7
INSTALLATION SYSTEM PIPING
Check local codes
for maximum
distance from
floor or other
allowable safe
point of discharge
RELIEF VALVE
DISCHARGE
PIPING
Figure 2 - Safety Relief Valve Discharge Piping
1.
Refer to local codes and appropriate ASME Boiler and
Pressure Vessel Code for additional installation require
-
ments. Install safety relief valve using pipe fittings
provided with boiler. See Figure 2
2.
Install safety relief valve with spindle in vertical posi
-
tion.
3.
Do not install shutoff valve between boiler and safety
relief valve.
4.
Install discharge piping from safety relief valve. See
Figure 2.
•
Use ¾” or larger pipe.
•
Use pipe suitable for temperatures of 375°F (191°C)
or greater.
•
Individual boiler discharge piping shall be independent
of other discharge piping.
•
Size and arrange discharge piping to avoid reducing
safety relief valve relieving capacity below minimum
relief valve capacity stated on rating plate.
•
Run pipe as short and straight as possible to loca
-
tion protecting user from scalding and properly drain
piping.
•
Install union, if used, close to safety relief valve outlet.
•
Install elbow(s), if used, close to safety relief valve
outlet and downstream of union (if used).
•
Terminate pipe with plain end (not threaded).
WARNING
Burn and scald hazard. Safety relief valve could
discharge steam or hot water during operation.
Install discharge piping per these instructions.
!
Содержание Olsen OSVB II Series
Страница 4: ...4 DIMENSIONS Model Width A OSVB 2 11 OSVB 3 14 1 4 OSVB 4 17 1 2 OSVB 5 20 3 4 OSVB 6 24 OSVB 7 27 1 4...
Страница 23: ...23 WIRING DIAGRAMS Figure 12 Control Module Damper is not an option...
Страница 37: ...NOTES...
Страница 38: ...38 NOTES...
Страница 39: ...39 Company Address Phone Company Name Tech Initials Service Performed Date SERVICE RECORD...
Страница 40: ...ECR International 2201 Dwyer Avenue Utica NY 13501 web site www ecrinternational com...