background image

5. WIRING (CONTINUED):

TABLE D: TERMINAL WIRE RANGE AND STRIPPING GUIDE 

AMPERE 

RATING 

30 

60 

100 

STRIP LENGTH (INCHES) 

TERMINAL WIRE RANGE lAWG) 

CONDUCTOR "A" 

.63 

.63 

.63 

=�����

Z)l---

�-

LINE CONDUCTORS 

l><XXXXXXXXXXX)����

::8)1-... 

--------

BUILDING WIRE 

#8 - #6(CU) 

#6 - #2(CU) 

#4 - #4/0(CU) 

l><XXXXXXXXXXX)�����

I

-. 

A

-

1-

1

-

-

GROUNDING CONDUCTOR

A. Referring to "FIGURE  C" feed power supply wiring into Housing 0 through conduit entry.

B. Strip the individual conductors per ''TABLE D".

C. Connect wires to the Line Side Lugs ® of the Disconnect Switch by loosening, but not removing Lug

Screws ®·  Insert conductors including all strands into lugs according to your established wiring scheme.

Tighten Lug Screws ® to the appropriate value shown in "TABLE C".  Please note the wire markers on the

wires connected between the Receptacle @ and either the Disconnect Switch Load Side Lugs (!) or Fuse

Holder Lugs @.  These wire markers correspond to the contact identification markings found on the back of

the receptacle contact block.  Refer to "FIGURE B".

D. Fused Switches are equipped with an installed Fuse Holder@ and interlocked Fuse Holder Cover@).  The

Cover 

can only be opened when the Switch is in the "OFF" position.  Attempts to open the 

Cover 

while the

Switch is "ON" may damage the 

Cover. 

The purposes of the 

Cover 

are: personnel safety from shock hazard

of energized electrical parts and to prevent removal of a fuse while Switch is "ON" which could cause an arc

in a potentially explosive atmosphere.

E. For fused  units,  install appropriate amperage fuses into Fuse Holder@.  Use only sand filled, non renewable

Class J Fuses.

F.  Wire Guide @ allows wiring to be run from the top or bottom of the Enclosure to the opposite end of the

Enclosure without interference with the Switching Mechanism.  Wiring should be held to Wire Guide by the

use of cable ties.

6. ELECTRICAL TESTING:

All wiring must be checked and tested to ensure that all circuits are according to plan and that there are no

unwanted opens,  shorts or grounds.

Do not apply power until the following steps are completed:

A. Test to verify correct phasing and ground connections.

B. Test insulation resistance by meggering high voltage or hi-pot test, to be sure the system does not have any

short circuits or unwanted grounds.

7. CLEAN COVER AND HOUSING:

Before closing the Cover @, it is strongly recommended that all dirt, debris and other foreign materials be

removed from the interior.

• This action should be taken to help eliminate the possibility of unwanted shorts or grounds.

• Make sure the cover gasket surface is clean and free of any tears or damage.

• Clean the mating surface of the Housing 0 in the same manner as the Cover @.

8. CLOSE COVER:

A. If the Cover@ was removed,  carefully rehang the Cover on the Hinges @ while the Cover is positioned

approximately 90 degrees from the Housing.

B. Close the Cover@.  Start the two Housing Cover Bolts G) by hand to prevent cross-threading.

• Tighten the Cover Bolts to 25-30 lb.- ft. torque.

• Do not over-tighten since there is a possibility of stripping threads in the Housing.

9. POWER:

Page 6 

With all electrical tests successfully made, the Cover Bolts tightened and the Receptacle turned "OFF",

power may be applied to the "MD2SR" unit.

Rev.  C  07/08/04 

Содержание Appleton MD2SR Series

Страница 1: ...S VOLTS AMPERES 250 600 30 250 600 30 250 600 60 250 600 60 250 600 100 250 600 100 FIGURE A g H P RATING CATALOG SWITCH AC NUMBERS TYPE STANDARD MAX MD2SR3023F FUSED 7 5 20 MD2SR3034F MD2SR3023U NON...

Страница 2: ...NG CURRENT RATING 30 30 30 30 60 60 60 60 100 100 100 100 TORQUE LB IN 40 45 50 Electrical power must be turned OFF before and during installation and maintenance Failure to do so may result in seriou...

Страница 3: ...NTACT IDENTIFICATION MARKING TYP CLASS II INTERLOCKED RECEPTACLE ASSEMBLY POWERTITE COMPATIBLE FUSES SHOWN NOT INCLUDED WITH UNIT PADLOCK HOLE FUSE COVER CUT AWAY TO SHOW FUSE HOLDER ASSEMBLY VIEW WIT...

Страница 4: ...OVED UNIT SHOW IS CAT NO MD2SR1034F ______ 16 7 42 3 CM CONDUIT ENTRY 0 3 0 7 6 CM 11 0 27 9 CM I CATALOG NUMBER DIMENSION A MD2SR3023F MD2SR3023U MD2SR3034F MD2SR3034U MD2SR6023F 19 3 MD2SR6023U 48 9...

Страница 5: ...erring to FIGURE C loosen the housing Cover Bolts G but do not attempt to remove them completely from the Cover because they are designed to be captive B The Cover is now free to swing open on its fac...

Страница 6: ...se Holder Use only sand filled non renewable Class J Fuses F Wire Guide allows wiring to be run from the top or bottom of the Enclosure to the opposite end of the Enclosure without interference with t...

Страница 7: ...Housing Referring to FIGURE C loosen line side Lugs Screws of the Disconnect Switch and remove line side wires from the Switch On non fused units loosen load side Lug Screws J of the Disconnect Switch...

Страница 8: ...rew Cover onto the Receptacle Housing until screw cover gasket is firmly seated against the receptacle housing face Replace the receptacle housing screw secure the free end of the Screw Cover chain to...

Страница 9: ...BLY 5 100 FUSE COVER 59351031000 1 ASSEMBLY 6 30 CLASS II RECEPTACLE 59312775000 1 ASSEMBLY 30 AMP 2 WIRE 3 POLE 7 30 CLASS II RECEPTACLE 59312766000 1 ASSEMBLY 30 AMP 3 WIRE 4 POLE 8 60 CLASS II RECE...

Страница 10: ...Clean interior of all foreign materials 6 Cover Bolts G must be tightened to 25 30 lb ft torque 7 Make sure the Receptacle Assembly Nameplate located on the outside of the cover remains clean and legi...

Отзывы: