CAUTION
If the ambient temperature is out of the operating range, the battery pack stops operating to protect itself.
The optimal temperature range for the battery pack to operate is 10°C to 40°C. Frequent exposure to harsh
temperatures may deteriorate the performance and life of the battery pack.
4.3 Grounding
Grounding cables shall be 10AWG or higher yellow-green cables. After connection, the resistance from battery
grounding point to Ground connection point of room or installed place shall smaller than 0.1Ω.
UP2500 modules’ grounding is based on metal directly touch between the module’s surface (SGCC) and
rack’s surface. If uses normal rack, may need to remove the paint at the corresponding place.
Or install a grounding cable to the grounding point of the modules
.