4 / 4
P/N 3102000-
EN • REV 002 • ISS 16MAR18
Table 7: Directional sound characteristics (vertical pattern) , per
CAN/ULC-S525
Angle (°) [1]
Sound output (dBA)
90 (Ref)
0 (Ref)
80 and 110
−
3
39 and 125
−6
[1] Angles are measured from a perpendicular axis;
positive angles are
up.
Table 8: Indoor strobe output (candela)
Lens
Standard D
C
B
A
Clear
UL 1971
15
29
70
87
Table 9
: Outdoor strobe output (candela at −35°C)
Lens
Standard
D
C
B
A
Clear
UL 1638
6
12
28
35
Table 10
: Outdoor strobe output (candela at −40°C)
Lens
Standard
D
C
B
A
Clear
CAN/ULC
-
S525
1
3
8
10
Table 11: Horn-strobe operating current in RMS (A), continuous
Setting
D
C
B
A
16 to 33
VDC
127
168
297
351
16 to 33
VFWR
218
239
393
422
24
VDC
107
130
210
238
24
VFWR
190
222
325
356
Regulatory information
UL/ULC rating
Horn-
strobe: Regulated 24 DC and 24 FWR.
This device was tested to the regulated
24 DC/FWR operating voltage limits of
16 V and
33
V. Do not apply 80% and 110% of these
values for system operation.
FCC compliance
This device complies with part 15 of the FCC
Rules. Operation is subject to the following two
conditions: (1) This device may not cause harmful
interference,
and (2) this device must accept any
interference received, including interference that
may cause undesired operation.
ICES compliance
This Class B digital apparatus complies with
Canadian ICES
-003.
Environmental
class
Indoor and outdoor
Synchronization
Meets UL 1971
and CAN/ULC-S526
requirements.
Maximum allowed resistance between any two
devices is 20
Ω. Refer to specifications for
compatible synchronization sources, this strobe,
and the control panel to determine allowed wire
resistance.
Agency
listings
UL 1971, UL 1638, UL 464, CAN/ULC
-
S525,
CAN/ULC
-
S526
Contact information
For contact information, see www.edwardsfiresafety.com.
firealarmresources.com