background image

2

EDS - TECHNICAL INFORMATION

LINEAR SMOKE

DETECTOR RK 75 R

The RK75R is a linear beam smoke detector whose
working is based on the interaction between the smoke
rising in a room and an infrared beam emitted by the
detector and reflected by a special optical reflector
(see fig. 1)
The device has to be installed on one side of the area
to be protected just under the level of the ceiling
and the special reflector (FX/01, FX/02, FX04,
FX/05), chosen according to the required range,
on the opposite side.
We recommend to read and follow our instructions
carefully to install the detector in a correct way.
The device's excellent working results, will widely
compensate the time spent in reading these
instructions.

1 - OPERATING  INSTRUCTIONS

1.1

 - Unmount the detector's body from the flush

mounting box taking off  the 4 screws.

1.2

 - Install the flush mounting box safely inside the

wall. Be careful to allign the box border with the
wall's surface. The border has not to be flushed into
the wall more than a few millimeters to avoid optical
problems (fig.2). The box has to be installed  30-50
cm. below the level of the ceiling.

1.3

- Put the guide tube and the cables inside the

box using the blowable holes marked on the box
to pass them through.

1.4 -

 Re-mount the detector's body with the 4 screws.

1.5

 - Install the FX reflector on the opposite wall at

the same height of the detector. It's not necessary that
the reflector is placed perfectly in front of the detector
(an angle difference up to 8 degrees in all directions is
allowed).

2 - WIRING

2.1

 - Connection cables. The small current of the

device (14 mA with normally not powered relay
and 25 mA with normally powered relay) allows
to use small cable sections. A shielded cable (8
wires + external shield) is suggested. With this

kind of cable it’s possible to have a remote signal:

„

the alarm signal (COM-NA-NC terminals)

„

the prealarm signal (OC terminal)

„

the signal level remote measure (TP1 terminal)

„

the  detector  remote control  terminals (sensitivity
adjustment) (TP2-TP3 terminals)

„

the power supply of detector (- and + terminals)

„

the  cable  shielding  must  be wired only on one
side (see fig. 9)

3 - ELECTRICAL CONNECTIONS

3.1

 - Connect the device cables as shown on the

labels facing the terminal boards. The given
symbols indicate what follows:

„

OC  Open  Collector  -  prealarm  output.  It is
possible to connect this terminal to the optional
EV450  to have a sound signal or a led for a
optical signal (see fig.9) for the prealarm,
maximun output current = 50 mA.

„

TP2-TP3.  They  must  be  connected to the
optional external accessory (EV570) for the re-
mote control of the sensitivity. Otherwise it must
be unconnected.

„

TP1.  Test  point 1. It  allows to measure the
signal level.This operation is carried out
connecting the accessory STS01 on the
connector of the printed circuit (see fig. 7) or
using a voltmeter connected between TP1 and
the negative [terminal (-), ground].

„

COM-NA-NC.  Alarm relay.   The  showed
connection  is valid when the detector is not in
alarm condition and the JP3 jump is in position
2-3. The CO-NA-NC terminals are voltage free.

„

(-) (+) input terminals 12/24 Vcc. Select the right
voltage using of the jumper JP4 ( see fig. 8). The
given polarities must be respected.

Содержание RK 75 R

Страница 1: ...1 EDS TECHNICALINFORMATION LINEAR BEAM SMOKE DETECTOR RK 75 R TECHNICAL MANUAL OPERATING INSTRUCTIONS POWER SUPPLY 12 24 V cc ...

Страница 2: ...tionsis allowed 2 WIRING 2 1 Connection cables The small current of the device 14 mA with normally not powered relay and 25 mA with normally powered relay allows to use small cable sections A shielded cable 8 wires external shield is suggested With this kind of cable it s possible to have a remote signal the alarm signal COM NA NC terminals the prealarm signal OC terminal thesignallevelremotemeasu...

Страница 3: ... transmitter emits a conic beam whose form and size related to the distance between the transmitter and the reflector are shown in the figures 5 and 6 It is important that the reflector is in the center of the beam emitted by the transmitter because in these conditions even if some small movements of the wall or surface on which the device is assembled occur caused by the strains the reflector alw...

Страница 4: ...TECHNICALDATA Power supply 12 24 Vcc 10 20 Protection against inversion of polarity Current 10 mAwith normally de energized alarm relay 25mA with normally enegized alarm relay sensitivity adjustment with internal trimmer or remote with the accessory EV570 red LED for the indication of alarm red YELLOW for the indication of prealarm condition output alarm realy 1A 24 V cc prealarmoutput OpenCollect...

Страница 5: ...ternal circuit during the optical alignment SC05 Plastic boxes to lodge 2 modules EV570 or EV450 Dimensions 97x55 5 mm EV570 This module allows to obtain the remote measuring of the detector RK70R signal the remote signaling of the detector prealarm condition the remote set point of the detector sensitivity Dimensions 107x25x42 mm EV450 This module signals acoustically the coming into a prealarm c...

Страница 6: ...6 EDS TECHNICALINFORMATION fx rk70 fig 1 fig 2 fig 5 fig 6 fig 7 fig 3 beam diameter cm distance m infrared emitting area screen hole white screen fig 4 RK70R RK75R ...

Страница 7: ...7 EDS TECHNICALINFORMATION Fig 8 INSIDE VIEW ...

Страница 8: ...8 EDS TECHNICALINFORMATION fig 9 ...

Страница 9: ...zation of the signal level measure the sensitivity remote adjustment the remote indication of the detector prealarm conditions fig 10 The modules EV570 electronic voltmeter show the signal level and permits the sensitivity adjustment of the detectors to which it is connected The module EV450 piezoelectric buzzer gives an acoustical signal when one of the detectors in prealarm condition This module...

Страница 10: ...DS TECHNICALINFORMATION fig 11 The example shows the connection among 10 RK75R detectors the alarm station and the accessories modules EV570 and EV450 Note that every 5 detectors is connected a module EV450 ...

Страница 11: ...11 EDS TECHNICALINFORMATION ...

Страница 12: ...t height P mt 20 position A H1 20 1 mt 19 position B H2 mt 7 a vaulted roof The max covered width M must be mt 15 The detector is to be installed in position A at least mt 30 50 under the beam that is H Q 30 cm c roof with regular beams The same comments as in b case are valid d flat roof The contained informations in this document have been carefully valued and are reliable In every case the EDS ...

Отзывы: