Eden CS/4S 21 Скачать руководство пользователя страница 20

Vers. 2009-3

water cassettes

20

INSTALLATION, OPERATION
AND MAINTENANCE MANUAL

to the valve output.

Remedy

: check the coil water temperature and correct valve operation. 

c) The incorrect mode has been set:
    - there is hot water when the mode is set on cooling;
    - there is cold water when the mode is set on heating;  

4) TIMER indicator light blinks continuously (Pic. 50A):

Air temperature sensor and water temperature sensor are damaged or not con-
nected.

5) TIMER indicator light blinks intermittently (Pic. 50B): the 

fi

 lters must 

be cleaned.

When the cassette has been operating for more than 500 hours, a warning is 
displayed as a reminder to clean the 

fi

 lter.

6) The POWER indicator 

fl

 ashes intermittently (Pic. 50 C).

Only for cassettes HC4S.
Safety switch (LS1) open.

ATTENTION: reset by cutting off the power for at least 10 seconds. Una 
volta ridata tensione l’unità rientra in allarme se dopo 3 minuti questo sta-
to persiste. Once the power returns the unit will return to the alarm status 
if this persists after 3 minutes.

Pic. 51

Set

FAN SPEED

COIL TEMPERATURE [Ti]

slow

OFF

CONDENSATE DRAIN PUMP OPERATION SPECIFICATIONS

PRE-HEATING FUNCTION

CASSETTE WITH A CONTROL BOARD THAT IS MANAGED ONBOARD
Cool

 - The unit is running: the pump is always on until the set temperature is 

reached.
The unit is turned off from the remote control or the set temperature has been 
reached: when the water reaches the 

fl

 oat, the contact is opened and the pump 

is activated for 3 minutes; after which, if the 

fl

 oat does not close the contact 

once again (water discharge), the unit will enter an alarm status.

Dry

 - cool.

Heat

 - The unit is running or was turned off from the remote control: the pump 

is activated by the 

fl

 oat.

Fan

 - heat.

Auto

If the unit is in the cool mode, the pump follows the cool operation. 
If the unit is in the heat mode, the pump follows the heat operation.

CASSETTE WITHOUT A CONTROL BOARD THAT IS MANAGED ONBOARD

The condensate discharge pump is activated when the water level inside the 
main condensation basin reaches the 

fl

 oat and opens its contact. A timer acti-

vates the condensate discharge pump for about 3 minutes (empty-basin cycle), 
which is repeated until the 

fl

 oat’s contact is closed.

No discharge condensate alarms are foreseen.

CASSETTE WITH A CONTROL BOARD THAT IS MANAGED ONBOARD

Pre-heating function is used to avoid cold air in 

HEAT

 mode when the valve is 

open. The valve remains open also if within 3 minutes the coil temperature has 
not reached the 35°C.

0

5

10

30

15

20

25

35

40

45

50

23

°C

Pic. 49

WALL MOUNTED CONTROL – SAME FUNCTIONS AS THE REMOTE CONTROL

WALL-MOUNTED CONTROL OPERATIONS 

TROUBLESHOOTING

CASSETTE WITH A CONTROL BOARD THAT IS MANAGED ONBOARD

CASSETTE WITH A CONTROL BOARD THAT IS MANAGED ONBOARD

1 Function 

mode: 

Cool = cooling; Heat = warming; Fan = only ventilation; 

Auto = only for units with 4 pipes (cooling and heating).

2  Select the desired room temperature (18 °C to 30 °C)
3  Select the fan speed (4 pos automatic)
4 Night 

function:

5  Setting the hour.
6  Setting the minutes.
7  Turns the unit on or off
8  Enables or disables the movement of the vents
9  Turbo function: warms or cools for 30 min at the maximum speed
10  Setting the current time.
11  Daily timer on
12  Daily timer off
Refer to the I.R. remote control to learn the functions

Self-diagnosis

The system comes with a self-diagnosis circuit to monitor the microprocessor 
functions. In the event of malfunction this circuit automatically resets the micro-
processor. 

System memory

The system stores the set parameters (such as the operating status, fan speed, 
etc.) in its non-volatile storage. After a power failure, the cassette will auto-
matically resume operation with the same parameters that were set prior to 
the blackout (except the 

SLEEP

 and 

TIMER

 modes which will be erased). Any 

change to the parameters will be saved in the non-volatile storage after 5 se-
conds.

Situation of normal operation

The 

POWER

 indicator light is on if the cassette was switched on via the I.R. 

remote control.
The 

TIMER

 indicator light is on if the 

AUTO START

 and 

AUTO STOP

 modes 

are active.
The 

SLEEP

 indicator light shows the temperature compensation during the 

SLEEP

 mode.

1) The POWER, SLEEP and TIMER indicator lights blink continuously: 

The 

system is protected by the cutting off of power to all the outputs.
This type of alarm is generated by one events:
- safety 

fl

 oat with an always open contact (the main condensation basin is full 

of water).

Remedy:

 check the condensate drainage circuit  (pump, 

fl

 oat, drain hoses): 

inclination and height.

2) The SLEEP indicator lights blink continuously (Pic. 50A):

- Coil water temperature above 80 °C.

Remedy

: check coil water temperature.

3) The POWER indicator 

fl

 ashes intermittently (Pic. 50 B).

This type of alarm can be caused by three events:
a) When 3 minutes have elapsed from the start of the 

COOL

 or 

DRY

 cycles, coil 

temperature is above 25° C. The system is protected by the cutting off of power 
to the valve output.

Remedy

: check the coil water temperature and correct valve operation.

b) When 3 minutes have elapsed from the start of the 

HEAT

 cycle, coil tempe-

rature is not above 20° C. The system is protected by the cutting off of power 

7

8

9

10

11

12

1

2

3

4

5

6

Fig. 50

ON
OFF

B

ON
OFF

A

ON
OFF

C

Содержание CS/4S 21

Страница 1: ...INSTALLATION OPERATION AND MAINTENANCE MANUAL WATER CASSETTES 2009 3...

Страница 2: ...INSTALLATION OPERATION AND MAINTENANCE MANUAL MANUALE IN USO E MANU...

Страница 3: ...ALLATION OF AUXILIARY DRAIN PAN 9 CONDENSATE DRAINAGE 9 ELECTRIC POWER CABLES AND VALVE PASSAGE 10 ELECTRICAL CONNECTIONS 10 Eccess to the control panel 10 WIRING DIAGRAM FOR CASSETTE 2 PIPE SYSTEM WI...

Страница 4: ...Hu mm 280 280 280 280 240 305 305 305 Depth of the panel Lp mm 720 720 720 720 953 953 953 953 Lenght of the panel Pp mm 720 720 720 720 953 953 953 953 Height of the panel Hp mm 65 65 65 65 80 80 80...

Страница 5: ...280 280 280 240 305 305 305 Depth of the panel Lp mm 720 720 720 720 953 953 953 953 Lenght of the panel Pp mm 720 720 720 720 953 953 953 953 Height of the panel Hp mm 65 65 65 65 80 80 80 80 Air su...

Страница 6: ...ture is quick and easy 4 adjustable louvers ensure best air distribution throughout the room Central intake grille with filter for cleaning the air The grille may be removed to access internal parts w...

Страница 7: ...r correct connection of the receiver panel to the unit Establish the position and size of the hole in the ceiling using the external dia meter of the cardboard mounting template pic 07 To fix the unit...

Страница 8: ...correctly or it will not go on 2 The unit has a protection system that intervenes by closing the water flow via the valve in cases such as a Where there is a condensate discharge problem if the valve...

Страница 9: ...f condensation which could drip into suspended ceilings causing considerable problems The water connections are fixed to the unit body to avoid damage when pi pes are connected It is advisable to tigh...

Страница 10: ...with European standard EN60947 3 Make sure that the electrical system is suitable for providing not only the working current required by the appliance but also the necessary current for powering house...

Страница 11: ...rain pump 230Vac 50Hz FS Float switch NC LS1 SM limit switch 60x60 cassette Safety switch 90x90 cassette when opening the filter panel the unit wii stop Com Common P1 P2 Pn Terminals C3 Condenser FS P...

Страница 12: ...FS Float switch NC LS1 SM limit switch 60x60 cassette Safety switch 90x90 cassette when opening the filter panel the unit will stop Com Common P1 P2 Pn Terminals C3 Condenser L N L N C FS P23 P18 P19...

Страница 13: ...HOUT A CONTROL BOARD THAT IS MANAGED ONBOARD Pic 28 LEGENDA Connector Earth M1 Fan motor 230Vac 50Hz SM Louver motor 230Vac 50Hz DP Drain pump 230Vac 50Hz FS Float switch NC DT Timer C1 Condenser FRON...

Страница 14: ...filter panel the unit wii stop Com Common P1 P2 Pn Terminals C3 Condenser LEGENDA Connector Earth L Phase N Neutral M1 Fan motor 230Vac 50Hz SM Louver motor 230Vac 50Hz DP Drain pump 230Vac 50Hz FS F...

Страница 15: ...LS1 SM limit switch 60x60 cassette Safety switch 90x90 cassette when opening the filter panel the unit will stop Com Common P1 P2 Pn Terminals C3 Condenser LEGENDA Connector Earth L Phase N Neutral M...

Страница 16: ...Vers 2009 3 water cassettes 16 INSTALLATION OPERATION AND MAINTENANCE MANUAL SECOND PART FOR THE USER...

Страница 17: ...in order to identify possible damage After prolonged use apply to specialised service personnel to control the instal lation conditions of the air conditioner Do not use flammable gas near the air con...

Страница 18: ...the corresponding part on the display will flash the current time is set via the key Once this is com pleted confirm the time by pressing the SEND key and the acoustic signal will verify that the corr...

Страница 19: ...REMOTE CONTROL Keep the key pressed for 2 seconds to block the remote control Keep the key pressed for 2 seconds to unblock the remote control ECONO Press the ECONO key in cooling heating or automatic...

Страница 20: ...c 49 WALL MOUNTED CONTROL SAME FUNCTIONS AS THE REMOTE CONTROL WALL MOUNTED CONTROL OPERATIONS TROUBLESHOOTING CASSETTE WITH A CONTROL BOARD THAT IS MANAGED ONBOARD CASSETTE WITH A CONTROL BOARD THAT...

Страница 21: ...the room HEAT The writing HEAT appears on the air conditioner control display The unit ope rates in the air conditioning mode the zone valve starts if Troom Tset 1 the zone valve stops if Troom Tset I...

Страница 22: ...SEASON MAINTENANCE Clean and replace the filters On a sunny day leave the cassette running in fan mode for a few hours to allow the inside of the unit to dry completely Remove the plug or turn off the...

Страница 23: ...NOTES...

Страница 24: ......

Страница 25: ......

Страница 26: ...With the perspective of improvement and against the continuous action of research and development the Manufacturer might modify even without any prior notice the given technical data...

Отзывы: