S1CG/S1HG refrigerant charge table
Table 2
Condenser
Evaporator
pairing
Line charge
per foot
Factory
charge
Condenser
Evaporator
pairing
Line charge
per foot
Factory
charge
S1CG9
CAH09
.25 oz/ft
(23 g/m)
39 .5
S1HG9
WLH09/UNH09
.25 oz/ft
(23 g/m)
51 .52
S1CG2
CAH12
.25 oz/ft
(23 g/m)
33 .75
S1HG2
WLH12/UNH12
.25 oz/ft
(23 g/m)
45 .75
S1CG8
CAH24
.64 oz/ft
(59 g/m)
65 .25
S1HG8
WLH24/UNH24
.64 oz/ft
(59 g/m)
63 .0
S1CG4
CAH24
.64 oz/ft
(59 g/m)
63 .0
S1HG4
WLH24/UNH24
.64 oz/ft
(59 g/m)
74 .0
S1CG3
CAC36
.64 oz/ft
(59 g/m)
97 .5
S1HG9
CAH09
.25 oz/ft
(23 g/m)
51 .52
S1CG6
CAC36
.64 oz/ft
(59 g/m)
110 .0
S1HG2
CAH12
.25 oz/ft
(23 g/m)
45 .75
S1CG9
WLH09/UNH09
.25 oz/ft
(23 g/m)
39 .5
S1HG8
CAH24
.64 oz/ft
(59 g/m)
63 .0
S1CG2
WLH12/UNH12
.25 oz/ft
(23 g/m)
33 .75
S1HG4
CAH24
.64 oz/ft
(59 g/m)
74 .0
S1CG8
WLH24/UNH24
.64 oz/ft
(59 g/m)
65 .25
S1CG4
WLH24/UNH24
.64 oz/ft
(59 g/m)
63 .0
S1CG3
WLC30/UNC36
.64 oz/ft
(59 g/m)
97 .5
Refrigerant Processing
(continued)
NOTICE –
to find charge adjustment
To find the charge adjustment and system charge for any evaporator and tubing
1.
length:
Line Adjustment = (Line Charge/FT) x Line Length
System Total = Factory Line Adjustment
Round to the nearest ounce and allow for gauges and hoses.
2.