GCU -DG3 User's Guide
EGCON Co,. Ltd
21 Page
16.8. SENSOR SELECT
NO.
Menu
Explanation
Setting Scope
Default
1
OP MODEL
Selection of oil pressure sensor
VDO
VDO
2
WT MODEL
Selection of water temperature sensor
VDO, DONGNAM
DONGNAM
3
OT MODEL
Selection of oil temperature sensor
VDO, DONGNAM
DONGNAM
4
OP CALIB
l
Revision of oil pressure sensor value
l
Value revision when using VDO sensor: unit
is 0.3bar
-4.0 ~ 4.0bar
0.0bar
5
WT CALIB
l
Revision of water temperature sensor value
l
Value revision when using VDO sensor: unit
is 3‘C
l
Value revision when using DONGNAM
sensor: unit is 5‘C
-40 ~ 40℃
0.0℃
16.9. PROTECT SETTING
NO.
Menu
Detection
Setting Value
Default
1
BASE
Overspeed, over oil, over
temperature, start failure,
overvoltage
GEN RUN, GEN STOP
(주3 참고)
GEN STOP
2
UVR
Detection of low-voltage
GEN RUN, GEN STOP
GEN RUN
3
OCR
Detection of over-current
GEN RUN, GEN STOP
GEN RUN
4
OCGR
Detection of over-current
GEN RUN, GEN STOP
GEN RUN
5
AFR
Detection of preliminary
fault input
GEN RUN, GEN STOP
GEN RUN
6
CURR UN
Detection of current
unbalance
USED , NONUSE
USED
16.10. ACB & ATS MODE SET
NO.
Menu
Setting Scope
Default
1
ACB & ATS MODE SET
ACB , ATS , NONUSE , MCCB TRIP
ACB
16.11. RS485 SET
NO.
Menu
Setting Scope
Default
1
ADDRESS
Setting of communication address (1 ~ 16)
1
2
BAUD RATE
9600bps
9600bps
3
RS485 CK
No : RS485 TEST nonuse
YES : RS485 TEST on - LCD indicate
NO
Содержание GCU-DG3