background image

4

4

4

4    

1

-800-497-4524                   EIC SOLUTIONS, INC

.

                       215-443-5190 

2.  INSTALLATION 

2.1 CHOOSING A LOCATION ON YOUR ENCLOSURE 

When  choosing  a  mounting  location  for  your  unit,  be  sure  to  keep  air  flows  of  both  the 

interior and exterior heatsinks and fans in mind.  Adequate clearance between the fans/heatsinks 
and nearby surfaces is required for unrestricted air flows which will ensure optimal performance 
and long, trouble free operation.  The general rule is to allow a minimum of two inches between 
the fans or heatsinks and any surface.  Refer to figure 1.1 for an air flow diagram.   

Other  considerations  in  deciding  on  a  mounting  location  include;  allowing  access  to 

thermostat  (this  will  be  inside  the  enclosure)  if  frequent  adjustments  are  to  be  made;  allowing 
access to the hot side heat sinks (this will be on the outside of the enclosure) for cleaning if the 
unit will be used in a harsh, dirty environment.    

2.2  ORIENTATION 

Your AC unit can be mounted either vertically on the front, rear or side of your enclosure or 

horizontally on the top of your enclosure.  See Figure 2.1 and 2.2. 

Vertically  mounted  (mounted  on  the  side  of  an  enclosure)  2500  Btu  units  are  always 

mounted  with  the  exposed  heatsink  fins  facing  left  and  right.  (Fig.  2.1)   

The  unit  cannot  be 

mounted  vertically  and  turned  90  degrees  with  the  exposed  heatsink  fins  at  the  top  and 
bottom.

  The AAC-151-4XT is equipped with a built in vertical condensate drip pan.  Once installed 

the drain hoses must be attached to the brass fittings located in the bottom of the cold side cover 
(inside the enclosure) and routed to outside the enclosure.  See Fig. 2.1. 

Mounting  the  unit  vertically  and  turned  90  degrees  on  the  side  of  an  enclosure  (with  the 

exposed heat sink fins facing the top and bottom), will cause condensate to drip in an uncontrolled 
manner,  possibly damaging electronic equipment  within  the  enclosure.   If this orientation is the 
only possible configuration, contact the Engineering Dept. at EIC for a custom solution.   

 

Horizontally mounted 2500 Btu units

 

always require a factory installed drip pan (part # 

DP-151H) to prevent dripping condensate from damaging electronic equipment.

  (Fig. 2.2)   

 

In either orientation, issues regarding access should be considered and minimum clearances 

must be maintained as outlined in Section 2.1 of this manual.  

 

 

 

 

 

 

 

Содержание AAC-151B Series

Страница 1: ...lectric Air conditioner installation and operation manual FOR 2500 Btu MODEL S AAC 151B 4XT AAC 151B 4XT HC AAC 151B XXXXX Cooling Solutions for Cooling Solutions for Cooling Solutions for Cooling Solutions for Mission Mission Mission Mission Critical Electronics Critical Electronics Critical Electronics Critical Electronics ...

Страница 2: ...7 2 6 APPLY POWER 8 3 OPERATION 3 1 THERMOSTAT SET POINTS AND HEATING COOLING UNITS 9 3 2 MAINTENANCE 9 4 SPECIFICATIONS 4 1 STANDARD SPECIFICATIONS 10 5 APPENDIX A STANDARD CUTOUT 11 B EXTENSION FRAME CUTOUT 12 EIC SOLUTIONS INC EIC SOLUTIONS INC EIC SOLUTIONS INC EIC SOLUTIONS INC 700 VETERANS WAY SUITE 200 WARMINSTER PA 18974 PHONE 1 215 443 5190 or 1 800 497 4524 FAX 215 443 9564 EMAIL info ei...

Страница 3: ...e practical for real world applications and are now found in everything from consumer goods to spacecraft Your EIC Solutions Thermoelectric Air Conditioner operates on this principle so there is no compressor and no expensive ozone depleting CFC s EIC s air conditioners use Thermoelectric modules sandwiched between high performance aluminum heat sinks high CFM axial fans and a patented electronic ...

Страница 4: ...osure See Figure 2 1 and 2 2 Vertically mounted mounted on the side of an enclosure 2500 Btu units are always mounted with the exposed heatsink fins facing left and right Fig 2 1 The unit cannot be mounted vertically and turned 90 degrees with the exposed heatsink fins at the top and bottom The AAC 151 4XT is equipped with a built in vertical condensate drip pan Once installed the drain hoses must...

Страница 5: ...AL INSTALLATIONOF 2500 BTUUNITWITH INTERNALLYMOUNTEDDP 151HDRIP PANANDDRAINTUBE ENCLOSURE HOT SIDE OF AC OUTSIDE OF ENCLOSURE COLD SIDE OF AC INSIDE OF ENCLOSURE DRAIN TUBE COLD SIDE FANS HOTSIDE FANS COLD SIDE HEATSINK FINS HOTSIDE HEAT SINKS HOTSIDE HEAT SINKS COLD SIDE HEATSINK FINS ...

Страница 6: ...stallation manual 4 Using a pencil center punch or other method mark the exact center point of each mounting hole on the enclosure 5 Using the jigsaw cut the opening in the enclosure 6 Using the appropriate drill bit drill a hole at each of the marks you made earlier 7 Using the 8 32 tap tap each of the holes you have drilled Non Extension Frame Only 2 4 INSTALLING THE AIR CONDITIONER INSTALL THE ...

Страница 7: ...ded with the AC unit Review the Fig 2 3 below for suggested drain line configurations FIG 2 3 YOU MUST USE THE FACTORY INSTALLED HORIZONTAL DRIP PAN IF YOU INSTALL THE AIR CONDITIONER HORIZONTALLY FIG 2 2 ON THE TOP OF YOUR ENCLOSURE FAILURE TO DO SO MAY ALLOW CONDENSATE TO DRIP IN AN UNCONTROLLED MANNER CAUSING DAMAGE TO YOUR EQUIPMENT ...

Страница 8: ... Wire colors are as follows Black or Brown line White or Blue line neutral Green or Green Yellow ground Amperage for 120 VAC unit is 11 8 amps Amperage for 220 VAC unit is 6 3 amps Upon applying power to the air conditioner the fans on the cold side inside the enclosure will come on The hot side fans outside the enclosure may also run depending on where the thermostat is set The cold side fans alw...

Страница 9: ...Thermoelectric Air Conditioners are virtually maintenance free The only time maintenance is required is when a unit is installed in an extremely dirty environment In these cases the hot side heat sinks outside the enclosure should be inspected regularly for a build up of dust or dirt If a build up is present on the heat sink fins it can be easily removed as follows 1 Disconnect the power from the ...

Страница 10: ...t Voltage Range 100 264 V Current 11 8 6 3 A Heating Capability HC Units Only 2700 BTU hr 800 W Weight 33 kg 72 lbs NEMA Rating 4X Cold Side Airflow 180 cfm 305 m3 hr Hot Side Airflow 250 cfm 425 m3 hr Sound Level at 1 meter 75 dBA Operating Temperature Range 4 to 140 F 20 to 60 C Storage Temperature Range 4 to 185 F 20 to 85 C Cooling Thermostat Accuracy 1 0 F 0 6 C ...

Страница 11: ...11 11 11 11 1 800 497 4524 EIC SOLUTIONS INC 215 443 5190 APPENDIX A Enclosure cutout for 2500 BTU air conditioner NON EXTENSION FRAME Holes to be 8 32 TAP ...

Страница 12: ...12 12 12 12 1 800 497 4524 EIC SOLUTIONS INC 215 443 5190 APPENDIX B Enclosure cutout for 2500 BTU air conditioner EXTENSION FRAME ONLY Holes to be 203 ...

Отзывы: