15
eleCTRICAl WIRINg
figure 14 electrical Connections
Wall
Mounted
Electrical connections
Ceiling
Mounted
Electrical connections
Site Preparation for Wiring
Electrical wiring must be in accordance with all electrical
codes. In absence of such requirements to the National
Electrical Code (NEC).
WARNINg
Electrical shock hazard. Turn OFF electrical power
supply before making electrical connections. Failure
to do so could result in death or serious injury.
!
1.
Check unit rating plate for circuit ampacity and breaker
or time delay fuse size. Use only HACR type breakers.
Select proper wire for ampacity rating.
2.
Each unit must have separate branch circuit protected
by time delay fuse or breaker. Refer to unit rating plate
for proper wire and breaker or time delay fuse size.
3.
Inspect existing wiring for any defects such as cut or
frayed wires. Replace if any such wiring if found.
4.
See
Figure 14 for electrical panel location.
Units rated 208/230v, primary side of transformer is factory
wired for 230v.
For 208v power supply, transformer tap must be changed
from orange to red.
Refer to wiring diagram located inside of left end cap of
unit.
Connect Wiring
1.
Remove painted cabinet and air handler mounted
as described in“UNIT MOUNTING” on page 8. Locate
control box (upper right corner of unit).
2.
Remove screw on front of control box to access High
and Low wiring.
Содержание UNHV09