4

  turning CW increase the level for damping generator transient output voltage. 

  turning CCW decrease damping level to cause under damping 

6.6.  Choice frequency switch depending on generator frequency (SW1) 

This option protects generator and AVR by decreasing generator output voltage if it reduces 
generator frequency. (under frequency protection) 

Frequency 50Hz system (refer to below 50Hz system) 

Frequency 60Hz system (refer to below 60Hz system) 

43

50

45 48

Hz

rated volt

residual volt

output volt

residual volt

output volt

rated volt

55

53

58 60 Hz

(V)

(V)

(60Hz System)

(50Hz System)

 

7. FLASH EXCITING 

7.1.  MANUAL FIELD FLASH ESCITING 

When generator does not build up to the rated value or has no output, manual field flash exciting 
could be executed as the following order.    Please refer to the below drawing. 

 

1)  Remove two output lines connected to the terminals J, K of generator. 
2)  Prepare a12Vdc battery and a push button ,and connect them as the drawing. 
3)  Start engine 
4)  When the revolution is reached rating, push the button for short time (about 1~2sec) 
5)  Check the output voltage. 

Содержание AVR-126

Страница 1: ...tage exceeds 85Vdc AVR output shut down to protect the generator winding coil from burning out 2 4 Starting engine generator set if the residual voltage remains on the stator winding of generator AC o...

Страница 2: ...1 Size W140 x H200 x D60 mm 4 2 Mounting size W90 x H190 mm x 5 4Holes 4 3 Color bottom and cover ivory 4 4 Frequency selection changeover switch 4 5 Weight about 2kg 5 INSTRUCTION AND CONNECTION NOT...

Страница 3: ...nnected to the F F or J K of exciter field respectively 6 ADJUSTING 6 1 Start prime mover and bring up to rated speed 6 2 Voltage would be automatically built up If not confirm until voltage build up...

Страница 4: ...system 43 50 45 48 Hz rated volt residual volt output volt residual volt output volt rated volt 55 53 58 60 Hz V V 60Hz System 50Hz System 7 FLASH EXCITING 7 1 MANUAL FIELD FLASH ESCITING When genera...

Страница 5: ...ED FLASH EXCITING Whenever start generator set to avoid no output voltage It is recommended to take automatic field flash exciting by using the generator control sequence as below drawing 8 PARALLE OP...

Страница 6: ...s F F not connected Power input leads not connected Blown or missing fuse Defective regulator Defective generator Check wiring diagram for proper Connections Flash generator field Refer to 7 FLASH EXC...

Страница 7: ...t is turned too high Rotate voltage adjust CCW until desired voltage is reached Rotate remote voltage adjust CCW until desired voltage is reached Output Voltage High No Adjustment Defective regulator...

Отзывы: