9
WARNING
Burn and scald hazard. Boiler supplied with dust caps
on supply and return tappings (4). Shall remove all
four (4) caps and plumb before filling boiler with
water. Failure to follow these instructions could result
in death or serious injury.
!
4.1 Connection Locations
• Boiler has one supply and one return tapping on each
side (4 total). Boiler supplied with dust caps only.
Remove all four (4) caps and plumb before filling boiler
with water.
• Supply and return may be piped to either side of boiler,
as desired. Both supply and return shall be on same
side of boiler. Do not "cross pipe" as boiler may not
deliver adequate heat with cross piping.
•
ASME relief valve may be located off unused
supply tapping IN UPRIGHT POSITION ONLY
.
•
Drain valve may be located off of unused return
tapping using a contractor supplied tee, piped right or
left side as desired. See Figure 4-3
• Unused supply and return tappings may be capped, as
desired. Relief valve and drain valve may be located on
near boiler piping using contractor supplied tees with
no valves.
4 - CONNECTING SUPPLY AND RETURN PIPING
Figure 4-1 Piping Options
PIPING OPTIONS
THIS BOILER HAS TWO SUPPLY (OUTLET) AND TWO RETURN (INLET) TAPPINGS.
PIPE SUPPLY AND RETURN ON THE SAME SIDE (FIG. 1 & 2)
DO NOT CROSS PIPE!
(FIG 3 & FIG 4)
FIG 1.
FIG. 2
FIG 3.
FIG 4.
FRONT
FRONT
FRONT
FRONT
RETURN
RETURN
SUPPLY
SUPPLY
. A
. B
. C
. D
PIPING OPTIONS
THIS BOILER HAS TWO SUPPLY (OUTLET) AND TWO RETURN (INLET)
TAPPINGS.
PIPE SUPPLY AND RETURN ON THE SAME SIDE (SEE FIG. A AND B)
DO NOT CROSS PIPE
- (SEE FIG. C AND D)
PN 240013268 Rev. D [08/15/2021]