P/N 3100897-EN • REV 05 • ISS 10DEC14
Windows automatically assigns COM ports to the FW-SP4I card serial
ports. See Figure 3.
Figure 3: FW-SP4I COM port assignments
To view the FW-SP4I COM port assignments:
1. Open Windows Device Manager.
2. Double-click Ports (COM & LPT).
3. Look for the devices labeled CTI PCI Express UART Serial Port 1
through 4.
The Windows COM port numbers are in brackets. The FW-SP4I
card serial number is in brackets (SN#0000xxxx).
Cable connections
Connect the RJ-45 to DB9 cable adapters to the FW-SP4I card. See
Figure 4.
Figure 4: RS-232 COM port connections
(1) Communication Security Level 0.
(2) RJ-45 to DB-9 adapter cable supplied with the FW-SP4I card. Limit
connection to the same room, within 20 ft. (6.1 m), and enclose in
conduit or equivalent protection against mechanical injury.
Specifications
Mounting space
One PCI expansion slot
RS-232 COM ports
Four
Optical isolation
Each port individually isolated up to 3 kVAC
peak to peak
Operating environment
Temperature
Relative humidity
32 to 120°F (0 to 49°C)
0 to 93% noncondensing
Contact information
For contact information, see www.edwardsutcfs.com