Egcon GCU-DG3 Скачать руководство пользователя страница 25

  GCU  -DG3  User's  Guide

EGCON  Co,.  Ltd 

 

25  Page

19. Failure  Causes  and  Measures

Statue

Cause

Soultions

Power  supply  is  not 
working(Nothing  can  be 
seen  on  LCD).

DC  blocker  opens.

Close  DC  blocker.

DC  fuse  disconnects.

Change  to  new  fuse  of  same  capacity.

Wrong  connection  of  wiring

Correct  wiring  through  referring  circuit 
diagram.

Battery  discharges.

Use  after  charging  battery  more  than  5 
hours.

Start-up  is  not 
working(Starting  motor  is 
not  rotating).

Battery  discharges.

Use  after  charging  battery  more  than  5 
hours.

Fault  of  starting  assistance 
magnet

Use  after  changing  start 

Fault  of  starting  motor

Use  after  changing  start  motor.

Wiring  is  not  connected  or 
wrongly  connected.

Correct  wiring  through  referring  circuit 
diagram.

Start-up  is  not 
working(Starting  motor  is 
rotating).

Fault  of  preheating  plug

Use  after  changing  preheating  plug.

Wrong  setting  of  engine  type 
in  option  setting

Select  ETR  and  ETS  correctly  after 
inquiring  of  engine  manufacturing 
company.

Start-up  is  not 
working(Start-up  works, 
but  it  is  turned  off  soon)

Wrong  PICK-UP  Setting  in 
option  setting

Inserting  the  number  ring  gear  correctly 
after  inquiring  of  engine  manufacturing 
company.

Wiring  of  OPG  is  not 
connected  or  wrongly 
connected. 

Correct  wiring  through  referring  circuit 
diagram.

OPG  alarm  sounds  when 
turning  on  power  supply.

Wiring  of  OPG  is  not 
connected  or  wrongly 
connected.

Correct  wiring  through  referring  circuit 
diagram.

Wrong  setting  of  OPS  MODE 
in  option  setting

Set  OPS  MODE  correctly.

Not  using  proper  sensor

For  OPU,  use  product  of  VDO  company.

The  rotating  number  of 
generator  is  not  correct.

Wrong  PICK-UP  Setting  in 
option  setting

Inserting  the  number  ring  gear  correctly 
after  inquiring  of  engine  manufacturing 
company.

Generator  is  operating, 
but  GEN.  RUN  LAMP  is 
not  working.

Wiring  of  PICK-UP  is  not 
connected  or  wrongly 
connected.

Correct  wiring  through  referring  circuit 
diagram.

Wiring  of  GEN.VOLT  is  not 
connected  or  wrongly 
connected.

Correct  wiring  through  referring  circuit 
diagram.

Power  value  is  not 
correct.

Wrong  CT  RATIO  Setting  in 
option  setting

Insert  the  number  of  used  CT  correctly.

Generator  voltage  input  and 
CT  input  are  different.

Correct  wiring  through  referring  circuit 
diagram.

Indication  of  power  factor 
is  not  normal.

Second  wiring  of  CT  is 
wrongly  connected.

Correct  wiring  with  drawing  after 
confirming  polarity  of  CT.

Even  though  commercial 
power  supply  is  in  outage, 
automatic  operation  of 
generator  is  not  working.

Wrong  COM  POWER  Setting 
in  option  setting

Correct  wiring  through  referring  circuit 
diagram.

No  input  of  ACB

The  value  of  generator 
voltage  is  lower  than  the 
value  of  UVR  setting. 

Make  generator  voltage  normal  through 
adjusting  AVR.

Содержание GCU-DG3

Страница 1: ...GCU DG3 User s Guide EGCON Co Ltd...

Страница 2: ...nnection Socket and Rating 10 10 Abbreviation 11 11 Manual Operation 12 12 Automatic Operation 12 13 Remote control Operation 13 14 Protection Control Drive test of Engine Generator 13 15 Modification...

Страница 3: ...lectrocution 4 Please do not touch when sheath of electric wire is damaged to prevent electrocution 5 Please do earthing of electric wire to prevent electrocution 1 Please permit a regular power suppl...

Страница 4: ...rt sounds 2 12 pause Solenoid burn preventive designal 2 13 Function of administrator password 2 14 Function of change from interface capacity for starter and pauseper 15A ACB input and block to high...

Страница 5: ...orage Temperature 24 45 C 4 3 Relative Humidity 0 90 Noncondensing 4 4 Vibration amplitude 0 35mm frequency 0 30Hz 4 5 Maximum Operating Altitude 3 000m 4 6 Maximum Storage Altitude 4 500m 4 7 Install...

Страница 6: ...switch in MNU manual mode Save after setting change Buzzer pause switch when detecting fault Lamp Test Function when OFF mode Fault Reset Button 3 ACB Control Switch 4 Lamp Blocking ACB in MNU manual...

Страница 7: ...n of line voltage and phase current 2 Pressing DOWN transfers to next screen 3 O F F M N U A T O R M R N 0 0 0 V R 0 0 0 0 A S N 0 0 0 V S 0 0 0 0 A T N 0 0 0 V T 0 0 0 0 A 1 Indication of line voltag...

Страница 8: ...rs to previous screen 3 Pressing DOWN transfers to screen 1 Indication of OPG and WTG differs according to option setting O F F M N U A T O R M R S 0 0 0 V R P M 0 0 0 0 R 0 0 0 A O P G 0 0 b a r H z...

Страница 9: ...circuit diagram 1 and 2 to circuit 2 5sq a circuit diagram 1 Cautions l Please connect voltage and current of generator power supply identically to prevent voltage indication error l Please do not con...

Страница 10: ...d output sockets of GCU are different from drawing and there will be indication of fault on LCD when there are wrong parts Option setting menu 2 GEN SET SETTING 1 ENGINE TYPE Engine fuel control type...

Страница 11: ...50V 10A 6X c 6X a Engine operating indication interface Dry contect AC250V 10A WTS Input of over temperature interface NORMAL OPEN DC Connection OPS Input of oil pressure switch NORMAL CLOSE DC Connec...

Страница 12: ...please press RPM and there will be an indication of oil pressure measurement in OPG For use of OPS indication will be OPG OFF 3 When actual engine speed and RPM are different please insert measuremen...

Страница 13: ...engine will pause after blocking ACB preparing for re outage in CDT time and cooling engine 12 10 When commercial electricity is in outage in CDT operation there will be input of ACB and initializati...

Страница 14: ...sing engine 4 LCD Screen indicates OVER SPEED ERROR_MESSAGE 5 When pressing buzzer and resetting it will return to normal state 14 4 Low Oil Pressure Test 1 When oil pressure switch operates after eng...

Страница 15: ...R e l a y O u t p u t S e t 1 3 F a u l t H i s t o r y 1 This is the last page 2 Items of options settings are all 12 and it is impossible to do option setting when generator is in operation 6 Reset...

Страница 16: ...M O D E N O N U S E 1 Pressing ENTER lets a cursor locate in front of setting value 6 2 G E N S E T S E T T I N G 1 E N G I N E T Y P E E T R 2 O P S M O D E N O N U S E 3 W T S M O D E N O N U S E 1...

Страница 17: ...R k e y P r e s s 1 This is the screen that a cursor locates at the first box 2 Pressing UP or DOWN to insert numbers 3 Pressing ENTER transfers to next box 4 P A S S W O R D 1 1 1 4 E n t e r k e y...

Страница 18: ...Explanations and setting scopes Default 1 ENGINE TYPE ETR A type that engine operates when power supplies to oil solenoid ETS A type that engine pauses when power supplies to oil solenoid ETR 2 OPS M...

Страница 19: ...for low oil fault 0 59 sec 1 sec 12 Wrn WATER Setting of over temperature alarm 40 110 90 13 Err WATER Setting of over temperature detection 40 110 100 14 OPE WATER Waiting time for over temperature d...

Страница 20: ...1 Setting_PW USE Using password in option setting NONUSED Not Using password in option setting NONUSED 2 PowerON_PW USE Using password at the first start up All operations are useless if not knowing...

Страница 21: ...it is 5 C 40 40 0 0 16 9 PROTECT SETTING NO Menu Detection Setting Value Default 1 BASE Overspeed over oil over temperature start failure overvoltage GEN RUN GEN STOP 3 GEN STOP 2 UVR Detection of low...

Страница 22: ...ration in fault of overspeed 48X Operation in fault of automatic mode start 59X Operation in fault of overvoltage 27GX Operation in fault of low voltage 51X Operation in fault of over current 51GX Ope...

Страница 23: ...temperature 6 26W_Wa Alarm of generator s over temperature 7 26W_Op Open of generator s temperature sensor In case that it can not detect oil sensor in the process of generator operation 8 48X Er Oper...

Страница 24: ...0 104 36 00 105 12 10 110 30 00 110 8 10 115 24 00 115 4 10 118 21 00 120 0 10 121 18 00 18 The Number of Major Engine Ring Gear Manufacturing of engine Engine Model Ring Gear teeth Manufacturing of e...

Страница 25: ...eferring circuit diagram OPG alarm sounds when turning on power supply Wiring of OPG is not connected or wrongly connected Correct wiring through referring circuit diagram Wrong setting of OPS MODE in...

Отзывы: