EHC Fusion Comet EHCCOM12KW Скачать руководство пользователя страница 4

 4

GB-031C_f

InsTallaTIOn

1. General

The boiler must be installed by a professional plumber or heating 

engineer  and  must  be  connected  to  the  public  low  voltage 

network by a competent person. For systems that require a three 

phase electrical supply we strongly recommend this is installed 

by a 17th Edition certified Electrician.

The Electric heating Company ltd will not be held responsible 

for  faulty  installations  which  are  performed  by  unqualified 

tradespersons.

2. Pipe Connections

All Fusion Electric Boilers have a 22mm compression connection 

at the boiler’s flow and return pipes. Please note that the boilers 

are supplied with blank washers fitted for transit purposes. These 

must be removed before connections to pipe-work can be made.

The flow (red) and return (blue) are clearly marked on the external 

case  and  under  no  circumstances  should  these  connections  be 

reversed. Hot connections are not recommended at the boiler for 

future maintenance and boiler disconnection. Lockshield valves 

are recommended.

3. Case Removal

Remove outer screws at the bottom of the boiler and pull the front 

cover outwards taking care to remove internal earth connections.  

Earth connections must be re-connected before the boiler case is 

re-installed.

4. Isolation Valves

We recommend that lockshield isolation valves are fitted on the 

flow and return pipework. Such valves must be „full bore” and not 

„standard ball valves”. The installation of „standard ball valves” in 

the flow and return pipework will reduce the recommended flow 

rate through the boiler and promote premature boiler shutdown.

5.  auto air vents

An auto air vent is integral within the boiler however an additional 

auto air vent must be fitted at the cylinder coil if the boiler is being 

used for central heating and domestic hot water.

6.  Boiler sizing

Calculate the „space heating” requirements in accordance with BS 

EN 12831 and BS EN 14336. If the boiler is to heat the domestic 

hot water, an additional allowance of 3kW (10,239 Btu’s) should 

be made to the ‘space heating’ calculation.

7. Insulation

Where  practical,  and  if  at  all  possible,  we  recommend  that  all 

pipe-work  be  insulated,  in  particular  the  primary  pipe-work 

within a boiler cupboard. This is to reduce heat loss and reduce 

high cupboard temperatures from exposed pipe-work. (BS 6700).

8. system Design

The  boiler  has  an  integral  automatic  bypass  valve  fitted  which 

should  be  set  to  the  relevant  settings  to  allow  the  minimum 

flow rates to pass through the boiler (8 l/min) when all radiator 

thermostats and zone valves are  closed.

Allowance should be made for a radiator to be installed within 

the heating circuit and locked open. This will be located in the 

room that has the room thermostat installed. 

To comply with building regulations, Part L and Part J (in Scot-

land), room and cylinder stats must be fitted.

9. Water Connections

Provisions must be made  for the replacement of water lost from 

the heating system (sealed systems). Reference should be made 

to BS EN 14336 for the method of filling and make up of water.

There must be no direct connection between the boilers central 

heating system and the main water supply. When mains water is 

required to fill the system directly, all local water bylaws must be 

observed, and any connection made must be disconnected after 

use.

10. Flushing

The system 

must be flushed

 to within 10% of mains water PPM to 

ensure that no debris is trapped in the system as this may result in 

boiler failure. Where existing radiators and pipe-work are utilized 

a power flush must be carried out to remove debris. For further 

guidance please see section - Flushing & System Protection.

11. system pressures 

All  boilers  are  tested  to  4.0  bar.  The  normal  working  pressure 

of  the  boiler  should  be  set  to  approx  1.0  /  1.5  bar.  All  sealed 

systems should comply with the relevant building regulations and 

standards, including BS EN 13831 – Specification for Expansion 

Vessels. 

Please note:

In order to protect the Flow Sensor located within the boiler, it is 

imperative that the pre-installed magnetic filter is removed and 

cleaned  at  least  annually.  Failure  to  carry  out  this  action  will 

increase contamination of the boiler by system residue.

12. system types

The Fusion Comet range of boilers can be used in various system 

designs. Please refer to The Electric Heating Company for more 

details on our Fusion Boiler for under floor heating. We are able 

to supply a heat pack that contains the relevant control valves, 

cylinder and room thermostats required to configure an „S” plan 

heating system. The heat pack has all the necessary components 

that  you  need  to  connect  the  systems  controls  and  plumbing 

configurations for „S” Plan design.

We  recommend  the  use  of  thermostatic  radiator  valves  on  all 

radiators except in the room that has the wall thermostat fitted. 

This radiator should be fitted with lock shield valves and left in 

the fully open position.

The  boiler  has  an  integral  automatic  bypass  valve  fitted  which 

should  be  set  to  the  relevant  settings  to  allow  the  minimum 

flow rates to pass through the boiler (8 l/min) when all radiator 

thermostats and „zone valves are closed”.

Systems  should  be  designed  to  meet  the  current  building 

regulations in force at the current time.

13. hanging the Boiler

1.  Hang the boiler in a vertical position on the fixing points and 

screws provided, with the flow and return connections to the 

bottom of the boiler, maintaining the clearances as per Figure 

12 of this manual. 

2.  Connect the boiler to a heating system that is equipped with 

isolation valves (see Figures 4 & 5). 

3.  Fill  the  heating  system  with  treated  water,  which  will 

substantially extend the life of the heating coils. See item 14 

„System Protection” below. 

4.  Connect  the  boiler  to  the  „mains”  electrical  system  as  per 

Figures 6, 8, 9 & 11 

5.  Connect  the  room  thermostat  /  Programmer  using  the  two 

control conductors marked RP as in Figure 7 & 10.

6.  For  all  other  electrical  connections  refer  to  the  ELECTICAL 

CONNECTIONS & CONTROL section of this manual.

Содержание Fusion Comet EHCCOM12KW

Страница 1: ...ate solution for central heating Installation technical Manual If you require any further assistance Telephone 01698 820533 Fax 01698 825697 E mail info electric heatingcompany co uk or visit our website www electric heatingcompany co uk ...

Страница 2: ...nt back to The Electric Heating Company as soon as possible for registration An internal Magnetic Filter is fitted to the Boiler and it must be cleaned at least annually Note Failure to clean the Magnetic Filter may result in boiler shutdown Warranty calls will not be covered for this repair This appliance is not intended for use by persons including children with reduced physical sensory or menta...

Страница 3: ...l provide an adequate fixing and should be fitted in a location that the boiler and pipe work are not subject to frost and damp conditions 3 Central heating design installation Detailed recommendations are given in BS EN 12828 BS 6700 and CP 342 2 Pipes forming part of the useful heating surface should be insulated to prevent any potential heat loss or frost damage BS 6700 Drain valves should be f...

Страница 4: ...ement of water lost from the heating system sealed systems Reference should be made to BS EN 14336 for the method of filling and make up of water There must be no direct connection between the boilers central heating system and the main water supply When mains water is required to fill the system directly all local water bylaws must be observed and any connection made must be disconnected after us...

Страница 5: ...y Temperature limiter 7 Return connection 8 Flow connection 9 Power Board 10 Control Module 11 Automatic Vent 12 Expansion vessel 13 By pass Valve 14 Magnetic Filter PF Internal mains phase connections from the PN connection block PN Incoming mains cable connection block WP Electric cable access M Boiler fixing points RP External Controls Volt Free Electrical mains input ...

Страница 6: ...Add Fernox F3 cleaner to the system at the furthest point from the boiler this is to allow the substance to fully dilute throughout the system If you are unsure of the correct dose rate contact Fernox on 03301007750 for advice 3 Re fill the system and circulate the F3 cleaner prior to the boiler being fired up Commission the system in the normal way The cleansing agent must be in the system for a ...

Страница 7: ...lace pointed by arrow 6 If the LEDs are signalling a different operating mode than recommended in table 15 1 set the appropriate mode according to the following instructions press the pump arrow button for longer than 2 seconds but less than 10 seconds LED s will start to flash the pump then switches to the programming mode LEDs glows to indicate the current settings To change the settings of the ...

Страница 8: ...8 GB 031C_f Temporary Filling Loop Mains Water Supply INSTALLATION Figure 4 ...

Страница 9: ...9 GB 031C_f Figure 5 Temporary Filling Loop Mains Water Supply ...

Страница 10: ...LL WIRING MUST BE CARRIED OUT IN ACCORDANCE WITH CURRENT IEE BS7671 WIRING REGULATIONS ALL ELECTRICAL CONNECTIONS MUST BE MADE BY A QUALIFIED ELECTRICIAN Load check must be taken into consideration when installing high power boilers This will be carried out by a qualified electrician There may be an additional requirement to upgrade the incoming main fuse supplying the property if other high power...

Страница 11: ... Stat Connections The boiler PCB has a voltage free connection for the controls RP NA Under no circumstances should 240V be connected to these controller block connections as this will damage the boiler s PCB and Void the Manufacturers warranty The stat programmer connections are clearly marked within the boiler Only after all connections have been made and checked should the system be filled with...

