81
User Interface Display
Explanation
CH Settings
Allowed Range: 35°F to 100°F (2°C to 38°C)
Default Setting: 70°F (21°C)
If outdoor temperature is greater than Warm Weather
Shutdown Temperature, demand for CH blocked and pumps
stopped.
Allowed Boiler Range: 60°F to 195°F (40°C
to 91°C)
Default Boiler Setting:180° F (82°C)
Boiler capable of operating in Outdoor Reset Mode when
included Outdoor Sensor is connected and proper CH Mode
selected.
If CH Mode = 1, ‘Outdoor Temperature Reset with Thermo-
stat’ or 2, ‘Full Outdoor Reset’ boiler will adjust CH set point
proportional to outdoor temperature as de
fi
ned by Outdoor
Reset Curve below.
Outdoor reset curve adjusted by modifying Design and Mild
Weather reference temperatures. See points A & B of Reset
Curve below.
Calculated CH set point always limited between ‘Reset Curve
Boiler Minimum/Maximum’ temperatures. See points C & D
of Reset Curve below.
Figure A-2 Outdoor Reset Curve
Calculated supply temperature follows thick black line in
graph above based on outdoor temperature.
25°F
170°F
20
180
200
160
140
120
100
80
60
40
60
100
70°F
A
D
C
B
Reset Curve
Boiler Minimum
Reset Curve
Boiler Maximum
Points
A
and
B
de
fi
ne a
straight line. Boiler min. and
max.,
C
and
D
de
fi
ne a
section on that straight line.
F°
C°
93
82
71
60
49
38
27
16
C°
F°
-6
4
16
38
21°C
21°C 70°F
77°C
-4°C
Note:
• Modes only function when outdoor temperature sensor
connected.
• If ‘Open’ outdoor sensor detected CH set point equal to
‘Boiler Reset Curve Design’ temperature.
• Outdoor temperature used for CH set point calculation
measured once a minute and averaged with
previous measurement to compensate for rapid outdoor
temperature variations.
Allowed Min. Range: 40°F to 180°F (4°C to 82°C)
Default Min. Setting: 70°F (21°C)
Allowed Max. Range: 80°F to 195°F (27°C to 91°
C)
Default Max. Setting: 180°F (82°C)
B
Allowed Boiler Range: 35°F to 120 F (2°C to
49°C)
Default Boiler Setting: 100°F (37°C)
Allowed Outdoor Range: 35°F to 85°F (2°C to
29°C)
Default Outdoor Setting: 70°F (21°C)
1 0 0
A
C
D
APPENDIX A - CONTROL MODULE
Содержание Olsen OLSSC-299
Страница 47: ...47 13 TROUBLE SHOOTING ...
Страница 51: ...51 13 TROUBLE SHOOTING ...
Страница 53: ...53 13 TROUBLE SHOOTING ...
Страница 62: ...62 Supply Water Temperature Sensor Resistance Chart 13 TROUBLE SHOOTING ...
Страница 66: ...66 14 3 Connection Diagram 299 MBH 14 WIRING DIAGRAM EXTERNAL PUMP RELAY LIMIT OF 1 AMP PER PUMP SEE SECTION 8 ...
Страница 84: ...ECR International Inc 2201 Dwyer Avenue Utica NY 13501 web site www ecrinternational com ...