Technical data
Electrical safety
• Protection (EN 60529): IP 20
• Safety extra low voltage SELV DC 24 V
EMC requirements
• Complies with EN 61000-6-2, EN 61000-6-3 and EN 50090-2-2
Environmental requirements
• Ambient temp. operating: - 5 ... + 45 °C
• Ambient temp. Non-op.: - 25 ... + 70 °C
• Rel. humidity (non-condensing): 5 % … 93 %
Certification
• EIB/KNX
CE norm
• Complies with the EMC regulations (residential and functional buildings) and low voltage
directive
Physical specifications
• Housing: Plastic
• DIN rail mounted device, width: 36 mm
• Weight: approx. 100 g
• Fire load: approx. 1000 kJ
Operating controls
• Learning key for EIB/KNX
Indicators
• Learning-LED (red)
• Signal-LED (green) for EIB/KNX
• Signal-LED (green) for LAN
Ethernet
• 10BaseT (10Mbit/s)
• Supported internet protocols ARP, ICMP, IGMP, UDP/IP and DHCP
Power supply
• External supply 12-24V
• Alternative: Power-over-Ethernet
• Power consumption: < 800 mW
Connectors
• EIB/KNX connection terminal
• LAN RJ-45 socket
• Screw connector for power supply