background image

• Near a 

decorative object, door, light fitting, window 

moulding

 etc., that may prevent smoke or heat from 

entering the Alarm.

• Surfaces that are normally warmer or colder than the rest of 

the room (e.g. 

attic hatches

). Temperature differences might 

stop smoke or heat from reaching the unit.

• Next to or directly above 

heaters

 or 

air conditioning vents, 

windows, wall vents

 etc. that can change the direction of 

airflow.

• In very 

high

 or 

awkward areas

 (e.g. over stairwells) where 

it may be difficult to reach the alarm (for testing, hushing 

or battery replacement).

• Locate away from very 

dusty

 or 

dirty areas

 as dust build-up 

in the chamber can impair performance. It can also block the 

insect screen mesh and prevent smoke from entering the 

smoke detector chamber.

• Locate the unit at least 1m from 

dimmer controlled lights 

and wiring

 as some dimmers can cause interference.

• Locate unit at least 1.5m and route wiring at least 1m away 

from 

fluorescent light fittings

 as electrical “noise” and/or 

flickering may affect the unit. Do not wire into the same 

circuit as fluorescent lights or dimmers. 

• Do not locate in 

insect infested areas

. Small insects getting 

into the smoke detector chamber can cause intermittent 

alarms. Insects and contamination on the Heat Alarm 

sensor can increase its response time.

The Alarm is designed to be permanently mounted, 

using it’s own built-in terminal block to connect it to the 

mains. The mounting plate can be screwed directly to 

the ceiling. Alternatively it can be screwed to a standard 

junction box. It requires a current of 40mA. The Alarm 

must not be exposed to dripping or splashing. There are 

important markings on the underside of the alarm.

Caution
Alternative Energy Sources 

- (Wind, Solar, UPS etc.)

This product is designed to be connected to a Pure or 

True Sine Wave 230 Vac supply.
If connecting to a power source that utilises an inverter, 

e.g. PV solar panel, the Total Harmonic Distortion (THD) 

must be less than 5%. If in doubt please check with the 

manufacturer of the inverter.
This also applies to battery powered UPS (Uninterruptible 

Power Supply) inverters.

Light Dimmer Circuits

 – The Alarms 

must not

 be 

powered from a light dimmer circuit.

IMPORTANT PRECAUTION:

 

Do not install the 

Alarms in new or renovated buildings until all work 

is completed (including floor coverings) and the 

building has been fully cleaned. The wiring can be 

installed when appropriate. (Excessive dust and 

debris from building work can contaminate the 

smoke chamber or heat sensor and cause problems, 

it will also invalidate the guarantee). If it must 

be installed, first cover it completely, particularly 

around the edges, with a dust cover (eg. with the 

elasticated cover supplied or a plastic bag), until all 

cleaning is finished.

The Alarm must not be connected when the house wiring 

insulation is being checked with high voltages. i.e. Do 

not use a high voltage insulation tester on the alarm.

13

Installation

Содержание EIB140RC Series

Страница 1: ...erconnected so that when one senses fire all the units alarm Interconnection can be achieved by hardwire or through a RadioLINK Base the EIB168RC A green LED indicates the presence of mains power A red LED will flash rapidly in an alarm scenario All Alarms feature a combined test hush button The Test Hush button will either silence false alarms or perform a unit self test In Test mode the Alarm wi...

Страница 2: ...onnectors Use only 9V Alkaline batteries Duracell MN1604 Energizer 522 Other batteries can cause problems We recommend that the replace by date on the battery should still have at least 2 years to go Older batteries will give beeps prematurely 6 Slide unit back on to the base A click should be heard as the alarm engages The unit cannot be replaced on the base unless a battery is installed 7 Press ...

Страница 3: ... pressing the button for 10 seconds All the units should alarm within 10 seconds of the first horn sounding The red light on the first unit only will flash about once a second On releasing the button the local Alarm will stop sounding immediately and the remote Alarms will stop sounding approximately 3 seconds later if testing using RF interconnection this could take slightly longer This will veri...

Страница 4: ...omer servicing of this product is required Repairs when needed must be performed by the manufacturer All Alarms are prone to dust and insect ingress which can cause nuisance false alarms or failure to alarm In certain circumstances even with regular cleaning contamination can build up in the smoke sensing chamber causing the Alarm to sound or fail If this happens the alarm must be returned to us f...

Страница 5: ...d very large levels of smoke from a nearby fire will override the silence period The unit will flash the red light every 10 seconds instead of the normal 40 seconds to indicate the sensitivity is reduced On interconnected Alarms pressing the Test Silence Button on the one sensing smoke i e the one with the red light flashing every second will silence all alarms Pressing the Silence Button on any o...

Страница 6: ...ailing air draughts carry the smoke heat away Installing Smoke Heat Alarms on both sides of closed doors and installing more than one Smoke Heat Alarm as recommended in the INSTALLER INSTRUCTIONS section significantly improves the probability of early detection The Alarm may not be heard A Smoke Heat Alarm may not wake a person who has taken drugs or alcohol Smoke Heat Alarms may not detect every ...

Страница 7: ...nected units the red light on the cover will flash rapidly only on the unit which is the source of the alarm If an optional EIB1529RC Control Switch or an EIB450 Alarm Controller is installed press Locate when the system is sounding to identify source of alarm 2 Check for fumes steam etc from the kitchen or bathroom Paint and other fumes can cause nuisance false alarms 3 Press the test silence but...

Страница 8: ...ks Australia PTY Ltd 4 Pike Street Rydalmere NSW 2116 Australia Tel 0296841466 www brooks com au Ei Electronics Shannon Co Clare Ireland Tel 061 471277 www eielectronics com Contact Us Conforms To AS3786 2014 ...

Страница 9: ...GES SLIDE ON ALARM 3 LOCATE THE ARROW ON THE FRONT FACE OF THE ALARM THE SLOT IS LOCATED DIRECTLY ABOVE THE ARROW INSERT A FLAT BLADED SCREWDRIVER HORIZONTALLY APPROX 1cm INTO THE CENTRE OF THE REMOVAL SLOT LOCATE REMOVAL SLOT INSERT SCREWDRIVER 1 WITH THE SCREWDRIVER STILL INSERTED PUSH THE LOWER HALF OF THE ALARM AWAY FROM THE SCREWDRIVER IN THE DIRECTION OF THE ARROW ON THE COVER SLIDE ALARM OF...

Страница 10: ...portant that nuisance false alarms are minimised to ensure the units are not disabled or ignored The Australian Standard AS1670 1 gives guidance on how many Alarms to install what type of Alarm to use where to position Alarms The above points will depend on the type of dwelling to be protected and the level of fire risk Fire Risk Assessment The number of smoke and or heat Alarms that need to be in...

Страница 11: ...cumstances recognises that a warning will only be given by the Heat Alarm when there is a very significant flaming fire in the room The door s and windows associated with the Heat Alarm must be closed to contain the fire and heat If the fire and heat are not contained it is extremely unlikely that the Heat Alarm would respond before a Smoke Alarm sited outside in the corridor 4 In enclosed kitchen...

Страница 12: ...ould only be considered where close spaced beams or similar obstructions may preclude ceiling mounting It is considered to be the responsibility of the installer client to determine if the presence of asbestos in the ceiling material would make ceiling mounting impractical Locations To Avoid DON T place Smoke Alarms in any of the following areas Bathrooms kitchens shower rooms garages or other roo...

Страница 13: ...built in terminal block to connect it to the mains The mounting plate can be screwed directly to the ceiling Alternatively it can be screwed to a standard junction box It requires a current of 40mA The Alarm must not be exposed to dripping or splashing There are important markings on the underside of the alarm Caution Alternative Energy Sources Wind Solar UPS etc This product is designed to be con...

Страница 14: ...r marked L N Neutral connect to the house wires coloured blue or marked N See page 16 for information on interconnection Note Wiring must be installed in compliance with AS3000 Warning Mixing the Live and Neutral connections when interconnecting alarms will damage all the alarms ensure that the same colours are used throughout the premises for Live Neutral and Interconnect wires We strongly recomm...

Страница 15: ... recessed wiring ensure the rear gasket seals around the edge of the hole in the ceiling or wall This is to prevent air draughts affecting the smoke heat entering the Alarm If the hole is too large or the Alarm does not seal it it should be sealed with silicone rubber or equivalent 6 Attach the battery to the battery snaps Carefully line up the unit on the base and slide on 7 Press and hold the te...

Страница 16: ...move any nuisance units i e units with red light flashing rapidly which are causing all the other Alarms to sound WARNING Do not connect these Alarms to any other model produced by another manufacturer Doing so may damage the Alarms and could result in a shock or fire hazard Wiring must be installed in compliance with AS3000 230V supply Brown red or marked L Neutral Blue black or marked N Intercon...

Отзывы: