INSTALLATION, OPERATION

AND MAINTENANCE MANUAL

water cassette

SOFT / SOFT-ECM

RS485 COMMUNICATION NETWORK

MAC ADDRESS TABLE SW2

Cable definition

Utilizzare cavo schermato e intrecciato per rete RS485 costituito da una o due 

coppie intrecciate e schermate aventi le seguenti caratteristiche:

- Impedenza 120 ohm a 1 MHZ

- Capacità max 50pF/m
Esempi:
- Belden 3106A
- Belden 9841

Wiring scheme 

Connect all devices by “daisy chain” topology. 

Network limitations 

The network should not be longer than 700 meters. The maximum amount of 
units per network should not be more than 60 units.

Note: longer distance and higher capacity can be achieved using repeaters 

Installation remarks 

- When pulling the cable, do not use force that may stretch the cable and 

distort its insulation and transmission properties. 
- Do not allow the cable to kink, knot, snag, or fray when rolling it out or se

-

curing it. 
- Do not splice cable segments. Use continuous runs of cable from one device 
to another.
- Do not cinch cables ties too tightly. Do not crush cables when securing them 
with staples or supports. Staple by hand or use staples with depth stops.
- Maintain the color-coding of all cabling throughout your system. 

- Maintain wire twisting and run the cable jacket as closely as possible to the 

termination point. 
- Install cables and controllers to minimize the possibility of accidental contact 
with other, potentially hazardous and disruptive power and SOFTing cables.  
Do not run communication cables in the same conduit of electrical cables and 
if you cross an electrical cable, cross at a 90° angle. 
- Do not place communication cables near other bare power cables, SOFTning 

rods, antennas, transformers, steam or hot water pipes, in any conduit, box, 

channel, duct or other enclosure containing power or SOFTing circuits of any 
type. Keep communication cables and controllers at least 2 meters from large 
inductive loads (power distribution panels, SOFTing ballasts, motors, etc.).

Addressing 

Use the attached MAC Address table to define the network addresses of the 
devices.

Termination 

First and last devices in the communication line should be terminated with 

a 120 resistor to prevent signal reflection. When applicable, use the “End of 
Line” jumpers for this purpose. 

Grounding 

Connect one end of the shield (at the end of the communication line) to a 

tested ground (earth). Leave the other end of the shield not connected (on 
the air). 

MAC...Switches ON

0….Not in use
1….1
2….2
3….1,2
4….3
5….1,3
6….2,3
7….1,2,3
8….4
9….1,4
10….2,4
11….1,2,4
12….3,4
13….1,3,4
14….2,3,4
15….1,2,3,4
16….5
17….1,5
18….2,5
19….1,2,5
20….3,5
21….1,3,5
22….2,3,5
23….1,2,3,5
24….4,5
25….1,4,5
26….2,4,5
27….1,2,4,5
28….3,4,5
29….1,3,4,5
30….2,3,4,5
31….1,2,3,4,5
32….6
33….1,6
34….2,6
35….1,2,6
36….3,6
37….1,3,6
38….2,3,6
39….1,2,3,6
40….4,6
41….1,4,6
42….2,4,6
43….1,2,4,6
44….3,4,6
45….1,3,4,6
46….2,3,4,6
47….1,2,3,4,6
48….5,6
49….1,5,6
50….2,5,6
51….1,2,5,6
52….3,5,6
53….1,3,5,6
54….2,3,5,6
55….1,2,3,5,6
56….4,5,6
57….1,4,5,6
58….2,4,5,6
59….1,2,4,5,6
60….3,4,5,6

Содержание SOFT NC

Страница 1: ...SOFT SOFT ECM 2015 3 Installation operation and maintenance manual...

Страница 2: ...operations if any should neither transit nor stop close to the operation area Electric energy and grounding systems are to be connected by expert and qualified personnel in compliance with standards...

Страница 3: ...ystem 8 Cassettes with a control board that is managed onboard 8 Cassettes with and without a control board that is managed onboard 8 INSTALLATION OF AUXILIARY DRAIN PAN 8 CONDENSATE DRAINAGE 9 ELECTR...

Страница 4: ...Coil numbers n 1 1 1 1 1 Hydraulic fitting ISO 228 female gas 1 2 1 2 3 4 3 4 3 4 Air supply in adjacent room mm 150 150 150 150 150 Air supply in adjacent room BxH mm 300x150 300x150 300x150 300x150...

Страница 5: ...tting ISO 228 female gas standard coil 1 2 1 2 1 2 1 2 1 2 1 2 auxiliary coil 1 2 1 2 1 2 1 2 1 2 1 2 Air supply in adjacent room mm 150 150 150 150 150 150 Air supply in adjacent room BxH mm 300x150...

Страница 6: ...ate collecting system comprising internal plastic tray for collecting condensation coming from the heat exchanger external auxiliary plastic tray for collecting condensation coming from the valves and...

Страница 7: ...e grille in the right position for correct connection of the receiver panel to the unit Establish the position and size of the hole in the ceiling using the cardboard mounting template pic 06 To fix t...

Страница 8: ...Always use suitably sized wrenches to fix or slacken the water pipes It is essential to insulate pipes valves and connections correctly in order toavoid the formation of condensation which could drip...

Страница 9: ...te water from the basin to the discharge pipe before blocking the dropped ceiling If the condensate drainage alarm is activated the zone valve is closed and the fan turned off Pic 19 the drain hose is...

Страница 10: ...s 2015 3 10 INSTALLATION OPERATION AND MAINTENANCE MANUAL water cassette SOFT SOFT ECM WIRING DIAGRAM FOR WATER CASSETTE MODEL SOFT NC WATER CASSETTE FORESEEN FOR WALL MOUNTED CONTROL WITH 3 SPEED MOT...

Страница 11: ...015 3 11 INSTALLATION OPERATION AND MAINTENANCE MANUAL water cassette SOFT SOFT ECM WIRING DIAGRAM FOR WATER CASSETTE MODEL SOFT ECM NC Pic 23 WATER CASSETTE FORESEEN FOR WALL MOUNTED CONTROL WITH EC...

Страница 12: ...2015 3 12 INSTALLATION OPERATION AND MAINTENANCE MANUAL water cassette SOFT SOFT ECM WIRING DIAGRAM FOR WATER CASSETTE MODEL SOFT RC Pic 24 WATER CASSETTE WITH INFRARED REMOTE CONTROL WITH 3 SPEED MO...

Страница 13: ...s 2015 3 13 INSTALLATION OPERATION AND MAINTENANCE MANUAL water cassette SOFT SOFT ECM WIRING DIAGRAM FOR WATER CASSETTE MODEL SOFT ECM RC Pic 25 WATER CASSETTE WITH INFRARED REMOTE CONTROL WITH EC MO...

Страница 14: ...ther potentially hazardous and disruptive power and SOFTing cables Do not run communication cables in the same conduit of electrical cables and if you cross an electrical cable cross at a 90 angle Do...

Страница 15: ...Vers 2015 3 15 INSTALLATION OPERATION AND MAINTENANCE MANUAL water cassette SOFT SOFT ECM WIRING DIAGRAM FOR WATER CASSETTE MODEL SOFT ECM RC MASTER SLAVE EXAMPLE OF MASTER SLAVE SYSTEM...

Страница 16: ...ette for applications such as the storage of foods plants precision equipment or works of art The quality of the objects that are stored could deteriorate Do not expose animals or plants to the direct...

Страница 17: ...will flash Adjust the hours using the or buttons Press the Select button the minutes will flash Adjust the minutes using the or buttons Stop Time Press the Select button PROGRAM STOP will flash on dis...

Страница 18: ...lecomando col simbolo sia stata modificata in impostazione manuale simbolo per tor nare alla modalit standard definita dal produttore procedere come segue Press the Select button 5 times the icon will...

Страница 19: ...place the filters On a sunny day leave the cassette running in fan mode for a few hours to allow the inside of the unit to dry completely Remove the plug or turn off the automatic circuit breaker WHAT...

Страница 20: ......

Страница 21: ......

Страница 22: ...With the perspective of improvement and against the continuous action of research and development the Manufacturer might modify even without any prior notice the given technical data...

Страница 23: ......

Страница 24: ...A GROUP S p A Via Montegrappa 67 31020 San Zenone degli Ezzelini TV ITALY Tel 39 0423 567774 Fax 39 0423 567985 info eden clima com www eden clima com info aliseogroup com www aliseogroup com...

Отзывы: