background image

"MD2SR" Series: 

330140 

INSTRUCTION SHEET 

Heavy  Duty  Single  T hrow  Safety  Switch  with  Interlocked 

Appleton Powertite  Compatible Receptacle. 

Instructions for Installation, Operation and Maintenance of 

"MD2SR" Interlocked Receptacle with Switch: 30,  60 &  100 

Ampere. 

Class I Div. 2 Group B, C,  D, T 3C 

Class II Div.  1  Group F,  G 

NEMA Type 3,  3R,  4,  4X,  12 (Screw Cover  Option) 

Electrical Rating: 

Compliances: 

UL Listed,  File No. E10784 

UL 1682 Standard for  Plugs,  Receptacles, and Cable 

Connectors of  the Pin and Sleeve Type 

Maximum Voltage:  600  VAC  at  60  Hz,  250 VDC  30,  60 or 

100  Amperes,  depending on  current  rating  of  product (See 

product  nameplate for details). 

UL 1010 - Plug Combinations for use in Hazardous Location 

UL98  - Enclosed and Dead-Front Switches 

UL50  - Enclosures for Electrical Equipment 

UL894  - Switches for use in Hazardous Locations 

NEC wire bending space, Table 373-6(8). 

Read instructions carefully and with full understanding for safe installation and operation. 

TABLE  A - HORSEPOWER RATING: 

DC 

AC 

VOLTS  VOLTS  AMPERES 

250 

600 

30 

250 

600 

30 

250 

600 

60 

250 

600 

60 

250 

600 

100 

250 

600 

100 

FIGURE A 

g. 

H.P.  RATING 

CATALOG 

SWITCH 

AC 

NUMBERS 

TYPE 

STAN DARD 

MAX 

MD2SR3023F 

FUSED 

7.5 

20 

MD2SR3034F 

MD2SR3023U  NON-FUSED 

--

30 

MD2SR3034U 

MD2SR6023F 

FUSED 

15 

50 

MD2SR6034F 

MD2SR6023U 

NON-FUSED 

--

50 

MD2SR6034U 

MD2SR1023F 

FUSED 

30 

50 

MD2SR1034F 

MD2SR1023U 

NON-FUSED 

---

50 

MD2SR1034U 

STANDARD FEATURES: 

• Epoxy coated finish on receptacle and disconnect switch

housing.

• Current carrying  parts in housing are all plated copper,

receptacle contacts are brass.

• Lugs - front removable, standard mechanical lugs on

incoming line.  Lay-in ground lug.

• Screw cover assembly provided for use on receptacle

housing, instead of flip cover assembly to meet NEMA
Type 4 and 4X environmental conditions.

Except  as  expressly  provided  by  Appleton  Electric,  LLC 

(Appleton) in writing,  Appleton products are intended for ulti­

mate  purchase  by industrial users and  for operation by per­

sons trained and experienced in the use and maintenance of 

this  equipment  and  not  for  consumers  or  consumer  use. 

Appleton  warranties  do  not  extend  to,  and  no  reseller  is 

authorized to extend  Appleton's warranties to,  any consumer. 

Rev.  C  07 /08/04 

Page 1 

Содержание Appleton MD2SR Series

Страница 1: ...S VOLTS AMPERES 250 600 30 250 600 30 250 600 60 250 600 60 250 600 100 250 600 100 FIGURE A g H P RATING CATALOG SWITCH AC NUMBERS TYPE STANDARD MAX MD2SR3023F FUSED 7 5 20 MD2SR3034F MD2SR3023U NON...

Страница 2: ...NG CURRENT RATING 30 30 30 30 60 60 60 60 100 100 100 100 TORQUE LB IN 40 45 50 Electrical power must be turned OFF before and during installation and maintenance Failure to do so may result in seriou...

Страница 3: ...NTACT IDENTIFICATION MARKING TYP CLASS II INTERLOCKED RECEPTACLE ASSEMBLY POWERTITE COMPATIBLE FUSES SHOWN NOT INCLUDED WITH UNIT PADLOCK HOLE FUSE COVER CUT AWAY TO SHOW FUSE HOLDER ASSEMBLY VIEW WIT...

Страница 4: ...OVED UNIT SHOW IS CAT NO MD2SR1034F ______ 16 7 42 3 CM CONDUIT ENTRY 0 3 0 7 6 CM 11 0 27 9 CM I CATALOG NUMBER DIMENSION A MD2SR3023F MD2SR3023U MD2SR3034F MD2SR3034U MD2SR6023F 19 3 MD2SR6023U 48 9...

Страница 5: ...erring to FIGURE C loosen the housing Cover Bolts G but do not attempt to remove them completely from the Cover because they are designed to be captive B The Cover is now free to swing open on its fac...

Страница 6: ...se Holder Use only sand filled non renewable Class J Fuses F Wire Guide allows wiring to be run from the top or bottom of the Enclosure to the opposite end of the Enclosure without interference with t...

Страница 7: ...Housing Referring to FIGURE C loosen line side Lugs Screws of the Disconnect Switch and remove line side wires from the Switch On non fused units loosen load side Lug Screws J of the Disconnect Switch...

Страница 8: ...rew Cover onto the Receptacle Housing until screw cover gasket is firmly seated against the receptacle housing face Replace the receptacle housing screw secure the free end of the Screw Cover chain to...

Страница 9: ...BLY 5 100 FUSE COVER 59351031000 1 ASSEMBLY 6 30 CLASS II RECEPTACLE 59312775000 1 ASSEMBLY 30 AMP 2 WIRE 3 POLE 7 30 CLASS II RECEPTACLE 59312766000 1 ASSEMBLY 30 AMP 3 WIRE 4 POLE 8 60 CLASS II RECE...

Страница 10: ...Clean interior of all foreign materials 6 Cover Bolts G must be tightened to 25 30 lb ft torque 7 Make sure the Receptacle Assembly Nameplate located on the outside of the cover remains clean and legi...

Отзывы: