4 - CONNECTING SUPPLY AND RETURN PIPING

Figure 4-2 - Safety Relief Valve

 WARNING

Burn and scald hazard.  Safety relief valve could 

discharge steam or hot water during operation.  

Install discharge piping per these instructions. Failure 

to follow these instructions could result in death or 

serious injury.

!

  

Discharge line shall be installed to relief valve outlet 

connection to avoid burns, scalding, or water damage due 

to discharge of steam and/or hot water during operation.

Discharge line shall:

4.2  Safety Relief Valve Installation                                           

       See Figure 4-2

Check local codes for maximum 

distance from floor or allowable 

safe point of discharge

.

RELIEF VALVE 

On Opposite 

side of supply

DISCHARGE 

LINE

 WARNING

Burn and scald hazard.  Safety relief valve shall be 

installed with spindle in 

upright position only

following ASME BPV code. Failure to follow these 

instructions could result in death or serious injury.

!

  

A.  connect to relief valve outlet and piped down 

to safe point of disposal. Check local codes for 

maximum distance from floor or allowable safe 

point of discharge.

B.  be of pipe size equal to or greater than that of 

the relief valve outlet over the entire length of 

discharge line;

C. 

have no intervening shutoff valve between safety 

relief valve and discharge to atmosphere (do not 

plug or place any obstruction in discharge line.

D.  terminate freely to atmosphere where any 

discharge will be clearly visible and at no risk of 

freezing;

E.  allow complete drainage of the valve and the 

discharge line;

F.  be independently supported and securely anchored 

to avoid applied stress on the relief valve;

G.  be as short and straight as possible;

H.  terminate with plain end (not threaded);

I.  be constructed of material suitable for exposure to 

temperatures of 375° F (191°C); or greater.

J.  Terminate freely to atmosphere where discharge is 

clearly visible and no risk of freezing.

Refer to local codes and appropriate ASME Boiler 

and Pressure Vessel Code for additional installation 

requirements.

Alternate Location 

Piped in Supply Line

(Contractor supplied 

fittings)

Do Not Install 

Pressure 

Relief Valve 

Horizontally

Figure 4-3 Optional Locations for Drain Valve

Left Side Drain 

Valve Location With 

Standard

Manufacturer 

Supplied Hardware 

Optional Right side 

Drain Valve Location 

with Contractor 

Supplied Tee 

 PN 240013268 Rev. D  [08/15/2021]

Содержание Dunkirk DXL-060K

Страница 1: ...ATION OPERATION MAINTENANCE MANUAL Models DXL 060K DXL 095K DXL 120K DXL 150K DXL 175K DXL 205K DXL 235K Tested For 100 psi ASME Working Pressure Manufactured by ECR International Inc 2201 Dwyer Avenu...

Страница 2: ...Check our website frequently for updates www ecrinternational com Information and specifications outlined in this manual in effect at the time of printing of this manual ECR International reserves the...

Страница 3: ...1 8 Vent Damper Installation Instructions 22 8 1 Vent Damper 22 9 Connecting Gas Service 24 9 1 General 24 9 2 Leak Check Gas Piping 24 10 Electrical 25 10 1 Electrical Wiring 25 10 2 Thermostat Insta...

Страница 4: ...ue Diameter 4 5 6 6 7 7 7 102 mm 127 mm 152 mm 152 mm 178 mm 178 mm 178 mm Supply Return Tappings 1 1 4 NPT 1 1 4 NPT 1 1 4 NPT 1 1 4 NPT 1 1 4 NPT 1 1 4 NPT 1 1 4 NPT Natural Gas Inlet 1 2 NPT 1 2 NP...

Страница 5: ...and all requirements before beginning installation FOR YOUR SAFETY READ BEFORE OPERATING Hot Water Can Scald Water heated to temperature for clothes washing dish washing and other sanitizing needs can...

Страница 6: ...w your detector s located on each floor of your home Follow your detector s instructions for operation and verification Some instructions for operation and verification Some jurisdictions may by law r...

Страница 7: ...nd height 7 Verify floor will support weight of boiler water and equipment 8 Boiler may be installed on combustible floor Do not install boiler on carpeting 9 Do not install where gasoline or other fl...

Страница 8: ...Acids Solvents etc Paint Varnish Turpentine etc Cleaning Solvents Hydrochloric acid muriatic acid Cements adhesives and glues Photo processing plants Garages with workshops Furniture refinishing areas...

Страница 9: ...d off unused supply tapping IN UPRIGHT POSITION ONLY Drain valve may be located off of unused return tapping using a contractor supplied tee piped right or left side as desired See Figure 4 3 Unused s...

Страница 10: ...rge B be of pipe size equal to or greater than that of the relief valve outlet over the entire length of discharge line C have no intervening shutoff valve between safety relief valve and discharge to...

Страница 11: ...e size less than 50 micron If the water quality is outside these ranges consult a local water treatment specialist for recommendations If the water is treated do not use petroleum based products or pr...

Страница 12: ...onnected to heating coils located in air handling unit exposed to refrigerated air circulation Install flow control valves or other automatic means to prevent gravity circulation of boiler water durin...

Страница 13: ...e mounted on system supply side mounting on system return side is also acceptable practice BACK FLOW VALVE PIPING LEGEND Figure 4 4 Circulators Mounted on Supply System Boiler Used In Configuration wi...

Страница 14: ...ure 4 5 Bypass Piping With Automatic Mixing Valve BACK FLOW VALVE PIPING LEGEND 4 CONNECTING SUPPLY AND RETURN PIPING PURGE VALVE DRAIN VALVE ASME RELIEF VALVE BACK FLOW VALVE PN 240013268 Rev D 08 15...

Страница 15: ...PLY AND RETURN PIPING Figure 4 6 Bypass Piping Fixed Low Temp Only With Zone Valve BACK FLOW VALVE PIPING LEGEND ASME RELIEF VALVE Manually adjust until proper system temperature is reached PN 2400132...

Страница 16: ...ING SUPPLY AND RETURN PIPING Figure 4 7 Bypass Piping 4 Way Valve Option With Circulator On Supply side BACK FLOW VALVE PIPING LEGEND ASME RELIEF VALVE DRAIN VALVE FLOW CONTROL VALVE PN 240013268 Rev...

Страница 17: ...4 CONNECTING SUPPLY AND RETURN PIPING Figure 4 8 Single Zone System With DHW Priority BACK FLOW VALVE PIPING LEGEND ASME RELIEF VALVE Back Flow Valve DRAIN VALVE Purge Valve PN 240013268 Rev D 08 15 2...

Страница 18: ...1 DHW Pump 12 po 305 mm Distance recommand e Ne d passez pas 12 po 305 mm Note Note Manufacturer requires all domestic hot water DHW installations use an anti scald valve Local codes may require addi...

Страница 19: ...Infiltration Rate See Table 5 1 for space with boiler only Use equation for multiple appliances Do not use an air infiltration rate ACH greater than 0 60 Volume 21 ft3 ACH x Total Input Refer to Nati...

Страница 20: ...operation the appliance being inspected Follow the lighting instructions Adjust thermostat so appliance will operate continuously 5 Test for spillage at the draft hood relief opening after 5 minutes o...

Страница 21: ...onform to requirements of the authority having jurisdiction or in absence of such requirements to The National Fuel Gas Code ANSI Z223 1 NFPA 54 7 4 Vent Pipe Connect draft hood to boiler using 2 scre...

Страница 22: ...ccessible for servicing See Figure 8 2 page 22 4 Damper must be in the open position when appliance main burners are operating 5 Boiler is equipped with factory wired harness that plugs into vent damp...

Страница 23: ...23 Figure 8 2 Vent Damper Placement Figure 8 3 Vent Damper Position Indicator 8 VENT DAMPER INSTALLATION INSTRUCTIONS PN 240013268 Rev D 08 15 2021...

Страница 24: ...INSTALL MANUAL VALVE WITHIN 6 FT 183 cm OF BOILER AND 5 FT 152 cm ABOVE THE FLOOR WHERE REQUIRED BY LOCAL CODES 3 8 cm Minimum Sediment Trap To Gas Control Inlet DANGER Fire Hazard Do not use matches...

Страница 25: ...drafts hot or cold pipes sunlight lighting fixtures televisions fireplace or chimney 5 Check thermostat operation by raising and lowering thermostat setting as required to start and stop burners 6 Ins...

Страница 26: ...gure 11 1 4200 Fuel Smart Hydrostat IC Control WARNING Modification substitution or elimination of factory equipped supplied or specified components may result in personal injury or loss of life PN 24...

Страница 27: ...27 11 WIRING DIAGRAM Figure 11 2 4200 Fuel Smart Hydrostat IC Control ladder PN 240013268 Rev D 08 15 2021...

Страница 28: ...urn clockwise to OFF DO NOT FORCE 5 Call qualified service technician WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or...

Страница 29: ...in death or serious injury A Power remains off until boiler water temperature drops below high limit setting B Circulator continues to operate under this condition until thermostat is satisfied 3 In e...

Страница 30: ...lamp in flue collector through draft relief opening or flue inspection cover With mirror positioned above burners flue gas passageways can be checked for soot or scale Follow this procedure to clean f...

Страница 31: ...r and free of combustible materials gasoline and other flammable vapors and liquids Free flow of combustion and ventilating air to boiler and boiler room shall not be restricted or blocked Inspect fac...

Страница 32: ...re than plus or minus 0 3 inches water column from specified pressure listed on boiler rating plate 7 Primary air adjustment is not necessary therefore air shutters are not furnished CHECK SAFETY CONT...

Страница 33: ...ric service to be 120 Volts 15 Amps 60 Hz The MEA number for the this boiler is 19 79 E 1 Input rating for sea level to 2 000 ft 610m above sea level United States over 2000 ft 610m above sea level Re...

Страница 34: ...he ECONOMY dial WARNING Burn and scald hazard Do not add water until boiler has fully cooled Failure to follow these instructions could result in death or serious injury Control LED legend 1 2 3 4 6 E...

Страница 35: ...it leakage to ground Replace pilot burner igniter sensor and provide shield if necessary If flame rod or bracket is bent out of position restore to correct position APPENDIX A CONTROL FUNCTION DANGER...

Страница 36: ...connect ignition cable STEP 4 Verify pilot and main burner light off 1 Initiate call for heat Turn thermostat above room temperature Ignition sequence may be delayed by thermal purge up to 2 minutes 2...

Страница 37: ...d position 4 Return thermostat to desired position 5 Place vent damper in open position to permit burner operation by using HOLD DAMPER OPEN switch located on damper controller 6 Thermostat controls b...

Страница 38: ...jumper wire across orange and yellow wires in Molex plug see Figure 4 This will create bypass of the damper boiler should then ignite If boiler ignites Go to section B 4 Vent Damper Troubleshooting G...

Страница 39: ...or heat 1 Thermostat not calling for heat 2 Burned out heat anticipator 3 Loose or broken connections 4 Off On operating limit pressure control or low water cut off 5 Off On blocked vent switch or fla...

Страница 40: ...tion THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE OF THE FOLLOWING CONDITIONS IS TRUE An external energy management system is installed that reduces the boiler water temperature as the heating l...

Отзывы: