6. INTERCONNECTING YOUR SMOKE ALARM

A maximum of 12 Ei 3105TYC/TYCH or Ei 100TYC Smoke
Alarms may be wired together such that when one unit
senses smoke all other units sound a warning. This helps
ensure smoke alarms will be heard. Do not connect to any
other device as it may damage the unit or affect performance.
A maximum of 250 metres (820ft) of signal cable can be used,
(maximum resistance between detectors 50 ohm). The units
are interconnected by wiring all the terminals marked 1
together, and all the terminals marked 2 together (as in figure
9) before screwing to ceiling. Draughts, through the ceiling,
from wiring openings, conduit, or mounting boxes/holes, may
blow smoke away from the sensing chamber, making it
insensitive. It is essential that all such openings including the
wiring hole (see figure 9) be closed by silicone sealant or
similar.
After wiring together the Interconnect Smoke Alarms, test the
first unit by pressing the button. All the detectors should alarm
and the test button on the first unit will flash about once a
second. Please note it can take up to 5 seconds for some of
the interconnected units to sound. Check all the other units
similarly.
These Smoke Alarms should be interconnected only within
the confines of a single family living unit. If they are connected
between different units there may be excessive nuisance
alarms. Everybody may not be aware that they are being
tested or that it is a nuisance alarm caused by cooking etc.

7. IMPORTANT SAFEGUARDS

When using household protective devices, basic safety
precautions should always be followed, including those listed
as follows:

11

Figure 9

B14355-R4-TY-UC-ENG-3105  21/12/10  1:30 PM  Page 11

Содержание Ei 3105TY

Страница 1: ...with a plastic bag or similar before renovations begin Ei Electronics 2008 P N B14355 Rev4 10 YEAR SMOKE ALARM WITH 10 YEAR LITHIUM BATTERY BUILT IN INSTRUCTION LEAFLET Contains vital information on...

Страница 2: ...ht flashes at the same time it indicates the battery is depleted and the entire alarm must be replaced This normally occurs when over 10 years has elapsed 2 LOCATING YOUR SMOKE ALARM Sufficient smoke...

Страница 3: ...long one Smoke Alarm will not be sufficient This is because no matter where it is located it will be more than 7 5 metres from potential fires Recommended locations Figures 1 2 3 for minimum protecti...

Страница 4: ...occur for instance where there is an electrical appliance such as an electric blanket or heater or where the occupant is a smoker You could also consider putting Smoke Alarms in any rooms where the o...

Страница 5: ...d ceilings install your Smoke Alarm 0 9m from the highest point measured horizontally see figure 5 because dead air at the apex may prevent smoke from reaching the unit 3 4 Locations to Avoid Don t pl...

Страница 6: ...should get your family into a safe place before you start investigating Check the house carefully in case there is a small fire smouldering somewhere Check whether there is some source of smoke or fu...

Страница 7: ...ical wiring in the ceiling drill holes through the centres of the marked locations Push the plastic screw anchors provided into the drilled holes Screw in firmly 4 2 Connecting the built in Lithium Ba...

Страница 8: ...to 10 seconds Figure 7 The alarm will stop sounding shortly after the button is released If the alarm fails to sound follow this checklist Check the age of the unit see replace by label on base of un...

Страница 9: ...while cleaning Do not vacuum or brush inside the Smoke Alarm To clean the cover remove it completely and use only mild soap and water Dry cover thoroughly before replacing it WARNING Do not paint you...

Страница 10: ...End of life The entire Smoke Alarm must be replaced if i The unit is installed for over 10 years check the replacement year marked on the unit ii The unit is giving a short beep every 40 seconds and...

Страница 11: ...ential that all such openings including the wiring hole see figure 9 be closed by silicone sealant or similar After wiring together the Interconnect Smoke Alarms test the first unit by pressing the bu...

Страница 12: ...larm see Getting your Smoke Alarm Serviced page 15 This appliance is intended ONLY for premises having a residential type environment This is not a portable product It must be mounted following the in...

Страница 13: ...ton to familiarize your family with the Alarm sound and to practice fire drills regularly with all family members Draw up a floor plan that will show each member at least 2 escape routes from each roo...

Страница 14: ...mouldering cigarettes and ashes Service central heating systems regularly Be sure all electrical appliances and tools have a recognised approval label This device cannot protect all persons at all tim...

Страница 15: ...sed and the date of purchase FIVE YEAR GUARANTEE Limited Ei Electronics guarantees this product against any defects that are due to faulty material or workmanship for a five year period after the orig...

Страница 16: ...nt or to human health When disposing of this product please separate it from other waste streams to ensure that it can be recycled in an environmentally sound manner For more details on collection and...

Отзывы: