Seite/Page 17 von/of 26
UV Flame Detector
Type: FL (Ex) d 07-.-..-..
10/21/2016
3
Date
Version
Betriebsanleitung Nr./
Operating Instructions No.
4.09262.9-1
WARNING
UV flame detector not ready type: FL (Ex) d 07-T-FB-.. (Fault)!
+
UV test fault:
e.g. visual pane dirty, UV-Fiber-Optic Cable defective, UV -
Transmitter defective.
(1) Clean visual pane.
(2) Check the UV-Fiber-Optic Cable for any fiber breakage.
(3) Shut off operating voltage briefly and switch it back on.
(4) See beginning of test item 5.2
(5) Is the UV - test fault still there?
(6) UV - Transmitter type: TE d 07, part ID: 80567.
(7) Shut off operating voltage briefly and switch it back on.
(8) See beginning of test item 5.2
(9) Is the UV - test fault still there?
(10) PCB type: Replace FL (Ex) d 07 MCU, part ID: 80569.
(11) Shut off operating voltage briefly and switch it back on.
(12) See beginning of test item 5.2
WARNING
UV flame detector not ready type: FL (Ex) d 07-T-FB-.. (Fault)!
The date and time are not set in the UV flame detector.
Set the date and time via the configured fieldbus system.
Functional code: $70 + send data content.
Fieldbus module hardware test or fieldbus type or node address error
in the UV flame detector.
CAUTION!
Only if the error is active for a longer period of time.
(1) Check the fieldbus system configuration.
(2) Replace the fieldbus module in the UV flame detector.
Fieldbus module node is offline or no power in the UV flame detector
CAUTION!
Only if the error is active for a longer period of time.
(1) Check the fieldbus system configuration.
(2) Replace the fieldbus module in the UV flame detector.
Fieldbus module Initialization of PROFIBUS ASIC in the UV flame
detector or Configuration Data and/or User Parameterizations data
(1) Check the fieldbus system configuration.
(2) Replace the fieldbus module in the UV flame detector.
LED
Flash
LED
Flash
LED
Flash
LED
Flash
FB Master IN
Reg. 0002/Lo
Bit 5 = 1
LED
Blink