 185 F 20 to 85 C Cooling Thermostat Accuracy 1 0 F 0 6 C ...

Страница 11: ...11 11 11 11 1 800 497 4524 EIC SOLUTIONS INC 215 443 5190 APPENDIX A Enclosure cutout for 2500 BTU air conditioner NON EXTENSION FRAME Holes to be 8 32 TAP ...

Страница 12: ...12 12 12 12 1 800 497 4524 EIC SOLUTIONS INC 215 443 5190 APPENDIX B Enclosure cutout for 2500 BTU air conditioner EXTENSION FRAME ONLY Holes to be 203 ...

Отзывы: