background image

2010ECL-NYC SERIES SIGNAL MONITOR 

OPERATIONS MANUAL 

Eberle Design Inc. 

Page 4 

Failure monitoring is disabled for all channels when the Red Enable input is not active, or the 
EE input (MC Coil) is active. 

2.2.2 RED INTERFACE CABLE FAULT 

When  inserted  into  the  output  file  without  the  Red  Interface  cable  assembly,  the  Signal 
Monitor will operate as a standard 210 Signal Monitor.  The Red Fail, Dual Indication, and 
Clearance monitoring functions will be disabled.  When the Red Cable Fault select option is 
installed (see Section 4.5.4), operating without the Red Interface cable will cause the Signal 
Monitor to enter the fault mode causing the Output relay contacts to close and enabling the 
Stop-Time output to the controller. To indicate this fault mode the Red Fail indicator will be 
illuminated with all channel indicators Off. 

The cabinet should be wired such that the Red Enable input is only interrupted by the Load 
Switch bus being de-energized. Red Fail preemption control to the monitor should use the 
Special Function inputs #1 or #2. 

2.3 GYR-DUAL INDICATION MONITORING 

This monitoring function detects simultaneous indications of active Green and Yellow, Green 
and Red, or Yellow and Red field signal outputs on the same channel. A GYR-Dual Indication 
fault places the Signal Monitor into the fault mode causing the Output relay contacts to close 
and  enabling  the  Stop-Time  output  to  the  controller.  GYR-Dual  Indication  Monitoring  is 
enabled  concurrently  with  Clearance  Monitoring  on  a  per  channel  basis  using  the  SSM 
switches  (see Section  4.2)  and  requires the  controller cabinet  assembly to  be  adapted  for 
Red Signal Monitoring. GYR-Dual Indication Monitoring is disabled for all channels when the 
Red Enable input is not active or the EE input (MC Coil) is active. 

An open or no load condition (i.e., burned-out bulb) may be detected as an active signal due 
to  load  switch  leakage  current  and  may  cause  a  Dual  Indication  fault.  Dual  Indication 
Monitoring may  also  anticipate  a possible  Conflict  in the  event that  a  proceed signal  on  a 
channel is constantly detected as active.  

2.3.1 GY-DUAL INDICATION MONITORING 

This monitoring function detects a simultaneous indication of active Green and Yellow field 
signal  outputs  on  the  same channel.  A  GY-Dual Indication fault  places the Signal  Monitor 
into the fault mode causing the Output relay contacts to close and enabling the  Stop-Time 
output to the controller. It does not require the controller cabinet assembly to be adapted for 
Red Signal Monitoring, and is enabled by setting option switch SW3-4 labeled GY ENABLE 
in  the  ON  position  (see  Section  4.4.4).  GY-Dual  Indication  Monitoring  may  be  enabled 
concurrently  with  GYR-Dual  Indication  Monitoring. When  GY-Dual  Indication  Monitoring  is 
enabled,  all  channels  will  be  individually  monitored  for  simultaneous  indications  of  active 
Green and Yellow field signal outputs. Any channels which have been selected for GYR-Dual 
Indication Monitoring will function as described above in Section 2.3. 

This  monitoring  function  is  intended  to  accommodate  Green  and  Yellow  Dual  Indication 
Monitoring  on  a  five  section  PPLT  signal  head.  It  is  also  useful  if  the  controller  cabinet 
assembly is not adapted for Red Signal Monitoring as in the case of a standard 210 Signal 
Monitor. 

2.4 CLEARANCE (SHORT OR ABSENT YELLOW) MONITORING 

This function detects the absence of a minimum period of active Yellow field signal output 
during  a  Green  to  Yellow  to  Red  sequence.  Clearance  (Sequence)  Monitoring  is  enabled 
concurrently  with  GYR-Dual  Indication  Monitoring  on  a  per  channel  basis  using  the  SSM 
switches  (see Section  4.2)  and  requires the  controller cabinet  assembly to  be  adapted for 
Red  Signal  Monitoring.  Clearance  Monitoring  is  disabled  for  all  channels  when  the  Red 
Enable input is not active or the EE input (MC Coil) is active. 

Содержание 2010ECL-NYC

Страница 1: ...2010ECLip 2018ECL 2018ECLip Firmware version 16AL43xx REVISION AUGUST 2019 pn 888 2010 115 MODEL 2010ECL NYC RMS Signal Monitor Operations Manual NOTE EDI ECCOM SOFTWARE MUST BE UPDATED TO VERSION 4...

Страница 2: ...DWARE COMPATIBILITY WITH THE MT 180 MONITOR TESTER RESISTORS R245 AND R219 HAVE BEEN REMOVED TO DISABLE THIS CIRCUIT IF SPECIAL FUNCTION 2 INPUT IS REQUIRED R245 AND R219 75K OHMS 1 4W SHOULD BE INSTA...

Страница 3: ...2 15 Memory Test 7 2 16 Watchdog Monitoring Disabled Indicator 8 2 17 Red Failure Monitor Disabled Indicator 8 2 18 Diagnostic Display Mode 210E 2010 8 2 18 1 No Fault Diagnostic Display 8 2 18 2 Fau...

Страница 4: ...2 Y VDC FAILED Indicator 24 5 1 3 R WDT ERROR Indicator 24 5 1 4 CONFLICT Indicator 24 5 1 5 RED FAIL Indicator 24 5 1 6 DUAL IND Indicator 24 5 1 7 CLEARANCE Indicator 24 5 1 8 PCA Indicator 25 5 1 9...

Страница 5: ...it Connector P1 33 9 1 1 Sixteen Channel 33 9 1 2 Eighteen Channel 34 9 2 Program Card Connector 34 9 2 1 Sixteen Channel 34 9 2 2 Eighteen Channel 35 9 3 Red Interface Connector P8 36 9 4 EIA 232 Con...

Страница 6: ...ns January 1989 When triggered by the detection of a fault condition which exists longer than the minimum period the Signal Monitor will enter the fault mode causing the Output relay contacts to close...

Страница 7: ...g the Stop Time output to the controller The WDT Latch option see Section 4 5 1 determines whether this WDT Error fault mode is latched through an AC Line brownout or not If the WDT Latch option is no...

Страница 8: ...tile EEPROM device is utilized to retain fault status information and event logs in the event of an AC Line power interruption The correct fault indications will be displayed upon restoration of AC Li...

Страница 9: ...ed out bulb may be detected as an active signal due to load switch leakage current and may cause a Dual Indication fault Dual Indication Monitoring may also anticipate a possible Conflict in the event...

Страница 10: ...e option can be selected see Section 4 5 2 which provides a flash interval of at least 6 seconds and at most 10 seconds in duration following a power up an AC Line interruption or a brownout restore D...

Страница 11: ...from 1000 ms minimum to 10 4 seconds maximum Recurrent Pulse detection can be disabled with the RP DISABLE option switch SW3 2 see Section 4 4 2 2 8 EXIT FLASH When the Signal Monitor series exits th...

Страница 12: ...DIAGNOSTIC indicator on the front panel will illuminate to indicate a monitor hardware and or firmware failure This type of failure is configured as latching With latching operation only a loss of AC...

Страница 13: ...can display the active Green Yellow and Red field status individually To enter this display mode depress and hold the Reset button Each time the Reset button is activated and held the next set of col...

Страница 14: ...he model 210E unit has not been triggered by a fault the fault status display mode will show the Green Yellow and Red channels active when the Program Card was removed If a PCA fault is displayed duri...

Страница 15: ...he model 210ECL unit has not been triggered by a fault the fault status display mode will show the Green Yellow and Red channels active when the Program Card was removed If a PCA fault is displayed du...

Страница 16: ...A channel pair is enabled for FYA operation the Signal Monitor will monitor the FYA logical channel pair for the following fault conditions 2 20 1 1 1 CONFLICT Channel conflicts are detected based on...

Страница 17: ...from the solid Green Arrow 13 14 15 16 to the solid Red Arrow 1 2 3 4 without a minimum clearance time on the solid Yellow Arrow 1 2 3 4 when SSM switch 1 2 3 4 is On The fault channel status will be...

Страница 18: ...Turn Channels Ga Opposing Through Channels Permissive Turn Channels Ra Ya fYa Green Arrow Signal Driver Source 13 2 1 9 Yellow Ped 14 4 3 10 Yellow Ped 15 6 5 11 Yellow Ped 16 8 7 12 Yellow Ped 2 20...

Страница 19: ...ault channel status will also be indicated for the solid Green Arrow channel 9 10 11 12 IF the solid Green Arrow was active The SSM Switch for each 1 3 5 and 7 channel must be in the ON position to en...

Страница 20: ...Section 4 4 8 1 2 20 3 FYAC COMPACT MODE H The Model 2010 NYC does support FYA Mode H operation WARNING IF THE PERMISSIVE FLASHING YELLOW ARROW AND PROTECTED GREEN ARROW CHANNEL ASSIGNMENTS ARE SWAPP...

Страница 21: ...f operation 3 2 2 EDI ECCOM MONITOR REPORT The EDI ECcom software package Version 3 8 or greater is required interfaces a Computer to the ECL and ECLip models The ECcom program will display the Status...

Страница 22: ...Enable Configuration Fault Enable Red Cable Fault enable AC Brownout timing e Watchdog Programming Watchdog Enable Watchdog timing and Watchdog Latch f Configuration Check Value the value of the 16 b...

Страница 23: ...Type 01 Firmware V5 0 Comm V3 6 RMS Engine Firmware Type 01 RMS Engine Firmware V2 3 ECcom Version 3 6 2 Downloaded at 10 13 48 AM Friday September 22 2006 Number of events 10 A symbol indicates that...

Страница 24: ...lse ENABLED Watchdog Timing 1 5 seconds GY Enable DISABLED FYAC Mode H DISABLED LEDguard Thresholds ENABLED Red Fail Enabled by SSM DISABLED Dual Indication Fault Timing 350 500 ms WDT Error Clear on...

Страница 25: ...ction is in hardware flash 4 1 2 SPECIAL FUNCTION PREEMPT INPUTS SF1 SF2 The pins numbered 8 and 6 of Red Interface connector P8 are Special Function SF inputs 1 and 2 respectively NYCDOT These inputs...

Страница 26: ...MMING The Signal Monitor provides switch options to modify the monitor operation The Option switches are labeled OPTIONS SW3 and are located near the program card edge connector 4 4 1 RED FAIL TIMING...

Страница 27: ...ed through an AC Line brownout or not If the WDT Latch select is not jumpered an AC Line brownout condition will reset the WDT ERROR fault mode when the AC Line is restored The WDT Error indicator wil...

Страница 28: ...ates fault or flash mode operation 4 5 7 FYA FLASHRATE MONITOR DISABLE SEL15 The Signal Monitor will respond to an enabled flashing Yellow Arrow signal that is not flashing at a minimum rate see Secti...

Страница 29: ...dicator will illuminate when a controller Watchdog fault is detected If the WD ENABLE switch is placed in the OFF position to disable Watchdog monitoring or the AC Line voltage is below the Watchdog d...

Страница 30: ...to the DTR signal in the false state while a frame is in the transmit queue 5 1 12 CHANNEL STATUS INDICATORS 210E 2010 During normal operation the 210E 2010 model Channel Status indicators will displ...

Страница 31: ...ired inputs for the Signal Monitor to monitor the Red Field Signal outputs It is polarized to insure proper mating with the adapter cable Ejector latches are included to facilitate removal and prevent...

Страница 32: ...ed to interconnect the main microprocessor to the following circuit blocks EEprom U21 Real Time Clock U29 24Vdc Logic Processor U41 Display Multiplexer U1 Program Card and Switch inputs U25 4 and the...

Страница 33: ...hannel The resulting data is transferred to the main MPU via the SPI interface The analog to digital converter U39 provides the voltage measurement data for the RMS Engine approximately every 6 micros...

Страница 34: ...ce fault D No internal watchdog pulses SOLUTIONS A The PCA indicator on the front panel will illuminate Re insert the program card with the diode side of the card facing the front panel slot and depre...

Страница 35: ...Eberle Design Inc Page 30 CAUSES Diode on the Program Card is open or absent SOLUTIONS Check the program card to verify that the required diode is in place If the diode is present then verify all conn...

Страница 36: ...rms Special Function Inputs no detect less than 50 Vrms detect greater than 70 Vrms Watchdog Enable AC level enable greater than 94 _ 2 Vrms disable less than 91 _ 2 Vrms LEDguard Low Threshold Signal...

Страница 37: ...milliseconds typical 1350 milliseconds Dual Indication no fault less than 200 milliseconds fault greater than 500 milliseconds typical 400 milliseconds Dual Indication Long no fault less than 700 mill...

Страница 38: ...YELLOW T UNASSIGNED 17 UNASSIGNED U CHANNEL 10 YELLOW 18 CHANNEL 12 YELLOW V CHANNEL 12 GREEN 19 UNASSIGNED W UNASSIGNED 20 CHASSIS GROUND X UNASSIGNED 21 AC Y DC GROUND 22 WATCHDOG TIMER Z EXTERNAL R...

Страница 39: ...NNEL 11 YELLOW S CHANNEL 11 GREEN 16 CHANNEL 9 YELLOW T CHANNEL 18 YELLOW 17 CHANNEL 18 GREEN U CHANNEL 10 YELLOW 18 CHANNEL 12 YELLOW V CHANNEL 12 GREEN 19 CHANNEL 17 RED W CHANNEL 18 RED 20 CHASSIS...

Страница 40: ...BIT COMMON FF NO CONNECT Mating connector shall be keyed between pins 24 and 25 and also BB and CC The Monitor circuit and the Program Card mate with a 28 56 pin double sided edge card connector havin...

Страница 41: ...NNEL 1 RED 10 CHANNEL 11 RED 20 RED ENABLE Note Pin 4 may be used to connect the monitor chassis to the cabinet CHASSIS GROUND To complete this connection a soldered wire jumper must be placed in loca...

Страница 42: ...5 DCD pin H should be connected to 5 pin D on the Controller Unit connector CTS pin M should be connected to RTS pin J on the Controller Unit connector 9 5 ETHERNET LAN PORT The Ethernet port must be...

Страница 43: ...2010ECL NYC SERIES SIGNAL MONITOR OPERATIONS MANUAL Eberle Design Inc Page 38...

Отзывы: