2018KCL(ip) SERIES SIGNAL MONITOR
OPERATIONS MANUAL
Eberle Design Inc.
Page 18
c) Cabinet Temperature: the latched temperature at the time of the fault.
d) AC Line Voltage: the AC Line voltage at the time of the fault.
e) Control Input Status: the latched state and RMS voltages of the Red
Enable input, EE input, Special Function #1 and #2 inputs, and
the WDT monitor.
AC Line (AC) Event Log (40)
a) Event Type: describes the type of AC Line event that occurred.
Power-up - AC on, monitor performed a cold start
Brown-out
- AC Line < drop-out level
Restore
- AC restored from AC brown-out or AC
interruption, no cold start
b) AC Line Voltage: the AC Line voltage at the time of the event.
Manual Reset (MR) Event Log (25)
a) The monitor was reset from a fault by the front panel Reset button or
External Reset input.
Configuration (CF) Event Log (10)
a) Conflict Matrix: the permissive programming for each channel.
b) Yellow Disable: the Yellow Disable programming for each channel.
c) Red Fail: the Red Fail programming for each channel.
d) Dual Indication: the Dual Indication (GY, GR, YR) programming for
each channel.
d) Clearance: the Clearance programming for each channel.
e) Unit Options: 1 Second WDT Timing, WDT Clear on PU, Red Cable
Fault Enable, Recurrent Pulse Disable, Special Function #1
Invert, LEDguard Thresholds, Dual Indication Timing Long,
92Vrms Brownout, MC Coil Invert.
f) Watchdog Programming: Watchdog timing.
g) Configuration Check Value: the value of the 16 bit Check Value for the
reported configuration.
3.2.3 EDI ECCOM MONITOR EVENT LOG EXAMPLES
An example of each type of record is shown below:
1) Previous Fault (PF) Event Log
>> Previous Fail Event Log
>> Monitor ID #73
>> EDI Model 2018KCL, Firmware Type 01, Firmware V5.0, Comm V3.6
>> RMS-Engine Firmware Type 01, RMS-Engine Firmware V2.3
>> ECcom Version 3.6.4
>> Downloaded at 10:23:35 AM Friday, September 22, 2006
>> Number of events = 25
PREVIOUS FAIL EVENT #1 at:
12:12:59 PM Monday, October 2, 2006
Fault = Red Fail Fault
Channel Status:
Ch: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
*
R . . R R . R R R R R R R R R R
. . . . . . . . . . . . . . . .
. . . . . G . . . . . . . . . .
Channel RMS Voltages:
R: 120 1 0 122 122 1 122 121 121 122 122 122 122 122 121 122
Y: 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
G: 0 0 0 0 0 121 0 0 0 0 0 0 0 0 0 0
AC Line = 122 Vrms @ 60Hz
Temperature = 80 F
Red Enable = Active (122 Vrms)