Figure 4: Jumper setup and terminal block
Item In
Out
(1)
High output
Low output
(2) Temporal
tone
Steady
(continuous)
tone
Maintenance
Note:
Do not change the factory-applied finishes.
This unit is shipped from the factory as an assembled unit; it
contains no user-serviceable parts and should not be
disassembled.
Perform a visual inspection and an operational test twice a
year or as directed by the local authority having jurisdiction.
Specifications
Operating voltage
24 VDC
Strobe operating current 320 mA at 24 VDC
Horn operating current
See Table 2 below
Sound output
See Table 3 below
Operating temperature
Indoor
UL
outdoor
32 to 120°F (0 to 49°C)
−
35 to 150°F (
−
37 to 66°C)
Relative humidity
Indoor
Outdoor
93% noncondensing
98% noncondensing
Table 2: Maximum horn operating current [1]
Voltage
Low Volume
High Volume
24 VDC
20 mA
48 mA
[1] Horn and strobe currents are additive when connected in parallel.
Table 3: Anechoic chamber, average peak sound output (dBA) [1]
Method
Low High
24 VDC
95
101
[1] Sound level output at 10 ft. (3.05m)
Regulatory information
Manufacturer
Edwards, A Division of UTC Fire & Security
Americas Corporation, Inc.
8985 Town Center Parkway, Bradenton, FL
34202, USA
Year of
manufacture
The first two digits of the date code (located on
the product identification label) are the year of
manufacture.
UL rating
24 DC
Environmental
class
Indoor, outdoor
North American
standards
Meets: UL 464 and UL 1638
FCC compliance
This equipment has been tested and found to
comply with the limits for a Class A digital device,
pursuant to Part 15 of the FCC rules and
regulations.
Contact information
For contact information, see www.edwardssignaling.com.
P/N 3100285 • REV 2.0 • ISS 22JUL11