2 / 2
P/N 3100796-
EN • REV 04 • ISS 16JAN15
Figure 2: Wiring installation and connections
(1) Power supply wires from selected AC or DC voltage source for
signal (2X)
(2) 1/2 in. NPT conduit (not supplied) attached to outlet box
(3) Outlet box suitable to hazardous location
(
4
)
Green wire for earth ground
(5) 1/2 -
14
NPT nipple (not supplied)
(6) Adaptatone signal
(7) Power connection wires from signal (2X)
(8) Wire nuts (not supplied)
(9) To earth ground
Maintenance and testing
Examine the unit semi-annually for external accumulation of dirt. Clean
if necessary.
Test the signal monthly or at the intervals required by applicable
regulations and codes.
Specifications
Voltage
Refer to
Table 1
Current
Refer to
Table 1
Weight
18.4 lb. (8.4 kg)
Hazardous locations [1]
Ambient temp.
−31 to 104°F (−35 to +40°C)
Nonhazardous locations
Variable ambient temp
.
−40 to 151°F (−40 to +66°C)
[1] Hazardous locations and variable ambient conditions apply only
where UL Listings are accepted.
Table 1: Input power
Model
Voltage
Current (A)
5522M-AQ
5523M-AQ
24 VDC
0.32
24 VAC 50/60 Hz
0.95
5522M-Y6
5523M-Y6
125
VDC
0.130
250 VDC
0.130
120 VAC 50/60 Hz
0.260
240 VAC 50/60 Hz
0.260
Table 2: Hazardous locations
Model number
Hazardous location
Temperature code
5522M-AQ
5522M-Y6
5523M-AQ
5523M-Y6
Class I, Div. 1, Groups B, C,
and D
Class I, Div. 2, Groups A, B,
C, D
T5 (100°C, 212°F
)
Regulatory information
Ratings
ANSI/ISA 12.12.01
CAN/CSA C22.2 No. 30
CAN/CSA C22.2 No. 205
UL 464
UL 1203
UL 1480
Contact information
For contact information
,
see www.edwardssignaling.com.
(1)
(9)
(6)
(5)
(2)
(3)
(4)
(7)
(8)