background image

4. TESTING AND MAINTAINING YOUR SYSTEM

4.1 AFTER INSTALLATION

4.1.1 Check that all RadioLINK Alarms and Accessories are powered correctly.

4.1.2 Check that the green light on the Ei171RF Strobe Module is continuously lit.

4.1.3 Press the test button on all RadioLINKED Smoke/Heat/Fire Alarms, Remote Controls and
Manual Call Points in turn, and check that all other Smoke/Heat/Fire Alarms in the system alarm after
about 4 seconds and that the Strobe Light Module activates. Also check that the RadioLINK
accessories were operated.

N.B. Wait 12 seconds before testing the next unit or if you wish to repeat testing.

4.1.4 Press the Strobe Module test button. Check that the strobe flashes and the red alarm light on
the Strobe Module flashes (this will also cause the Smoke/Heat/Fire Alarms to sound and also their
red lights to flash rapidly, and any other additional Strobe Module to flash).

4.2 DAILY & WEEKLY TESTING

Check daily that the green light on the Strobe Module is on constantly. We recommend that you test
your system weekly by pressing all the smoke/heat/fire alarm test buttons and checking that the strobe
light operates.

Check the Strobe Module indicator lights as follows (see figure 4)

4.2.1 Green mains power should be constantly on. If it is off check that it is plugged into the mains,
that the socket is not switched off, fuses, circuit breakers etc. If the mains is off, the green light will be
off and the unit will be running on the rechargeable battery. The green light will be replaced by an
amber flash every 4 seconds to indicate battery is satisfactory. When this amber flash stops, the
battery is depleted and the mains should be reinstated (If the mains cannot be reinstated at this time,
the depleted battery should be removed, until the mains can be re-connected).

4.2.2 Press the Test button on the Strobe Module and check that the strobe flashes, the red alarm light
flashes and that the blue RadioLINK light illuminates on for about 3 seconds indicating the radio test
signal is being sent to the Smoke/Fire/Heat alarms and any accessories.

4.2.3 Check that the amber fault light is not flashing every 4 seconds. If it is check that the conversion
jack is connected firmly to the socket with its plug latched (see figure 1). If this connection is
satisfactory, it is probably indicating that the battery is depleted. Connect the unit to the mains and
check after 24 hours that the amber fault light has ceased flashing.

4.3 PERIODIC TESTING OF RECHARGEABLE BATTERY

4.3.1The rechargeable battery can take up to 20 hours to charge when the unit is first powered up. It is
then maintained in a fully charged state by continuous trickle charge. In the event of a mains failure the
battery will power the system in standby for a week and then be capable of at least 4 minutes of alarm.
If the mains fails, the green light is extinguished and the amber light flashes every 4 seconds on the
Strobe Module to indicate it is on battery power. The amber light will also flash every 4 seconds if the
battery is almost depleted. Both the amber lights will go off to indicate the battery is depleted and the unit
is totally unpowered. The battery will last 5 years in normal use provided it is not exposed to extremes of
temperature for prolonged periods, or fully discharged & charged a large number of times.

We recommend that the functioning of the rechargeable battery is checked at least yearly as follows:-

4.3.2 Ensure the Strobe Module has been mains powered for at least the previous 20 hours for the 
battery to charge.

4.3.3 Turn off the mains power to the unit by unplugging it or switching off the circuit at the distribution
board. Check that the green light goes off and the amber light starts to flash.

4.3.4 Press the Strobe Module test button for 20 seconds and check the strobe flashes brightly and
that all the RadioLINK alarms trigger. Check that the red alarm light flashes while the test button is
pressed. (Cover the strobe light with a card to stop this dazzling you while looking at the red light). If
the red light goes off, or if the strobe is weak, the battery will need to be replaced. Contact the nearest
address in this leaflet for advice about getting a replacement.

6

B16566-R0-Ei171RF-ENG-UC  2/9/09  2:54 PM  Page 6

Содержание RadioLINK Ei171RF

Страница 1: ...arm is required to make the Ei171RF Alarm operational This is not supplied with the Ei171RF and must be obtained separately Important Read these instructions together with those from the separate RadioLINK Smoke Heat Fire alarms and accessories before installation All instruction leaflets must be left with the end user after installation Model Ei171RF B16566 R0 Ei171RF ENG UC 2 9 09 2 54 PM Page 1...

Страница 2: ... normally be fixed such that the internal strobe light can be seen from the bed An additional strobe module can be then placed in any other living area of the house which can be readily seen by the occupant It has to be powered from the mains 230VAC so a suitable socket or junction box must be available to which it can be permanently connected The back up battery in the Strobe Module must not be e...

Страница 3: ...let can be used to locate the screws accurately The screws large heads should be screwed into the wall leaving a gap of approximately 4mm 0 15in under the head Fit the keyhole slots on the back of the Strobe Module over the screw heads and slide the panel down vertically into position The mains adaptor should then be plugged into a socket or permanently wired to a mains junction box see overleaf T...

Страница 4: ...so that they will not accidentally signal to or be affected by nearby systems The units will all communicate with each other providing they are within range as delivered i e without any House Coding however it is recommended that they are House Coded as follows 3 1 1 Install power all the elements of the system 3 1 2 Press the House Code switch on all units see individual instruction leaflets for ...

Страница 5: ...n as this will put it back into House Code Mode 3 2 ADDING UNITS To add units to the system simply repeat the above procedure i e put all into House Code Mode new as well as old units and ensure that the number of flashes shown equals the number of units in the system For the other RadioLINK components see their instruction leaflets 3 3 RESETTING HOUSE CODES Sometimes it is necessary to cancel the...

Страница 6: ...moke Fire Heat alarms and any accessories 4 2 3 Check that the amber fault light is not flashing every 4 seconds If it is check that the conversion jack is connected firmly to the socket with its plug latched see figure 1 If this connection is satisfactory it is probably indicating that the battery is depleted Connect the unit to the mains and check after 24 hours that the amber fault light has ce...

Страница 7: ...iary devices can be plugged in see figure 5 These plugs can be removed by pressing the latch lever on the side nearest the AUX marking before gently pulling the plug off Clock Input Socket not available without a vibration pad A suitable alarm clock signal with a 5 to 24 Volts AC or DC output electrically isolated from the mains supply can be connected to this input socket with a 3 5mm mono jack p...

Страница 8: ...es to normal conditions of use and service and does not include damage resulting from accident neglect misuse unauthorised dismantling or contamination howsoever caused This guarantee excludes incidental and consequential damage If this device should become defective within the guarantee period it must be returned to the nearest address given below carefully packaged with the problem clearly state...

Страница 9: ...mplate for Mounting Screws Drill Holes Here 12V 180mA max Aux1 12V 20mA max Aux2 Conversion Jack Remove protection plug before connecting accessories Figure 5 B16566 R0 Ei171RF ENG UC 2 9 09 2 54 PM Page 9 ...

Страница 10: ... battery fully depleted Sensing Fire Fire signal received from Smoke Alarm __ __ __ __ Test Mode Test button pressed on deaf alarm 1 flash 2 sec __ __ __ __ 40 flashes min on for 4 sec flashes on 1 flash 2 sec __ __ __ Test button pressed on deaf alarm Fault Mode Conversion Jack disconnected 40 flashes min on __ __ __ __ __ __ __ __ Battery disconnected mains on House Code Mode for RF Press button...

Страница 11: ... Green mains disconnected amber flash 4 seconds RadioLINK Signalling Blue Control Panel Indicators Alarm Red Fault Indicator Amber Strobe TEST ALARM FAULT INDICATOR SUMMARY B16566 R0 Ei171RF ENG UC 2 9 09 2 54 PM Page 11 ...

Страница 12: ...s that this product should not be disposed of via the normal household waste stream Proper disposal will prevent possible harm to the environment or to human health When disposing of this product please separate it from other waste streams to ensure that it can be recycled in an environmentally sound manner For more details on collection and proper disposal please contact your local government off...

Отзывы: