P/N 3100796-

EN • REV 04 • ISS 16JAN15

 

 

Figure 2: Wiring installation and connections 

 

(1)  Power supply wires from selected AC or DC voltage source for 

signal (2X) 

(2)  1/2 in. NPT conduit (not supplied) attached to outlet box 

(3)  Outlet box suitable to hazardous location 

(

4

Green wire for earth ground

 

(5)  1/2 - 

14

 NPT nipple (not supplied) 

(6)  Adaptatone signal 

(7)  Power connection wires from signal (2X) 

(8)  Wire nuts (not supplied) 

(9)  To earth ground 

Maintenance and testing 

Examine the unit semi-annually for external accumulation of dirt. Clean 

if necessary. 
Test the signal monthly or at the intervals required by applicable 

regulations and codes. 

Specifications 

 

Voltage

 

Refer to 

Table 1 

Current 

Refer to 

Table 1 

Weight 

18.4 lb. (8.4 kg)

 

Hazardous locations [1]

 

Ambient temp. 

−31 to 104°F (−35 to +40°C)

 

Nonhazardous locations 

 

Variable ambient temp

−40 to 151°F (−40 to +66°C)

 

[1] Hazardous locations and variable ambient conditions apply only 

where UL Listings are accepted. 

Table 1: Input power 
Model 

Voltage 

Current (A) 

5522M-AQ 
5523M-AQ 

24 VDC

 

0.32 

24 VAC 50/60 Hz

 

0.95 

5522M-Y6 
5523M-Y6 

125 

VDC

 

0.130 

250 VDC

 

0.130 

120 VAC 50/60 Hz

 

0.260 

240 VAC 50/60 Hz

 

0.260 

Table 2: Hazardous locations 
Model number 

Hazardous location 

Temperature code 

5522M-AQ 

5522M-Y6 

5523M-AQ 

5523M-Y6 

Class I, Div. 1, Groups B, C, 

and D 

Class I, Div. 2, Groups A, B, 

C, D

 

T5 (100°C, 212°F

Regulatory information 

 

Ratings

 

ANSI/ISA 12.12.01

 

CAN/CSA C22.2 No. 30 

CAN/CSA C22.2 No. 205 

UL 464

 

UL 1203 

UL 1480

 

 

Contact information 

For contact information

,

 see www.edwardssignaling.com. 

 

(1)

(9)

(6)

(5)

(2)

(3)

(4)

(7)

(8)