NORMAL SEqUENCE OF OPERATION

On a call for heat, the thermostat will actuate, completing   

the   circuit   to  the  boiler.  In  turn,  the ignition systems 

are activated and ignition will begin.

In the event of a low water condition, an automatic low 

water cut-off device will interrupted power between the low 

water cut-off and the burner. The burner will remain off until 

the low water condition is corrected, (i.e., manually restore 

boiler water or utilize a water feeder device which will 

automatically restore water to its normal operating level).

IMPORTANT TO THE INSTALLER - 

Before putting the 

Refill boiler to its normal water line.

boiler in operation, test the mechanical low water cut-off 

device for proper operation. While burner is on, open the 

blow-off valve located in the lower portion of the cut-off 

body. This will drain the water quickly from the cut-off body 

and break the circuit to the burner. If it does not, replace 

control.

!

  

WARNING

WATER WILL BE BOILING HOT.

OPERATING INSTRUCTIONS

The venting system should be inspected at the start of each 

heating season. Check the vent pipe from the boiler to the 

chimney for signs of deterioration by rust or sagging joints. 

Repair if necessary.
Remove the vent pipe at the base of the chimney or 

flue and, using a mirror, check for obstruction and verify 

compliance to the latest revision of the NFPA 211.
The lever of the pressure relief valve 

(Figure #14)

 on the 

boiler should be operated periodically to make sure that it is 

functioning properly.

MOUNTING

(BOTH SIDES)

LOWER FRONT

JACKET PANEL

PRESSURE RELIEF

VALVE

TOP JACKET

PANEL

1/4" SLOT

BURNER

ELECTRICAL

DISCONNECT

28"

WATER

ELECTRONIC LOW

WATER CUT OFF

INSPECTION

COVER

LINE

SCREWS

HOT 

The pressure relief valve should open before the steam 

pressure exceeds the 15 lb. reading on the gauge. If this 

pressure is exceeded and the pressure relief valve leaks 

steam when the boiler is operating at normal pressures, it 

should be immediately replaced. Corrosion can build up 

rapidly at the valve seat and prevent its functioning as a 

safety device.

 

START-UP AND ADJUSTMENT OF OIL BURNER

(See oil burner instructions for nozzle and electrode setting)

!

  

CAUTION

DO NOT SET FIRE vISUALLY.

Instruments are the only reliable method 
to  determine  proper  air  adjustments. 
An improperly adjusted burner causes 
soot  and  high  fuel  bills  because  of 
incomplete  combustion  of  the  fuel  oil. 
This  in  turn  may  require  excessive 
boiler maintenance, service costs, and 
in  some  instances,  house  cleaning 
or  redecorating.  A  competent  service 
mechanic should be consulted to make 
the  proper  adjustments  with  a  smoke 
tester, CO

2

 indicator, and draft gauge. 

NoTE:

 Bacharach or Dwyer test kits include these 

instruments.

Check oil burner nozzle to make certain it is tight in 

A. 

adapter. Burner mounting bolts should be tight.

Check electrode setting, as they may have been jarred 

B. 

out of position during transportation.

Lubricate burner motor if necessary.

C. 

!

  

WARNING

Discharge  will  be  boiling  hot  water  and 
steam.

Figure #14

Содержание UTICA SFE0365

Страница 1: ...RED CAST IRON BOILER INSTALLATION OPERATION MAINTENANCE MANUAL Utica Boilers 2201 Dwyer Ave Utica NY 13501 www ecrinternational com An ISO 9001 2008 Certified Company MODEL NUMBERS SFE0365 SFE3100 SFE4100 SFE4125 SFE4150 SFE5175 SFE5200 SFE6225 SFE7275 ...

Страница 2: ... which if not avoided may result in minor or moderate injury DANGER Indicates a hazardous situation which if not avoided WILL result in death or serious injury WARNING 1 Keep boiler area clear and free from combustible materials gasoline and other flammable vapors and liquids 2 DO NOT obstruct air openings to the boiler room 3 Modification substitution or elimination of factory equipped supplied o...

Страница 3: ...o brand all others are Delavan 6 The electrical service is 120 Volts 15 Amps 60 Hz 7 The MEA number for this boiler series is 182 86E 8 The MEA number for the AFG Beckett Burner used in this boiler series are AF 156 77 E AFG 213 83 E AFII 85 24 92 E AFII 150 456 90 E Ratings Data And Dimensions STANDARD EQUIPMENT Crated boiler flush jacket oil burner target wall liner ASME relief valve steam water...

Страница 4: ... Society of Mechan ical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers ANSI ASME No CSD 1 Locate boiler in front of final position before removing crate Provide a level solid base as near chimney as possible and centrally located with respect to the heat distribution system as practical WARNING Boilermaynotbeinstalledoncombustible flooring Allow 24 inches in ...

Страница 5: ...side buildings the confined space shall be provided with two permanent openings one starting 12 inches from the top and one 12 inches from the bottom of the enclosed space Each opening shall have a minimum free area of 1 square inch per 1 000 BTU per hour of the total input rating of all appliances in the enclosed space but must not be less than 100 square inches These openings must freely communi...

Страница 6: ... assumed that wood louvers will have 20 25 free area and metal louvers and grills will have 60 75 free area Louvers and grills shall be fixed in the open position or interlocked with the boiler so that they are opened automatically during boiler operation space shall be provided with two permanent openings one commencing within 12 inches from the top and one commencing 12 inches from the bottom of...

Страница 7: ... T TRAP HIGH LEVEL SPILL DO NOT USE WITH CONDENSATE PUMP TO RECEIVER TANK STEAM MAIN TRAP PUMPED RETURN TO SYSTEM FROM RECEIVER TANK FROM RECEIVER TANK STOP VALVE TO RECEIVER TANK STOP VALVE PIPING FOR BUILT IN DOMESTIC HOT WATER HEATER PIPING FOR BUILT IN DOMESTIC HOT WATER HEATER COLD WATER IN UNTEMPERED HOT FLOW REGULATOR TEMPERING VALVE COLD WATER DOMESTIC HOT WATER T P VALVE UNTEMPERED HOT WA...

Страница 8: ...drawn into the fuel pump making it difficult to maintain oil pressure at the nozzle Do not run overhead fuel lines from tank to oil burner WARNING Boiler is to be vented by natural draft and shall not be connected into any portion of a mechanical draft operating system under a positive pressure Inspect chimney to make certain it is constructed according to the latest revision of the NFPA 211 Local...

Страница 9: ...st conform with the latest revisions of the National Electrical Code ANSI NFPA No 70 and or local authority having jurisdiction When an external electrical source is utilized the 1 boiler when installed MUST BE electrically grounded in accordance with these requirements oil tank and piping Install a fused disconnect switch between boiler and 2 meter at a convenient location When the boiler is equi...

Страница 10: ...20V 24V 40VA 1K1 Relay Contacts Wire Connection TR 2 Transformer 120V 24V 50VA 1K2 Relay Contacts LWCO Low Water Cut Off LGV24 Volt Gas Valve LS Limit Switch EWF Electric Water Feeder PS Pressure Switch MS Manual Switch PG Power Generator STEAM WIRING W BECKETT BURNER NOTE Not all components listed are used in all control systems WIRING CODE Line Voltage By Factory Low Voltage By Factory Line Volt...

Страница 11: ...11 STEAM WIRING W RIELLO BURNER WIRING CODE Line Voltage By Factory Low Voltage By Factory Line Voltage By Installer Low Voltage By Installer ...

Страница 12: ...12 STEAM WIRING W CARLIN BURNER WIRING CODE Line Voltage By Factory Low Voltage By Factory Line Voltage By Installer Low Voltage By Installer ...

Страница 13: ...e Figure 14 on the boiler should be operated periodically to make sure that it is functioning properly MOUNTING BOTH SIDES LOWER FRONT JACKET PANEL PRESSURE RELIEF VALVE TOP JACKET PANEL 1 4 SLOT BURNER ELECTRICAL DISCONNECT 28 WATER ELECTRONIC LOW WATER CUT OFF INSPECTION COVER LINE SCREWS HOT The pressure relief valve should open before the steam pressure exceeds the 15 lb reading on the gauge I...

Страница 14: ...nce RIELLO SETTINGS Boiler No Burner No Air Damper Pump Press Turb Nozzle Fur nished 3100 F 5 3 6 150 PSI 1 85 80W 4125 F 5 4 150 PSI 3 1 10 60W 4150 F 5 6 150 PSI 4 1 25 60W 5200 F 10 5 150 PSI 0 1 75 80B CARLIN SETTINGS Boiler No Burner No Air Damper Pump Press Head Bar Nozzle Fur nished 3100 EZ 1 0 85 150 PSI 85 1 00 85 70B 4125 EZ 1 1 00 1 10 150 PSI 1 10 1 25 1 10 70B 4150 EZ 1 1 25 1 35 150 ...

