Controller setup
Press anywhere on the display and then press the OPE-
RATION icon.
Operation settings menu:
Use the + and - buttons together with OK and the Return
key to navigate the menu system.
- Confirm that burner is set to OFF.
Feeder menu:
Enter the FEEDER SETTINGS menu.
Change the pellets diameter to 6 or 8 mm. pellets.
Change the start dose value to 48s which will get you
reasonably close to the correct start dose value.
▀
Calibration of feed dose - Suction version
Burner
Fan
Feeder settings
Temperature set
Information
Service
Installation
Off
VER: 3.0
Operation settings
Start dose
Support dose
Pellets diameter
Run start dose
Run supp. dose
Run oper. dose
Feeder settings
50s
10s
6
No
No
No
A correctly adjusted start dose is one of the most critical and important steps of a
comissioning process. If the start dose is incorrect it will give the wrong output on the
boiler which might create operational issues, excessive wear on parts and even be
dangerous in extreme situations.