© 2017 United Technologies Corporation
1 / 5
P/N 387040P-
EN • REV 013 • ISS 20SEP17
SIGA-CC2 Dual Input Signal Module
Installation Sheet
Description
The SIGA-CC2 Dual Input Signal Module is an addressable
device that connects one of two risers to a Class B supervised
output circuit.
When activated, the module connects the output circuit to the
Riser 1 or Riser 2 input. The input can be either 24 VDC (to
operate polarized audible and visible signal notification
appliances), or 25 or 70 VRMS (to operate audio evacuation
speakers). Typically, the Riser 1 input connects to the ALERT
channel and the Riser 2 input connects to the EVAC channel.
The module does not provide signal synchronization. To meet
UL 864 requirements for horn and strobe signal
synchronization, you must install a Genesis Signal Master
module. This module does not provide supervision of the riser;
the fire alarm panel provides this function.
The SIGA-CC2 module requires two addresses on the
signaling line circuit (SLC). Addresses are assigned
electronically. There are no address switches.
Diagnostic LEDs provide visible indication of the state of the
module through the cover plate:
•
Normal: Green LED flashes
•
Alarm/active: Red LED flashes
Personality codes
Use the personality codes described below to configure the
SIGA-CC2 module. See Table 1 for listing information.
Table 1: Personality codes
Code
Description
UL 864
CAN/ULC-
S527
EN 54-18
7
Riser selector -
supervised output
(Class B)
Personality code 7
: Riser selector - supervised output
(Class B). Configures the SIGA-CC2 module as a
one - or two - input, signal power (24 VDC) or audio evacuation
(25 or 70 VRMS) riser selector. The output circuit is monitored
for open or shorted wiring. If a short exists, the control panel
inhibits the activation of the signal circuit, so the riser is not
connected to the wiring fault.
Installation
Install this device in accordance with applicable national and
local codes, ordinances, and regulations.
Notes
•
The module is shipped from the factory as an assembled
unit; it contains no user-serviceable parts and should not
be disassembled.
•
This module does not operate without electrical power. As
fires frequently cause power interruption, discuss further
safeguards with the local fire protection specialist.
To install the module:
1. Write the address assigned to the module on the label
provided, and then apply the label to the module. Remove
the serial number label from the module, and then attach it
to the project documentation.
2. Wire in accordance with
“Wiring” on page 2.
3. Using the self-tapping screw provided, attach the wall
plate to the module. See Figure 1.
4. Using the four machine screws, attach the wall plate and
module to the electrical box.