Страница 15: ...riodically to make sure that it is functioning properly Refill boiler to its normal water line C Primary Control and Flame Sensor To Check Flame Failure 1 simulate by shutting off oil supply with hand valve while burner is on Sixty seconds after flame out the safety switch locks out ignition stops motor stops and oil valve when used closes To restart open oil supply valve and reset safety switch I...

Страница 16: ...nd other flammable vapors and liquids The free flow of combustion and ventilation air to the boiler and boiler room must not be restricted or blocked WARNING Discharge will be boiling hot water and steam The safety valve should open before the steam pressure exceeds the 15 lb reading on the gauge Figure 14 If this pressure is exceeded and the safety valve does not open it must be replaced If the s...

Страница 17: ... X Inspect and Clean Appliance X Inspect Oil Line Size Leaks X Inspect Electrical Connections X Install New Filter X Room Make up Air X Electrode Setting X Proper Light Off Hot Cold X Service Record Date Nozzle Pump Pressure PSI Line Voltage Motor Amps Smoke Draft CO2 or O2 Flue Temp F Size Angle Type O F INF Controls and Safety Devices X Nozzle Size Angle Type Pump Pressure Vacuum Line Voltage Mo...

Страница 18: ...GE WATER LEVEL 1 4 240007394 BRASS SIPHON OFF CENTER LOOP 62208 1 5 14693057 TEE BRASS 1 4 1 6 240007412 PIPE BRASS 1 4 x3 1 7 240007411 ELB BRASS 1 4 90 STREET 2 8 GA 003 00 GAUGE PRESSURE STEAM 1 9 240007160 ELWCO CG450 P 2060 CYCLE GUARD 1 10 SS 001 01 PRESSURE SWITCH PA404A 1009 1 11 1263012 HARN J BOX 22 BECKETT RIELLO 1 240007185 HARN J BOX STEAM CARLIN 12 240007187 HARN BRNR STEAM BECKETT 1...

Страница 19: ...6701 Stud 5 16 18 x 2 4 5 2252501 Support Jacket Brkt 2 6 HW07001 Stud 5 16 x 18 x 1 3 7 HW06901 Nut 5 16 18 Wislock 8 8 HW 016 02 Drain 1 9 PF 004 04 Pipe Fit Bushing 1 x 1 10 2452906 Flue Collector 3 Sec 1 2452902 Flue Collector 4 Sec 2452903 Flue Collector 5 Sec 2452907 Flue Collector 6 Sec 2452908 Flue Collector 7 Sec 11 109007327 Baffle Assy H E Rear 1 ...

Страница 20: ...03 Tie Rod x 20 6 Sec HW 025 09 Tie Rod x 23 7 Sec ITEM PART NO DESCRIPTION QTY 8 100 1 5 01 22 Push Nipple 3 Sec 2 22 Push Nipple 4 Sec 3 22 Push Nipple 5 Sec 4 22 Push Nipple 6 Sec 5 22 Push Nipple 7 Sec 6 9 MS 006 00 Rope Med Density 3 Sec 13 0 Rope Med Density 4 Sec 19 5 Rope Med Density 5 Sec 26 0 Rope Med Density 6 Sec 32 5 Rope Med Density 7 Sec 39 0 10 HW 008 03 Washer ID Flat 3 11 HW 003 ...

Страница 21: ...803 Left Side Panel 4 Sec 21521804 21521804 21521809 21521804 Left Side Panel 5 Sec 21521805 21521805 21521810 21521805 Left Side Panel 6 Sec 21521806 21521806 21521811 21521806 Left Side Panel 7 Sec 21521807 21521807 21521812 21521807 Not Shown Jacket Replacement Kit 3 Sec 3001487AH 3001487C 3001487AC 3001487AD Jacket Replacement Kit 4 Sec 3001488AH 3001488C 3001488AC 3001488AD Jacket Replacement...

Страница 22: ...1 BRNR BECK CF375 UT2602 NOZ 2 25 60B 1050006 BRNR F5 40 SERIES RIELLO 2 PCS BN07007 BRNR F10 40 SER RIELLO 3949071 NEW BRNR OIL EZ1 3100SE STE CARLIN NEW BRNR OIL EZ1 4100SE STE CARLIN NEW BRNR OIL EZ1 4125SE STE CARLIN NEW BRNR OIL EZ1 4150SE STE CARLIN NEW BRNR OIL EZ1 5200SE STE CARLIN 2 BN08001 BURNER OIL FLANGE GASKET 3616 1 3 CD 001 01 CAD CELL FOR BOILERS W BECKETT BURNERS ONLY 1 4 2400088...

Страница 23: ...NOTES ...

Страница 24: ...Date Service Performed Company Name Tech Initials Company Address Phone ...

Отзывы: