If Ti < 23°C, fan is OFF.
If 23 < Ti < 35°C, fan runs at minimum speed
If Ti > 35°C, fan runs at setted speed.
ELECTRICAL CHARACTERISTICS
- Power supply
1Ph from 185 to 255 VAC, 50/60Hz
- Power consumption
Less than 8 VA in stand-by
- Valve activation time delay
3 minutes ± 5 seconds
Temperature:
- Room temperature accuracy
±1°C
- Coil temperature accuracy
±2°C
- Storage temperature
0÷70°C
- Operating temperature
10÷70°C
- Setting temperature range
18÷30°C (+1°C step)
- ON/OFF temperature differential
1°C
Pic. 52
Pic. 53
OPERATING DETAIL
CASSETTE WITH A CONTROL BOARD THAT IS MANAGED ONBOARD
The following commands be given by the buttons on the eall-mounted control.
Switching on/off
Press the
POWER
button to switch the cassette on or off. When the system has
been switched on, it will operate according to the settings shown on the display.
The
POWER
indicator light on the display comes on.
Fan
Press the
FAN
button to select the fan speed (high, medium, low or auto mode).
The display instantly shows the operating status.
Auto mode
When the fan speed is set in the
AUTO
mode, the speed is adjusted automa-
tically according to the difference between the room temperature and the set
temperature:
- If the difference is 3°C or more, the speed is
HIGH
;
- If the difference is 2°C, the speed is
MEDIUM
;
- If the difference is 1°C or less, the speed is
LOW
.
Function mode:
- Ventilation (
FAN
)
- Air-conditioning (
COOL
)
- Dehumidifying (
DRY
)
- Heating (
HEAT
)
- Automatic (
AUTO
)
FAN
The writing
FAN
appears on the air-conditioner control display. In this mode the
unit operates as a fan only. The
SLEEP
and
buttons are not used.
COOL
The writing
COOL
appears on the air-conditioner control display. The unit ope-
rates in the air-conditioning mode.
- the zone valve starts if Troom
≥
Tset+1
- the zone valve stops if Troom
≤
Tset
In any case activation of the zone valve is subject to 3 minutes delay each time
it stops.
DRY
The writing
DRY
appears on the air-conditioner control display. The unit ope-
rates in the dehumidifying mode to reduce the percentage of humidity in the
room.
HEAT
The writing
HEAT
appears on the air-conditioner control display. The unit ope-
rates in the air-conditioning mode.
- the zone valve starts if Troom
≤
Tset -1
- the zone valve stops if Troom
≥
Tset
In any case activation of the zone valve is subject to 3 minutes delay each time
it stops.
FAN
COOL
DRY
HEAT
AUTO
Pic. 54
HOURS
START SLEEP MODE
ROOM TEMPERATURE
Increase of 1°C
after 1 hour
COOLING
TIPS FOR BEST USE
ENERGY SAVING
AUTO
The writings
COOL
and
HEAT
appear on the display simultaneously.
Temperature setting
The setting temperature can be set in the range of 18°C-30°C by pressing
button. The LCD on the display unit will show the setting temperature.
Louver swing
Press the
button to start/stop louver swing.
SLEEP mode
Press the
SLEEP
key to activate the mode. The
symbol will appear on the di-
splay. In cool air-conditioning mode, the temperature is automatically increased
by 1 °C after an hour. Similarly, in warm air-conditioning mode the temperature
is decreased by 1 °C after an hour.
- Connect the cassette to a dedicated power socket protected by a magnetother-
mal circuit breaker of suitable capacity for the electrical input of the appliance.
- When the water cassette starts or stops, especially in the heating mode, cre-
aking sounds may be heard. This is caused by thermal expansion of the unit
parts.
- Mist may sometimes be produced by the cassette for a few seconds in the co-
oling mode. This is quite normal and is caused by the difference in temperature
between the air
fl
owing out of the appliance and the air in the room.
- Do not place heat sources near to the cassette as this could deform the plastic
parts.
- Do not insert objects into the air intakes or outlets when the cassette is in
operation.
- Do not place objects in a position that may obstruct the passage of the air into
the unit as this could affect appliance ef
fi
ciency.
- Avoid opening and closing doors and windows: the continuous thermal transfer
hinders the unit’s production.
- Do not set a temperature that is too high (in heating mode) or too low (in
cooling mode).
- Avoid installing the unit where it is directly exposed to sunlight.
- Use the timed shutdown to prevent it from being left on unnecessarily.
- Use the
SLEEP
function during the night.
20.0
22.0
0
1
2
AUTO
MINIMUM
MAXIMUM
AVERAGE
TURBO
Содержание CS/4S 21
Страница 1: ...INSTALLATION OPERATION AND MAINTENANCE MANUAL WATER CASSETTES 2009 3...
Страница 2: ...INSTALLATION OPERATION AND MAINTENANCE MANUAL MANUALE IN USO E MANU...
Страница 16: ...Vers 2009 3 water cassettes 16 INSTALLATION OPERATION AND MAINTENANCE MANUAL SECOND PART FOR THE USER...
Страница 23: ...NOTES...
Страница 24: ......
Страница 25: ......