4
1.5.2 Backup Solar plus Storage
During a grid outage, the Evolve Hub islands the battery system and
backup electrical panel off the grid. In this mode, the EMC is in a
monitoring state, with most control handed over to the Evolve ESS. The
Evolve ESS curtails PV when the battery is either full or exceeds the
charge limit of the battery. On low SOC, the battery system goes into a
standby state until either the solar resource or the grid returns.
IMPORTANT!
Shutting off the Evolve Hub circuit breaker at the main
electrical panel will place the ESS into backup mode and continue to
energize the backup panel.
1.5.3 Backup Solar PV curtailment method: Frequency Shift Power Control (FSPC)
During backup power operation of the Evolve ESS, PV curtailment is achieved by shifting the frequency up or down to trip
the PV inverter. This curtailment method, defined as frequency shift power control (FSPC), is required to prevent solar from
over-charging the battery. By default, the Evolve ESS will ramp up frequency to a PV trip range of 62.1 Hz, but this is
adjustable depending on the regulatory frequency trip limits within the jurisdiction.
IMPORTANT!
PV inverters connected to the backup panel must have frequency trip settings programmed within the
following ranges: PV low frequency trip range: 57.0 to 59.3 Hz, PV high frequency trip range: 60.5 to 62.0 Hz.
If the PV inverter cannot be adjusted within the range specified, the PV inverter must not be connected to the backup panel.
Note:
The Evolve Hub is not suitable for use in applications where the electric utility prohibits PV power export to the grid.
For non-export applications, consult your Eguana dealer for alternate EMS panel solutions.
1.5.4 Circuit and system sizing for 100 / 125 / 150 Amp electrical panels
Line side tapping the main electrical panel is required for ESS installations where the electrical service rating is under 200
Amp. Refer to section 2.3, figure 11.
1.5.5 Circuit and system sizing for 200+ Amp electrical panels
The Evolve Hub may be connected to a 200+ Amp electrical panel using a single 40A breaker. For this configuration, the
total solar PV output connected to the backup electrical panel will depend on the curtailment features of the solar PV inverter.
If the PV inverter is equipped with its own curtailment controls that can limit PV output to 5kW or less in backup mode, the
maximum rating of the PV inverter connected to the Evolve hub is 7.6 kW AC. For PV inverters without internal curtailment
methods, the 5 kW PV restriction applies. Regardless of PV size, this configuration permits the Evolve Hub’s EMS to limit
continuous combined solar plus storage output to 7.6 kW AC (32 Amp).
1.5.6 Over-sized PV systems
For installations with PV systems that are larger
than the Evolve Hub and Evolve ESS can
accommodate, the PV inverters must be split up
such that the balance of PV is wired directly to the
main electrical panel.
An additional CT must be added to the main
panel connected PV inverter.
Solar
Inverter
Evolve
Hub
Evolve
ESS
Load
Home loads
Backup
Electrical
Panel
Solar
Inverter
Solar panels
Evolve
Hub
Evolve
ESS
Grid
Load
Main
Electrical
Panel
Backup
Electrical
Panel
Home
loads
Home loads
Solar
Inverter
Excess PV
Solar panels
Figure 4: Backup solar plus storage.
Figure 5: Over-sized PV systems connected to main panel.