To direct surface mount the base: 

1.  Remove the two knockouts for mounting screws from the 

signal base bottom. See Figure 1 for the location of the 
knockouts. 

2.  Place the mounting gasket provided in the hardware kit on 

the mounting surface, and mark the center of the three 
holes in the gasket onto the mounting surface. Remove 
the gasket, and then drill a 3/8 in. (9.5 mm) hole at each of 
the marked positions. See Figure 2. 

3.  Install the two rubber expansion plugs provided in the 

hardware kit into the two outer holes in the mounting 
surface as shown in Figure 2. 

4.  Route the field wiring from the required power source for 

the signal (refer to its label for the voltage rating) through 
the center holes in the mounting surface, mounting gasket, 
and signal base. 

5.  Align the holes in the mounting gasket with the holes in 

the signal base. Insert the two screws with lock washers 
provided in the hardware kit through the mounting holes 
inside the base and align the screws with the rubber 
expansion plugs as shown in Figure 2.  

6.  Press the base firmly against the mounting surface and 

tighten the screws.  

7.  Proceed to “Wiring” below for wiring connections.  

Figure 2: Direct surface mounting 

 

Note: 

For direct surface mounting, the 51XBRF series signals 

may be installed in any position. 

WARNING: 

To prevent leakage and a potential shock hazard, 

when mounting outdoors the signal must be installed with the 
lens or dome facing directly up. 

To mount on ½ in. NPT conduit: 

1.  Route the field wiring from the required power source for 

the signal (refer to its label for the voltage rating) through a 
½ in. NPT conduit (not supplied) and through the center 
hole in the signal base. 

2.  Install the base on the conduit.  

3.  Proceed to “Wiring” below for wiring connections. 

To mount on a 4 in. (102 mm) octagon box (indoor 
installation only): 

1.  Remove the two knockouts for mounting screws from the 

signal base bottom. See Figure 1 for the location of the 
knockouts. 

2.  Route the field wiring from the required power source for 

the signal (refer to its label for the voltage rating) through 
the center hole in the base. 

3.  Fasten the base to the octagon box (not supplied) by 

installing the screws supplied with the box through the 
holes in the base.  

4.  Proceed to “Wiring” below for wiring connections. 

Wiring 

To wire 24 VDC models: 

1.  Using wire nuts (not supplied), connect the signal's red 

wire to the positive (+) power source lead and connect the 
black wire lead to the negative (

) power source wire. 

2.  Neatly place the connected wires inside the base, and 

then carefully position the lens/lamp assembly onto the 
base.  

3.  Turn on the power, and then verify that the signal operates 

properly. 

To wire 120 VAC models: 

1.  Using wire nuts (not supplied), connect the signal's black 

wire to hot power source lead and connect the white wire 
lead to the neutral power source wire. 

2.  Connect the green wire to the earth ground connection. 

3.  Neatly place the connected wires inside the base, and 

then carefully position the lens/lamp assembly onto the 
base.  

4.  Turn on the power, and then verify that the signal operates 

properly. 