WARNING
If any parts of the "MD2SR" unit appear to be
missing, broken or show signs of damage:
DISCON TINUE USE IMMEDIATELY!
This condition could cause serious / fatal
personal injury due to electrocution and / or
equipment damage. Repair with the proper
replacement part(s) before continuing service.
DURING THE INSPECTIONS, PERFORM AT LEAST THE FOLLOWING:
1. Electrical power must be turned "OFF" before performing maintenance.
2. Inspect all conductor terminations for secureness.
• Retorque to values given previously in these instructions.
• Discoloration due to excessive heat is an indication of possible problems and should be thoroughly
investigated and repairs made as necessary.
3. Check grounding and bonding effectiveness / continuity.
• Retorque connections to original values.
4. Check gaskets for damage. Replace as necessary.
5. Clean interior of all foreign materials.
6. Cover Bolts G) must be tightened to 25-30 lb.- ft. torque.
7. Make sure the Receptacle Assembly Nameplate located on the outside of the cover remains clean and
legible.
• Do not paint Nameplate.
It is recommended that an electrical preventive maintenance program,
such as found in the National Fire Protection Bulletin NFPA no. ?OB, be
followed in addition to the above.
All statements, technical information and recommendations contained herein are based on information and
tests we believe to be reliable. The accuracy or completeness thereof are not guaranteed. In accordance
with Appleton Electric, LLC "Terms and Conditions of Sale", and since conditions of use are outside our
control, the purchaser should determine the suitability of the product for his intended use and assumes all
risk and liability whatsoever in connection herewith.
Page 10
When finished with installation, file and retain these instructions
for future reference during inspection and maintenance.
Rev. C 07 /08/04