11
STEP 3:
A separate 8 AWG
ground (green wire)
conductor for the incoming circuit is required. Route the
ground
wire along the same path as
Line 1
and
Line 2
. Using a Philips head screwdriver, tighten the
ground
wire to the
ground lead.
STEP 4:
Use a flat head screwdriver to
DOUBLE CHECK
the electrical connections to make sure they are correct
and that all wire connections are tight and secure. Pull on wires to ensure that they do not pull out of their
connections. Also confirm that the correct breaker size and wire gauge has been used and confirm that the unit
has been connected to a ground in accordance with applicable codes.
STEP 5:
Be sure to install the front cover back on the unit before turning on power to the unit.
Confirm that all
the air has been purged from the water lines prior to turning on power to the unit. Refer to STEP 3 in the
plumbing installation section.
DANGER
Failure to do so can result in property damage, injury or death.
CAUTION
Ensure that you have made the correct connections. You must follow the wire connection as
shown to ensure proper operation of the unit. If you mix up one set of wires with another, the unit will not
operate correctly even though it turns on and otherwise appears to function properly.
The water heater is now installed and ready to use! Follow the General Operating Instructions to complete the
setup.
Electrical Specifications by Heater Input
Wiring Diagram
HEATER INPUT
13kW
ELEMENTS
2
VOLTAGE
240 VAC Single Phase
MAX kW
13 kW
kW PER ELEMENT
6.5 kW
MAX AMPERAGE DRAW
54 AMPS
REQUIRED BREAKERS
1 x 60 AMP (Double
Pole)
REQUIRED WIRE GAUGE
2 x 6 AWG
HotMax requires 1 Double Pole
Breaker and 2 wires
L1
L2