background image

Page 2 of 4

 

  D A T A   S H E E T

 S85001-0618

 

Not to be used for installation purposes.

  Issue 4  

Application

The SafeAir 250-CO Carbon Monoxide Detector is intended for 
ordinary indoor-dwelling unit applications in both residential and 
commercial occupancies, including single/multiple family residential 
occupancies, hotel rooms, dorm rooms, and other areas approved 
by the authority having jurisdiction (AHJ). The 250-CO detector 
can connect to either UL 985 (Household Fire Warning) or UL 864 
(Commercial Fire) control panels. It is not intended for use in indus-
trial applications such as gasoline refineries or parking garages, 
which require different listings. The 250-CO detector has an optional 
adapter mounting plate for the 240COe CO detector. To purchase 
the plate order P/N 250-COPLT-5PKG.

Selecting a suitable location is critical to the operation of CO 
detectors. Install the 250-CO in accordance with NFPA 720 Stan-
dard for the Installation of Carbon Monoxide (CO) Detection and 
Warning Equipment. Place wall-mounted detectors at least 5 ft. 
(1.5 m) up from the floor. For ceiling mounted applications, place 
the detector at least 1 ft. (0.3 m) from any wall.

Recommended CO detector locations:

 

9

Within 10 ft. (3 m) of all sleeping areas, including areas such 
as hotel rooms and dorm rooms.

 

9

In a suitable environment: areas with a temperature range of 
32 to 104°F (0 to 40°C) and with a relative humidity range of 0 
to 90% noncondensing.

 

9

In residential dwellings, locate detectors in every bedroom, 
within 10 ft. (3 m) of sleeping areas, and on each level. At a 
minimum, place one detector outside the sleeping areas.

 

 Recommended locations for CO detectors

Always check with your local building codes,  

legislation, and Authority Having Jurisdiction  

for specific CO location requirements in your area

Recommended CO detector locations in commercial occupancies:

 

9

On every habitable level of the building based on an engineer-
ing evaluation considering potential sources and migration of 
carbon monoxide

 

9

In any area required by local building codes, legislation, or 
Authorities Having Jurisdiction

 

9

On a firm, permanent surface

Do not install the CO detector:

 

8

Within 10 ft. (3 m) of a fuel-burning appliance

 

8

Near air conditioners, heating registers, and any other ventilation 
source that may interfere with CO gas entering the detector

 

8

Where furniture or draperies may obstruct the airflow

 

8

In a recessed area

 

Operation

SafeTest functional test:

 This test facilitates the use of CO test 

spray to verify the correct operation of the detector. Functional 
testing is mandatory per NFPA 70 as of January 2012. SafeTest 
mode is activated by pressing and holding down the test/hush 
button per the installation instructions. While in SafeTest mode, 
directing UL approved CO testing spray at the sensor port will 
result in the activation of the alarm relay, and the sounder and red 
LED to activate in a temporal-four pattern. Pressing and holding 
the test/hush will exit SafeTest mode.

Distinct 85 dB temporal four-sounder alarm: 

The 85 dB 

temporal-four sounder provides a distinctive alarm notification that 
is easy to differentiate from smoke alarm notification devices. The 
alarm beeps four times, rests five seconds and then repeats the 
pattern.

Test/hush button:

 Use the test/hush button to test the alarm and 

silence an activated alarm. Pushing the test/hush button silences 
the integral sounder for five minutes. The red alarm light stays on 
and if CO is still present after five minutes, the detector once again 
sounds in the temporal-four pattern. The hush feature does not 
operate at CO levels above 350 ppm (parts per million).

End of sensor life indicator: 

The detector uses both a flash-

ing green LED and intermittent sounder chirps to indicate that the 
detector needs replacing. To silence the detector, push the test/
hush button. The detector also begins signaling a trouble when the 
CO sensor is approaching end-of-life. When connected to a Listed 
control panel, the trouble relay can report a trouble condition locally 
at the panel and optionally at the central station, if the system is 
monitored. 

Common trouble relay: 

The trouble relay opens to indicate a 

trouble condition upon lost power, CO sensor cell trouble, or cell 
end-of-life.

Installation

The 250-CO Carbon Monoxide Detector is a four-wire device 
designed to use a Class 2 output from a control panel or auxiliary 
power supply Listed to UL 985 or 864 standards.

All wiring must conform to the NFPA 70 National Electric Code, UL 
2075, NFPA 720, an applicable codes. Use 14 to 22 AWG wire.

WARNINGS: 

Connect the CO detector only to a zone dedicat-

ed exclusively for CO detection and that is monitored 24 hours 
a day. Do not connect to an initiating circuit with fire or security 
devices. Failure to properly install, test, and maintain a CO 
detector may cause it to fail, potentially resulting in loss of life.

The 250-CO/240-COe adapter plate

Use the 250-COPLT-5PKG adaptor plate when replacing a 240-
COe with a 250-CO to cover the footprint of the 240-COe. For 
example, use the plate to cover any paint discoloration left behind 
from the 240-COe.

Отзывы: