1

-800-497-4524                   EIC SOLUTIONS, INC

.

                       215-443-5190 

1.  GENERAL INFORMATION 

1.1 PRINCIPLES OF OPERATION 

n 1834 Jean Peltier discovered that by passing a current through two dissimilar conductors the 
junction of those materials will either absorb or release heat depending on the direction of the 

current flow.   Thirteen years earlier, Thomas Seebeck had discovered that current would flow 
when you placed a temperature gradient across the junction of two dissimilar metals.  These 

two discoveries were the basis of thermoelectrics.  With the advent of modern semiconductors, 

thermoelectric devices became practical for real world applications and are now found in 
everything from consumer goods to spacecraft.   

Your EIC Solutions Thermoelectric Air Conditioner operates on this same principle so there 

is no compressor and no expensive, ozone depleting CFC’s.  EIC’s air conditioners use 
Thermoelectric “modules” sandwiched between high performance aluminum heat sinks, high CFM 
axial fans, and a patented electronic design to “pump” the heat from the inside of your enclosure 
to the outside, without exposing your delicate electronics to any outside air or contaminates.  See 
Figure 1.1.  

EIC uses only the highest quality components in our air conditioners and you can expect 

years of trouble free cooling from these solid-state devices.  Every unit we sell is backed by our 
one year parts and labor warranty. 

 

FIGURE 1.1 

AMBIENT AIR 

REMOVES HEAT 

FROM HOT SIDE 

HEAT SINK

COLD AIR 

CIRCULATED 

WITHIN THE 

ENCLOSURE

HOT

SIDE

HEAT 

SINK

COLD 

SIDE 

HEAT 

SINK

FAN

FAN

I

Содержание AAC-120-4XT Series

Страница 1: ...INC 215 443 5190 EIC SOLUTIONS INC Air conditioner installation and operation manual FOR 200 Btu MODEL S AAC 120 4XT AAC 120 4XT HC AAC 120 4XT F AAC 120 4XT HCF AAC 120 4XT XXXXXX Cooling Solutions for Mission Critical Electronics ...

Страница 2: ...NDITIONER 6 INSTALL A THROUGH MOUNT AIR CONDITIONER 6 INSTALL A FLUSH MOUNT AIR CONDITIONER 7 INSTALL THE DRAIN LINE 7 APPLY POWER 10 3 OPERATION 3 1 THERMOSTAT SET POINTS AND HEATING COOLING UNITS 11 3 2 MAINTENANCE 11 EIC SOLUTIONS INC 700 VETERANS WAY SUITE 200 WARMINSTER PA 18974 PHONE 1 215 443 5190 or 1 800 497 4524 FAX 215 443 9564 EMAIL info eicsolutions com VISIT US ON THE WEB AT www eics...

Страница 3: ...om consumer goods to spacecraft Your EIC Solutions Thermoelectric Air Conditioner operates on this same principle so there is no compressor and no expensive ozone depleting CFC s EIC s air conditioners use Thermoelectric modules sandwiched between high performance aluminum heat sinks high CFM axial fans and a patented electronic design to pump the heat from the inside of your enclosure to the outs...

Страница 4: ...unting the AC on the top of your enclosure can result in damage to your equipment from dripping condensate If mounted on the bottom of your enclosure any condensate that is produced will not be able to drain from the integral drip pan This may lead to fungal growth and or early failure of the AC unit Vertically mounted 200 Btu units are always mounted with the fans at the top Fig 2 1 In this orien...

Страница 5: ...D SIDE OF AC INSIDE OF ENCLOSURE DRAIN TUBE ENCLOSURE HOT SIDE FAN COLD SIDE FAN HOT SIDE HEAT SINK FINS COLD SIDE HEAT SINK FINS VERTICAL INSTALLATION OF AAC 120 4XT F 200 BTU FLUSH MOUNT UNIT WITH INTERGRAL DRIP PAN ENCLOSURE COLD SIDE HEAT SINK FINS DRAIN TUBE HOT SIDE HEAT SINK FINS HOT SIDE OF AC OUTSIDE OF ENCLOSURE HOT SIDE FAN COLD SIDE OF AC INSIDE OF ENCLOSURE COLD SIDE FAN ...

Страница 6: ...king cutting or drilling check that the location meets the clearance requirements as specified in the installation manual 4 Using a pencil center punch or other method mark the exact center point of each mounting hole on the enclosure Also mark the four corners of the section to be cut out 5 Remove the stencil and using a pencil or other method connect the marks you made at the corners of the cut ...

Страница 7: ...e and through the appropriate holes in the gasket 2 Place a Phillips screwdriver in one of the top corner mounting screws in the enclosure Carefully align the AC unit mounting hole with screw being held Bring the AC in contact with the screw and start the screw into the mounting hole in the AC unit Only engage a few threads 3 Follow step 2 above for the remaining top mounting screws and then for t...

Страница 8: ...8 1 800 497 4524 EIC SOLUTIONS INC 215 443 5190 not to scale ...

Страница 9: ...9 1 800 497 4524 EIC SOLUTIONS INC 215 443 5190 not to scale ...

Страница 10: ...0 VAC unit is 1 75 amps Amperage for 220 VAC unit is 1 0 amps DC Supply Voltage If you purchased our DC model you will have received a 3 wire shielded cable with a DC jack on one end and no termination on the other This cable should be connected to an appropriate 24 28 volt DC power supply as follows Red positive Black negative Green ground Amperage for a 24 VDC unit is 3 75 For other voltages you...

Страница 11: ...mely dirty environment In these cases the hot side heat sinks outside the enclosure should be inspected regularly for a build up of dust or dirt If a build up is present on the heat sink fins it can be easily removed as follows 1 Disconnect the power from the unit 2 Dry dust dirt can be removed using compressed air to blow out the heat sinks Do not direct any high pressure air at the fans 3 Your A...