Страница 12: ...4 16 15 N L N L 1 HTG 1 Call 3 EC10001 1 Channel COM Call Volt free Control Connections 3A Switched Fuse Isolator 6Amp 240V 50Hz Supply N NOTE RP are Volt free Contacts EXTERNAL CONTROL WIRING Figure 8 Heating Only Wiring Non Standard Volt Free Switching ...

Страница 13: ...EC10002 2 Channel EC10003 3 Channel COM Call Volt free Control Connections 3A Switched Fuse Isolator 6Amp 240V 50Hz Supply N NOTE RP are Volt free Contacts COM Call COM Call COM 16 Way Junction Box BL HC10008 HC10008 HC10008 HW Zone Valve HTG Zone Valve 1 HTG Zone Valve 2 BR GR OR BL BR GR OR BL BR GR OR Product EC10010 Description 16 Way junction box Optional 2nd heating zone 230V 10A 50Hz ClassI...

Страница 14: ...e Figure 10 SAFETY NOTE RP and NA are signal conductors only DO NOT CONNECT ANY VOLTAGE to these as this will damage the boiler and invalidate the boilers warranty Shower Sensor connection Optional External Volt Free Call Signal Programmer Thermostat ...

Страница 15: ...3 Grz 1 Grz 2 Grz 3 Grz 4 Grz 5 Grz 6 L1 L2 L1 L2 L3 L3 G1 G1 G2 G2 G3 G3 G4 G5 G5 G6 G4 G6 P R F N L PUMP L N red blue Ground Power supply 230 400V POWER BOARD CONNECTION 415V 3N 39kW Connection of power board 39kW 415V 3N ...

Страница 16: ...16 GB 031C_f POWER BOARD CONNECTION 415V 3N 14 4 23 kW Connection of power board 14 4 23kW 415V 3N Power supply 230 400V U N Ground H e 1 H e 2 H e 3 red blue L3 G3 L2 G2 L1 G1 N V W P R F N L PUMP L N ...

Страница 17: ...17 GB 031C_f POWER BOARD CONNECTION 240V 4 14 4kW Connection of power board 4 14 4kW 240V Power supply 230 400V U N Ground H e 1 H e 2 H e 3 red blue L3 G3 L2 G2 L1 G1 N V W P R F N L PUMP L N ...

Страница 18: ...18 GB 031C_f EXTERNAL BOILER WIRING BOILER DIMENSIONS Figure 11 Figure 12 Return Inlet Flow Outlet 710 ...

Страница 19: ...ernal boiler interrupt active P Pump Indicator on pump is active proper flow rate of water has been reached Flashing lack of flow or insufficient flow rate of water heating elements are off Temperature Indicator Red light Boiler is in heating mode Green light Boiler temperature has been reached in radiators A Indicator flashing water pressure is not sufficient below 0 5 bar F When boiler is in Sum...

Страница 20: ...rops below 5L min and therefore blocking any further heating until the flow rate is improved 2 6 To check the amount of kW energy being used by the boiler at any point in time press the button a number of times until only indicator C is illuminated The Kw figure will now be shown 2 7 When indicator H is illuminated the pump is running 3 Temperature Setting We recommend the boiler temperature be se...

Страница 21: ...lable at Pump head if power available replace as necessary If power not available check fuse on Controller Module and replace if necessary Flow sensor not operating Check the flow sensor and replace as necessary G indicator is flashing but boiler digital display operating NA connection open circuit Ensure NA connection is closed or if using external control e g Shower Sensor that this is working c...

Страница 22: ... Vessel charge pressure 1 5 bar Safety Class IP22 Overall dimensions height x width x depth 710 x 418 x 252 Dry weight 25kg Electrical supply 240V 1ph 50Hz 415V 3ph 50Hz Load current 25 0 Amp 37 5 Amp 50 0 Amp 60 0 Amp 3 x 16 7 3 x 20 0 3 x 29 2 3 x 53 8 Minimum permitted cable diameter 6mm 10mm 16mm 5 x 2 5 5 x 4 5 x 6 5 x 10 Heating output 20472 Btu 30709 Btu 40945 Btu 49134 Btu 40945 Btu 49134 ...

Страница 23: ...23 GB 031C_f ...

Страница 24: ... the end of its working life To prevent possible harm to the environment or human health from uncontrolled waste disposal please separate this from other types of wastes and recycle it responsibly to promote the sustainable reuse of material resources Household users should contact either the retailer where they purchased this product or their local government office for details of where and how t...

Отзывы: