UPS MTD-XL
Technical
Data
MTD series
73
12.1.1
Displayed messages and acoustic alarm signals
Display
AC mode
NORM---normal operating mode
Backup mode
Display: “bATT” acoustic signal in 4 seconds intervals
Charging mode
LCD-display
Fault mode
LCD-display, dis
play red and message “ **** ”
Overload
LCD-
display, display red and message “OVLD”
Low battery status
LCD-
display, display red and message “bTLW”
Acoustic alarm
Backup mode
Acoustic signal in 4 seconds intervals
Low battery status
Acoustic signal every second.
Fault mode
continuous signal
Overload
Acoustic signal every second.
Replace batteries
Acoustic signal every second.
12.1.2
Ambient and operating conditions
Temperature
0° to 40 °C
Humidity
20 % - 80 % relative humidity (non condensing)
Altitude
< 1500 m
Storage temperature
- 15
to 45
C
12.1.3
Dimensions, measures and weights
Model
1000
1500
2000
3000
UPS
housing
net weight (kg)
10
10
16
16
Dimensions
(mm)
( W x H x D)
438 x 86,5 x 436
438 x 86,5 x 608
Battery
housing
Dimensions
(mm)
W x H x D)
438 x 86.5 x 436
438 x 86,5 x 608
net weight (kg)
20.5
33.3
Содержание ACX11MST1K0000XL
Страница 7: ...UPS MTD XL Introduction MTD series 7...
Страница 31: ...UPS MTD XL UPS Device Description MTD series 31 Fig 3 2 3 Relay slot card...
Страница 32: ...UPS MTD XL UPS Device Description MTD series 32 Fig 3 2 4 Relay card diagram...
Страница 41: ...UPS MTD XL UPS Device Description MTD series 41...
Страница 77: ...UPS MTD XL MTD series 77 EFFEKTA Regeltechnik GmbH Rheinwaldstra e 34 D 78628 Rottweil...