Read and retain carefully for as long as the product is being used. Contains vital information on the
operation and installation. This leaflet should be regarded as part of the product.

If you are just installing the unit, 

this leaflet must be given to the householder

. This leaflet is to be

given to any subsequent user.

The RadioLINK Carbon Monoxide Alarm Ei262 will
communicate with all other RadioLINK devices including
Smoke/Heat/Fire Alarms, Relays and other accessories.

RadioLINK

MAINS POWERED

CARBON MONOXIDE ALARM

WITH RECHARGEABLE LITHIUM CELL BACK-UP

B16587-R0-262-UC-ENG  15/4/09  3:38 PM  Page 1

Содержание RadioLINK Ei262

Страница 1: ...e just installing the unit this leaflet must be given to the householder This leaflet is to be given to any subsequent user The RadioLINK Carbon Monoxide Alarm Ei262 will communicate with all other RadioLINK devices including Smoke Heat Fire Alarms Relays and other accessories RadioLINK MAINS POWERED CARBON MONOXIDE ALARM WITH RECHARGEABLE LITHIUM CELL BACK UP B16587 R0 262 UC ENG 15 4 09 3 38 PM ...

Страница 2: ...erconnecting etc 4 3 Hardwired Interconnect USING TESTING YOUR SYSTEM HOW TO DISTINGUISH BETWEEN CO ALARM SMOKE ALARM WARNINGS MAINTENANCE LIMITATIONS OF CO ALARMS HOW TO PROTECT YOUR FAMILY GETTING YOUR CO ALARM SERVICED FIVE YEAR GUARANTEE TECHNICAL SPECIFICATIONS ACCESSORIES TROUBLESHOOTING Page CONTENTS 2 3 4 5 9 13 13 17 20 22 24 24 26 28 30 30 31 34 36 B16587 R0 262 UC ENG 15 4 09 3 38 PM Pa...

Страница 3: ... pressing and holding the Test Hush button The horn will sound and the radio frequency RF signal will be transmitted Green light turns red while RF message is transmitted Replace sensor module after 5 years operation see page 25 When the CO Alarm detects abnormal levels of CO above 50ppm CO the red light starts to flash the horn will sound within 90 minutes and the RadioLINK signal will be transmi...

Страница 4: ... has stopped If the alarm has been silenced by pressing the Test Hush button wait at least 5 minutes The alarm will then check that the CO has cleared 7 Do not use the fuel appliances again until they have been checked by an expert In the case of gas appliances this must be a Registered Gas Installer Note If the Ei262 Carbon Monoxide Alarm is interconnected to Smoke Heat Alarms quickly press the L...

Страница 5: ...in rapid damage to the heart and brain from oxygen starvation High levels of CO in a house can be caused by Incorrectly or poorly installed fuel burning appliances Blocked or cracked chimneys flues Blocked vents or draught proofing which makes areas with fuel burning appliances or fireplaces airtight Engines of cars lawnmowers etc left running in confined spaces Portable paraffin or gas heaters in...

Страница 6: ...al headaches within 1 2 hours life threatening after 3 hours also maximum parts per million in flue gas on an air free basis according to US Environmental Protection Agency 800 Dizziness nausea and convulsions within 45 minutes Unconsciousness within 2 hours Death within 2 3 hours 1 600 Headache dizziness and nausea within 20 minutes Death within 1 hour 3 200 Headache dizziness and nausea within 5...

Страница 7: ...arm Response unless it has been in alarm see 2 4 CO Alarm Memory overleaf If your CO Alarm sounds follow the instructions on page 4 When ventilation is provided by leaving windows and doors open the CO build up may have dissipated by the time help arrives and the alarm may have stopped sounding Although your problem may appear temporarily solved it is crucial that the source of the CO is determine...

Страница 8: ... previously detected CO and been in alarm The flash rate indicates the level of CO detected as below Alarm Red light is Off No CO detected since reset or power up Alarm Red light flashes 2 times in 2 seconds every 40 seconds 50 ppm CO detected for approximately 90 minutes since reset or power up Alarm Red light flashes 4 times in 2 seconds every 40 seconds 100 ppm CO detected for approximately 40 ...

Страница 9: ...iance Locate a CO Alarm in a room where the occupant s spend most of their time e g living room In a bedsit the CO Alarm should be placed as far away from the cooking appliance as possible but near to where the occupant sleeps If the appliance is in a room not normally used such as a boiler room the CO Alarm should be placed just outside the room so that the alarm will be heard more easily 3 2 UNS...

Страница 10: ...hould be located at a height greater than the height of any door or window but still be at least 150mm from the ceiling If it is mounted on the ceiling it should be at least 300mm from any wall or light fitting The CO alarm should be a horizontal distance of between 1m and 3m from the potential CO source If there is a partition in the room the CO Alarm should be located on the same side of the par...

Страница 11: ... m DEAD AIR DON T LOCATE HERE CO Alarm Figure 1 Location in room with a fuel burning appliance 1 to 3m from appliance Ceiling 300mm min from walls Wall 150mm vertically down from ceiling B16587 R0 262 UC ENG 15 4 09 3 38 PM Page 11 ...

Страница 12: ... Location in bedroom rooms remote from the appliance Figure 2 Location in rooms with sloped ceilings 300mm from apex of ceiling High side of the room Wall mounted Breathing level approx 1 to 2m above floor B16587 R0 262 UC ENG 15 4 09 3 38 PM Page 12 ...

Страница 13: ...ed including floor coverings and the building has been fully cleaned The wiring can be installed when appropriate Excessive dust and debris from building work can contaminate the sensor and cause problems it will also invalidate the guarantee If it must be installed cover it completely particularly around the edges with a suitable covering until all cleaning is finished LOCATION FOR TAMPERPROOF SC...

Страница 14: ...d off by a switch Caution Alternative Energy Sources Wind Solar UPS etc This product must be connected to a Pure or True Sine Wave 230 Vac supply It must not be connected to devices giving a Modified Sine Wave or Quasi Sine Wave 230 Vac such as most inverters connected to solar panels wind turbines water turbines or batteries This also applies to battery powered UPS Uninterruptible Power Supply in...

Страница 15: ...ck for Live using a neon tester check that the Interconnect wire is NOT connected to Live Neutral or Earth Do not use an Earth wire for the Interconnect line Note The Alarm does not need to be earthed However the terminal marked is provided for the convenience of the installer so that any copper Earth wire or cable coloured green yellow can be safely terminated 4 Lift off the wiring cover as shown...

Страница 16: ...adio aerial 8 Replace the wiring cover 9 Carefully line up the unit on the base and slide on 10 It is essential to House Code the RadioLINK Ei262 to ensure they will not accidently communicate with nearby systems even if you do not plan to use the RadioLINK feature yourself This is easily done as explained in Section 4 2 L N IC EARTH IF PRESENT L LIVE N NEUTRAL IC INTERCONNECT TERMINAL SCREWS RECE...

Страница 17: ... knockout in the sidewall of the mounting plate as shown in Figure 4 and inserting the self tapping screw 3mm diameter 12mm long after the unit is on the mounting plate 4 2 RadioLINK for interconnecting etc The Ei262 will transmit an RF alarm signal when it detects potentially dangerous levels of CO This RadioLINK Alarm signal can be used to 1 Wirelessly interconnect to other Ei Electronics RadioL...

Страница 18: ...11H3 Remote Control 4 2 1 Interconnection After all the RadioLINK devices have been installed they must all be house coded as follows Housecoding your alarm 1 Press and hold the housecode switch on the bottom of the cover with a small screwdriver until the green power light turns red see figure 7 2 Immediately release the switch and the light will flash red alternating with green quickly a few tim...

Страница 19: ... all other units Check that the RadioLINK Indicator lights on all other units have stopped flashing red If some units are still flashing it may indicate a problem with the radio communication from this unit to the other units or these devices may have to be taken out of house code mode manually see their instruction manuals Repeat the process once more and if this fails see Section 14 Troubleshoot...

Страница 20: ...be observed as each unit turns on its RadioLINK Indicator light as a RadioLINK message is being repeated Note If it is necessary to disable the Repeater function see section 12 page 34 Technical Specification 4 2 2 RadioLINK Accessories When using RadioLINK accessories simply install all the devices as per their instructions first Then follow the house coding and checking procedure described in 4 ...

Страница 21: ...aximum of 250 metres 820 ft of wire can be used maximum resistance between detectors 50 Ohms Connect as shown in Figure 8 Alarms should be interconnected only within the confines of a single family living unit If they are connected between different units there may be excessive nuisance alarms Everybody may not be aware that they are being tested etc 21 L N IC L N IC IC INTERCONNECT MAINS POWER TO...

Страница 22: ...ed system it is on the Ei1529RC Remote Control to silence all the alarms except the one sensing danger If a Remote Control was not fitted find the alarm with its red alarm light flashing rapidly if it is a Carbon Monoxide Alarm follow the instructions on page 4 If it is a fire evacuate everybody from the premises closing all doors as you leave call the Fire Brigade and follow the other emergency i...

Страница 23: ...his is equivalent to pressing the Test button on the Alarm For further information see ACCESSORIES section 5 2 4 If the Alarm gives a short beep and the amber fault light flashes every 40 seconds it means the self checking circuit has detected a fault Press and hold the Test Hush button If the amber light flashes without the horn sounding the sensor is faulty 5 2 5 If the Alarm fails to operate wh...

Страница 24: ... Alarm is sounding the red alarm light on the cover will be flashing Testing both your CO Alarms and Smoke Heat Alarms weekly will help you and your family to clearly distinguish between them in an emergency Note When the Test Button is pressed on the CO Alarm the red alarm light does not flash unless the CO memory was activated If CO Alarms and Smoke Heat Alarms are interconnected and are all sou...

Страница 25: ...after 5 years operation or by the date on the REPLACE SENSOR BY label on the side of the unit After 5 years operation the amber light will flash once every 40 seconds without a beep to indicate the sensor should be replaced It must also be replaced if the amber light flashes and the unit beeps every 40 seconds as this indicates the sensor is faulty 1 Remove the alarm from the mounting plate as des...

Страница 26: ...air draughts and obstructions can prevent the CO from reaching the Alarm For these reasons we recommend CO Alarms are fitted both near and in bedrooms particularly if bedroom doors are closed at night Additionally install in rooms where members of the household spend much of their time and in rooms with potential sources of CO gas The CO Alarm may not be heard The sound output is loud but it may n...

Страница 27: ...e presence of natural gas methane bottled gas propane butane or other combustible gases Fit combustion gas alarms to detect these WARNING THIS CO ALARM IS DESIGNED TO PROTECT INDIVIDUALS FROM THE ACUTE EFFECTS OF CARBON MONOXIDE EXPOSURE IT WILL NOT FULLY SAFEGUARD INDIVIDUALS WITH SPECIFIC MEDICAL CONDITIONS IF IN DOUBT CONSULT A MEDICAL PRACTITIONER 8 2 Radio Communications Ei Electronics radio ...

Страница 28: ...more of the following measures i Re orientate or re locate the unit ii Increase the distance between the Ei262 CO Alarm and the device being affected iii Connect the device being affected to a mains outlet on a circuit different from the one that supplies the Ei262 iv Consult the supplier or an experienced radio television technician 9 HOW TO PROTECT YOUR FAMILY Follow these guidelines to reduce t...

Страница 29: ...or closed Never leave the door from the house to the garage open if the car is running Never adjust your own gas pilot lights Never use a gas cooker or a barbecue for home heating Children should be warned of the dangers of CO poisoning and instructed never to touch or interfere with the CO Alarm Do not allow small children to press the Test Hush button as they could be subjected to excessive nois...

Страница 30: ... guarantees this Carbon Monoxide Alarm for five years from the date of purchase against any defects that are due to faulty materials or workmanship This guarantee only applies to normal conditions of use and service and does not include damage resulting from accident neglect misuse unauthorised dismantling or contamination howsoever caused This guarantee excludes incidental and consequential damag...

Страница 31: ...270 independently tested Test Hush Button Checks electronics and horn When the unit is alarming after sensing CO pressing the Test Hush button will immediately stop the horn the red alarm light will continue to flash If CO is still present the red alarm light and the horn will turn on again after about 4 minutes The unit can only be silenced once during a CO incident At 300 ppm CO the unit cannot ...

Страница 32: ...ts coded up to 12 units the flashes are every 5 seconds above 12 units the flashes are every 10 seconds to indicate the number of House Coded units in the system Duration of House Code Mode Exits mode automatically after 30 minutes Alternatively manually exit by pressing the house code button this sends a RadioLINK exit house code signal to all other RadioLINK devices which can act on it Clearing ...

Страница 33: ...i261RC Smoke Heat Fire Alarms can be interconnected provided that an Ei1529RC Remote Control is used Wireless Interconnect Up to 12 Ei262 CO Alarms can be interconnected so that when one senses CO all alarm Alternatively up to a combined total of 12 Ei262 CO Alarms and Ei161RC Ei164RC Ei166RC Ei2110 Smoke Heat Fire Alarms on an Ei168RC RadioLINK base can be interconnected provided that an Ei411H3 ...

Страница 34: ...e System Control Ei411H3 for use with models Ei161RC 164RC 166RC Ei2110 Alarm on an Ei168RC Base Ei262 CO Alarm only The RadioLINK System Control Switch is recommended for systems with at least one Carbon Monoxide Alarm and three or more Smoke Heat Fire Alarms It allows the user to perform the following functions from a remote location LOCATE If alarms sound press Locate to allow source of alarm t...

Страница 35: ... Switch is recommended for systems with at least one Carbon Monoxide Alarm and three or more Smoke Heat Fire Alarms It allows the user to perform the following functions from a remote location LOCATE If alarms sound press Locate to allow source of alarm to be identified audibly HUSH Press Hush to silence nuisance alarms TEST Operate weekly to Test the alarms MAINS CHECK Test will not work with mai...

Страница 36: ...eady been House Coded correctly in the system It is important therefore to check that all detectors are communicating in their final installed positions If units are rotated and or resited we recommend that all units are returned to the factory settings see section 12 Technical Specifications on how to clear house codes Then House Code all units again in their final positions as per Section 4 Inst...

Страница 37: ...ing re occurs replace the sensor module 3 ALARM BEEPS EVERY 40 SECONDS without amber light flashing Rechargeable cells depleted Reconnect mains power if green light is off 4 ALARM SOUNDS FOR NO APPARENT REASON Follow the detailed instructions in Section 1 on page 4 entitled WHAT TO DO WHEN THE ALARM SOUNDS If there are still problems Ensure there are no fuel burning appliances in the vicinity whic...

Страница 38: ...is sensing CO Smoke Heat Alternatively if an optional Ei411H3 RadioLINK Remote Control is fitted to a RadioLINK system pressing the LOCATE switch when all the alarms are sounding will silence all alarms apart from the alarm that is sensing CO or fire This area can then be safely investigated and if determined that it is a false alarm press the HUSH switch to silence the alarm 38 The crossed out wh...

Страница 39: ...39 B16587 R0 262 UC ENG 15 4 09 3 38 PM Page 39 ...

Страница 40: ...bury Rd Oswestry Shropshire SY10 8NN U K Tel 0870 758 4000 www aico co uk Ei Electronics Shannon Co Clare Ireland Tel 353 0 61 471277 www eielectronics com Ei Electronics 2009 P N B16587 Rev 0 B16587 R0 262 UC ENG 15 4 09 3 38 PM Page 40 ...