EIB/KNX IP Router 

mit Power over Ethernet (PoE)

 

 

 

 

IP-Router / Interface between LAN and EIB/KNX bus 

 

 

 

(Quelle: © EIBMARKT GmbH, Reference no.: N000402)

 

 

Содержание EIB/KNX

Страница 1: ... 1997 2010 EIBMARKT GmbH Page 1 EIB KNX IP Router mit Power over Ethernet PoE IP Router Interface between LAN and EIB KNX bus Quelle EIBMARKT GmbH Reference no N000402 ...

Страница 2: ...P backbone The KNX IP Router can also be used as an interface for accessing the bus via IP replacing an RS232 or USB interface It has an external 12 V to 24 V power supply or can alternatively be powered via Power over Ethernet IEEE 802 3af The EIB KNX IP Router has a filter table and is able to buffer up to 150 telegrams ...

Страница 3: ...ear e g FS108P The device disposes of 8 ports four of which are equipped with Power over Ethernet IEEE802 3af 48 VDC The IP router for example can be connected to one of these four ports As an alternative power supply can be provided by means of screw connecting terminals at the upper side using a separate power supply unit 12 24V DC or transformer 12 24V AC Parallel power must be avoided ...

Страница 4: ...ions residential and functional buildings and low voltage directive Physical specifications Housing Plastic DIN rail mounted device width 36 mm Weight approx 100 g Fire load approx 1000 kJ Operating controls Learning key for EIB KNX Indicators Learning LED red Signal LED green for EIB KNX Signal LED green for LAN Ethernet 10BaseT 10Mbit s Supported internet protocols ARP ICMP IGMP UDP IP and DHCP ...

Страница 5: ...mbH Page 5 Operating and installation manual Coupler function KNXnet IP routing The EIB KNX IP Router can operate as a line and or backbone coupler In both cases the LAN IP acts as a backbone KNX IP Router as a line coupler ...

Страница 6: ... 1997 2010 EIBMARKT GmbH Page 6 KNX IP Router as a backbone coupler ...

Страница 7: ...physical address is in the form of x y 0 x y 1 15 the router operates as a line coupler If it is in the form of x 0 0 x 1 15 the router acts as a backbone coupler Attention If the EIB KNX IP Router is used as a backbone coupler x 0 0 there must be no KNX IP Router in the topology beneath it For example if a KNX IP Router has the physical address of 1 0 0 there must be no KNX IP Router with the add...

Страница 8: ... can be transmitted on IP If several consecutive telegrams are transmitted on the same line they must be buffered in the router to avoid telegram loss The EIB KNX IP Router has a memory for 150 telegrams from IP to KNX EIB Bus access function KNXnet IP Tunneling The EIB KNX IP Router can be used as an interface to KNX EIB KNX EIB can be accessed from any point in the LAN For this purpose a second ...

Страница 9: ...address is automatically assigned on the DHCP i e additional settings are not required To be able to use this function there must be a DHCP server in the LAN many DSL routers have an integrated DHCP server Manual In this case the IP address the subnet and the gateway IP address must be entered manually IP configuration IP Routing Multicast Address This address is used for routing telegrams on IP T...

Страница 10: ...he KNX IP Router will only used in the local LAN the entry of 0 0 0 0 can remain unchanged Example of assigning IP addresses A PC is to be used to access the EIB KNX IP Router IP address of the PC 192 168 1 30 Subnet of the PC 255 255 255 0 The EIB KNX IP Router is located in the same local LAN i e it uses the same subnet The subnet constrains the IP addresses that can be assigned In this example ...

Страница 11: ...of main groups 14 and 15 are routed to IP Route All group telegrams of main groups 14 and 15 are routed to IP Group telegrams main groups 16 to 31 Block No group telegrams of these main groups are routed to IP Route An additional page appears on which the routing of main groups 16 to 31 can be disabled or enabled in pairs Note The group addresses of main groups 16 to 31 are reserved addresses that...

Страница 12: ...egrams from KNX EIB if they are routed to IP Acknowledge ACK of physically addressed telegrams Always An acknowledge is generated for every received physically addressed telegram from KNX EIB Only if routed An acknowledge is only generated for received physically addressed group telegrams from KNX EIB if they are routed to IP Answer with NACK Every received physically addressed telegram from KNX E...

Страница 13: ...ock No group telegrams of main groups 14 and 15 are routed to KNX EIB Route All group telegrams of the main groups 14 and 15 are routed to KNX EIB Group telegrams main groups 16 to 31 Block No group telegrams of these main groups are routed to KNX EIB Route An additional page appears on which the routing of main groups 16 to 31 can be disabled or enabled in pairs Physically addressed telegrams Blo...

Страница 14: ...e received physically addressed telegram is not resent to KNX EIB in case of a fault Enable The received physically addressed telegram is resent up to three times in case of a fault Resending of broadcast telegrams Disable The received broadcast telegram is not resent to KNX EIB in case of a fault Enable The received broadcast telegram is resent up to three times in case of a fault ETS Connection ...

Страница 15: ...r requires an additional physical address This second physical address is only used for bus access and must be set up separately Select the Communication tab under Extras Options in the ETS The communications interface is the connection that is currently configured Click on Settings to open the following window Enter a physical address of your choice This address should lie in the same topological...

Страница 16: ... Flashes to indicate telegram traffic 6 LED green Lights up to indicate an Ethernet connection Flashes to indicate telegram traffic 7 RJ 45 socket for connecting an Ethernet patch cable An external power supply only needs to be connected if the switch in use does not support Power over Ethernet EIBMARKT GmbH Friedensstraße 54 08523 Plauen Germany ___________________________________________________...