2.6 APPLY POWER
Once the air conditioner is mounted, check the serial label and confirm the voltage required
and then apply appropriate power as outlined below.
120 VAC units – plug into standard 120 volt, grounded outlet.
220 – 240 VAC units – this unit will not have a plug on the end. Connect the wires to an
appropriate power source using standard safe wiring methods as follows:
Wire colors are as follows:
Black or Brown – line
White or Blue – line/neutral
Green or Green/Yellow – ground
Amperage for 120 VAC unit is 11.8 amps
Amperage for 220 VAC unit is 6.3 amps
Upon applying power to the air conditioner the fans on the cold side (inside the enclosure) will
come on. The hot side fans (outside the enclosure) may also run depending on where the
thermostat is set. The cold side fans always run to circulate air within your enclosure thereby
eliminating any “hot spots”. The hot side fans will only run when the air conditioner is cooling –
they are “pumping” the heat from the inside of your enclosure to the outside air.