background image

 

© 2017 United Technologies Corporation 

1 / 5 

P/N 387040P-

EN • REV 013 • ISS 20SEP17 

 

SIGA-CC2 Dual Input Signal Module  
Installation Sheet 

 

Description 

The SIGA-CC2 Dual Input Signal Module is an addressable 
device that connects one of two risers to a Class B supervised 
output circuit.  

When activated, the module connects the output circuit to the 
Riser 1 or Riser 2 input. The input can be either 24 VDC (to 
operate polarized audible and visible signal notification 
appliances), or 25 or 70 VRMS (to operate audio evacuation 
speakers). Typically, the Riser 1 input connects to the ALERT 
channel and the Riser 2 input connects to the EVAC channel. 

The module does not provide signal synchronization. To meet 
UL 864 requirements for horn and strobe signal 
synchronization, you must install a Genesis Signal Master 
module. This module does not provide supervision of the riser; 
the fire alarm panel provides this function. 

The SIGA-CC2 module requires two addresses on the 
signaling line circuit (SLC). Addresses are assigned 
electronically. There are no address switches. 

Diagnostic LEDs provide visible indication of the state of the 
module through the cover plate: 

• 

Normal: Green LED flashes 

• 

Alarm/active: Red LED flashes 

 

 

Personality codes 

Use the personality codes described below to configure the 
SIGA-CC2 module. See Table 1 for listing information.   

Table 1: Personality codes 

Code 

Description 

UL 864 

CAN/ULC-
S527 

EN 54-18 

Riser selector - 
supervised output  
(Class B) 

 

 

 

 

Personality code 7

: Riser selector - supervised output 

(Class B). Configures the SIGA-CC2 module as a  
one - or two - input, signal power (24 VDC) or audio evacuation 
(25 or 70 VRMS) riser selector. The output circuit is monitored 
for open or shorted wiring. If a short exists, the control panel 
inhibits the activation of the signal circuit, so the riser is not 
connected to the wiring fault. 

Installation 

Install this device in accordance with applicable national and 
local codes, ordinances, and regulations. 

Notes  

• 

The module is shipped from the factory as an assembled 
unit; it contains no user-serviceable parts and should not 
be disassembled. 

• 

This module does not operate without electrical power. As 
fires frequently cause power interruption, discuss further 
safeguards with the local fire protection specialist. 

To install the module: 

1.  Write the address assigned to the module on the label 

provided, and then apply the label to the module. Remove 
the serial number label from the module, and then attach it 
to the project documentation.  

2.  Wire in accordance with 

“Wiring” on page 2. 

3.  Using the self-tapping screw provided, attach the wall 

plate to the module. See Figure 1. 

4.  Using the four machine screws, attach the wall plate and 

module to the electrical box. 

Содержание SIGA-CC2

Страница 1: ...s described below to configure the SIGA CC2 module See Table 1 for listing information Table 1 Personality codes Code Description UL 864 CAN ULC S527 EN 54 18 7 Riser selector supervised output Class B Personality code 7 Riser selector supervised output Class B Configures the SIGA CC2 module as a one or two input signal power 24 VDC or audio evacuation 25 or 70 VRMS riser selector The output circu...

Страница 2: ...ations Each terminal on the module is limited to a single conductor Test resistors are supplied with the SIGA CC2 to prevent trouble signals on unused circuits during installation When connecting field wires remove the test resistors and install a UL ULC Listed 47 kΩEOLR at the end of the circuit The module does not support conventional smoke detectors Riser wiring notes For maximum line impedance...

Страница 3: ...conductors extending beyond the jacket are separated by a minimum of 0 25 in 6 4 mm space or by a nonconductive sleeve or nonconductive barrier from all other conductors Refer to the NFPA 70 National Electrical Code for more details 4 If using a G1 P Genesis series horn while connected to a compatible fire alarm control panel a CDR 3 Bell Coder must be used to comply with NFPA 72 standard alarm ev...

Страница 4: ...tted substitute cables provided these power limited cable conductors extending beyond the jacket are separated by a minimum of 0 25 in 6 4 mm space or by a nonconductive sleeve or nonconductive barrier from all other conductors Refer to the NFPA 70 National Electrical Code for more details 4 Unshielded twisted pair 5 47 kΩ EOLR P N EOL 47 6 Signaling line circuit SLC to next device 7 Channel 1 ALE...

Страница 5: ...x with a dual gang cover Wire size 12 to 18 AWG 1 0 to 4 0 mm Operating environment Temperature Relative humidity 32 to 120 F 0 to 49 C 0 to 93 noncondensing Storage temperature range 4 to 140 F 20 to 60 C Regulatory information FCC compliance This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and...

Отзывы: