8

PN 240012875 REV. D [03/15/2022]

GENERAL INFORMATION - WIRING

Electrical Wiring Information:

All field wiring shall conform to the authority having 

jurisdiction or, in the absence of such requirements to:                       

•  USA

: National Electrical Code, ANSI/NFPA 70,  

•  Canada

: Canadian Electrical Code, Part I, CSA           

C22.1: Safety Standard for Electrical Installations.                                                                                                                                   

                                                                                                                                                      

 

Wiring diagrams shown in this manual utilize ARGO™ 

Controls, the 

optional 

use of an Indirect Domestic Hot 

Water Tank, and 

optional

  use  of  a  H2O  Buffer  Tank.                                                                                                            

Reference the zone control manufacturer instruction 

manual for control operation and priority setting of DHW 

zones.

Note

DO NOT 

use 120 V thermostat 

terminals (M1- #1 and #2).

Provided Wiring and Piping 

illustrations are meant to show 

system concepts only.  Installer 

is responsible for all equipment 

required by authority having 

jurisdiction.

Note

SUPPLY Cord 

120V/60HZ

BOILER CONTROL

10k Ω

 DHW Indirect 

Tank Sensor (125 

Unit Only)

or 

DHW Indirect Tank 

Aquastat (Heating 

Only Boilers)

1K

 Ω

 

Outdoor 

Reset 

Sensor

Zone Control 

End-Switch

Open Therm

S

0-10 V Connection

*

* Ground Sensors using terminal 4

G

Do Not 

Use

Содержание Dunkirk DCBF

Страница 1: ...ctured by ECR International Inc 2201 Dwyer Avenue Utica NY 13501 Tel 800 325 5479 www ecrinternational com DCBF 75 DCBF 100 DCCF 115 DCBF 125 DCCF 150 DCBF 165 DCCF 150 DCCF 205 CONDENSING GAS FIRED B...

Страница 2: ...DCCF 150...

Страница 3: ...CONTENTS INSTALLATION OPERATION AND MAINTENANCE MANUAL 240013509 APPLICATION GUIDE 240012875 COMMISSIONING GUIDE 240011376 REQUIRED INSPECTION SPECIAL 240011561 BACK COVER...

Страница 4: ...DCBF 125...

Страница 5: ...NTENANCE MANUAL Manufactured by ECR International Inc 2201 Dwyer Avenue Utica NY 13501 Tel 800 325 5479 www ecrinternational com PN 240013509 REV A 03 15 2022 Models COMBI DCCF 115 DCCF 150 DCCF 205 H...

Страница 6: ...x 1 1 4 x 1 2 Document Package VERIFY CONTENTS RECEIVED Threaded End Non Threaded End Copper Tee NOTICE Using proper brazing or soldering technique insert copper flush bushing into copper tee with th...

Страница 7: ...ct Storage Tank 46 8 9 Management Of 0 10v Input 46 9 Start Up Procedure 48 9 1 Central Heating System Connections Heat Only 48 9 2 Central Heating System Connections Combi 48 9 3 System Start Up 49 9...

Страница 8: ...r Sweat 165 N A 205 3 4 19 1 mm I Boiler Return 3 4 19 1 mm 1 38 1 mm Boiler Filling Connection External to Boiler Primary Water Content 0 95 gal 3 60 L 1 gal 3 80 L 11 4 gal 4 73 L Central Heating Se...

Страница 9: ...4 35 in 111 mm 111 mm 6 12 in 6 12 in 156 mm 156 mm 7 31 in 7 31 in 186 mm 186 mm 1 80 in 1 80 in 46 mm 46 mm 43 65 in 43 65 in 1 1 m 1 1 m 40 23 in 40 23 in 1 0 m 1 0 m 37 20 in 37 20 in 95 m 95 m 2...

Страница 10: ...84 mm 9 39 in 9 39 in 239 mm 239 mm 6 26 in 6 26 in 159 mm 159 mm 3 07 in 3 07 in 78 mm 78 mm 41 87 in 41 87 in 1 06 m 1 06 m 7 39 in 7 39 in 187 mm 187 mm 6 26 in 6 26 in 159 mm 159 mm 10 in 10 in 2...

Страница 11: ...zing needs can scald and cause permanent injury Children elderly and infirmed or physically handicapped persons are more likely to be permanently injured by hot water Never leave them unattended in ba...

Страница 12: ...imited to Installation by licensed plumber or gas fitter 2 6 The unit MUST NOT Directly heat potable water Indirect heating is acceptable Heat water with non hydronic heating system chemicals present...

Страница 13: ...Heating Return 12 Gas Inlet 13 Optional Indirect Tank Connection 14 Heating Supply Connection 15 Condensate Connection 16 Low Water Pressure Cutoff 17 3 Way Valve with Motor 18 Gas Valve 19 Over Tempe...

Страница 14: ...ator 10 Boiler Drain Tap 11 Heating Return 12 Gas Inlet 13 Optional Indirect Tank Connection 14 Heating Supply Connection 15 Condensate Connection 16 Low Water Pressure Cutoff 17 3 Way Valve with Moto...

Страница 15: ...Gas Inlet 14 Condensate Connection 15 Low Water Pressure Cutoff 16 Inlet Element 17 Gas Valve 19 Over Temperature Thermostat 20 NTC Heating Sensor 21 Ignition Electrode 22 Pressure Relief Valve 23 Ex...

Страница 16: ...ating Supply 18 Condensate Connection 19 DHW Heat Exchanger 20 NTC DHW Sensor 21 Low Water Pressure Cutoff 22 3 Way Valve with Motor 23 Gas Valve 24 Water Safety Thermostat 25 NTC Heating sensor Retur...

Страница 17: ...9 Pump with Air Separator 10 DHW Priority Sensor 11 Flow Sensor with Water Filter and Flow Restrictor 12 Boiler Drain Tap 13 Heating Return 14 Cold Water DHW Inlet 15 Gas Inlet 16 DHW Outlet 17 Heatin...

Страница 18: ...nnection 17 Condensate Connection 18 DHW Heat Exchanger 19 NTC DHW Sensor 20 Low Water Pressure Cutoff 21 3 Way Valve with Motor 22 Gas Valve 23 NTC Heating sensor Flow Return QTY 2 1 Shown for clarit...

Страница 19: ...well gas is not manufacturer recommended with this boiler 4 LOCATING BOILER 4 2 Floor Location Place crated boiler as close to selected location as possible and uncrate boiler Boiler may be moved into...

Страница 20: ...ation 0 in 0 mm between Back of Unit and wall 0 in 0 mm between Back of Unit and wall 1 3 4 in 45 mm 13 4 in 45 mm 13 4 in 45 mm 450 mm Front View of Boiler 0in 0 mm 0in 0 mm Top View 0 in 0 mm 0 in 0...

Страница 21: ...tings with thermal insulation shall be prohibited Failure to follow these instructions could result in death or serious injury 5 COMBUSTION AIR AND VENT PIPING Support piping in accordance with pipe m...

Страница 22: ...to common venting system are located and other spaces of building Turn on clothes dryer and any appliance not connected to common venting system Turn on exhaust fans such as range hoods and bathroom...

Страница 23: ...specified sized pipes are to be used When using venting material other than boiler manufacturer s venting note the correct installation procedure Failure to follow these instructions could result in d...

Страница 24: ...opylene venting for the exhaust pipe See Figures 5 8 to 5 10 for L1 L2 details VENT MATERIAL OPTIONS Maximum Equivalent Vent Length Shown 165 205 Vent Type Vent Size Vent Material Intake L1 Exhaust L2...

Страница 25: ...le materials is zero when using coaxial vent system After installing venting use calibrated analyzer to verify there is no recirculation of combustion Ensure Horizontal termination is positioned with...

Страница 26: ...5 Coaxial Vertical Exhaust CAN BE USED ON ALL SIZES 12 305 mm Minimum Separation Manufacturer Recommends Greater Separation FIGURE 5 7 Coaxial Horizontal Exhaust CAN BE USED ON ALL SIZES Multiple Appl...

Страница 27: ...highest anticipated snow level 24 610 mm above roof Avoid locations where snow may drift and block vent and combustion air Ice or snow may cause boiler to shut down if vent or combustion air becomes...

Страница 28: ...s See Figures 5 13 thru 5 14 1 Inspect Coaxial Connector on top of boiler Confirm the factory installed inner and outer gaskets are in place 2 Insert the Flue adapter 1 into the Coax connector push do...

Страница 29: ...he Flue adapter 1 into the Coax connector push down firmly to fully seat it Figure 5 16 3 Remove 3 screws securing the Fresh Air cover plate 2 Figure 5 17 4 Remove the gasket and discard 5 Install the...

Страница 30: ...4 Insert the male end of the second pipe into the clamp on the up etched side Force the two pipes together 5 Verify the two pipes are secure together with clamp in place 5 13 Securing Twin Pipe Polyp...

Страница 31: ...nt pipe must exit above top of chimney with clearances as shown in Figure 5 14 Vent Terminal Combustion Air Ground Level FIGURE 5 21 Twin Pipe on Roof Combustion Air On Sidewall CAN BE USED ON ALL SIZ...

Страница 32: ...IZES 3 80 mm Min 24 610 mm Max Separation See Grade Snow Ice Combustion Air Vent FIGURE 5 29 2 60 mm ONLY Vent Pipe with T CAN BE USED ON ALL SIZES Combustion Air Vent 3 80 mm Min 24 610 mm Max Separa...

Страница 33: ...chimney Avoid sharp bends in flexible venting FIGURE 5 33 3 80 mm Only Flexible Venting System CAN BE USED ON ALL SIZES Combustion Air Vent Terminal Flexible Vent Rigid Vent 5 COMBUSTION AIR AND VENT...

Страница 34: ...r 9 229 mm 9 229 mm G Clearance to inside corner 36 456 mm 36 456 mm H Clearance to each side of center line extended above meter regulator assembly 3 ft 0 9 m within a height of 15 ft 4 5 m above the...

Страница 35: ...liminate any sages Use field source condensate pump designated for use with condensing boiler if boiler located below disposal point Condensate pump should have overflow switch Condensate from Boiler...

Страница 36: ...ves and isolation valves are not installed install them to properly clean the system When purging installations that include standing iron radiators and systems with manual vents at high points start...

Страница 37: ...ature pressure gauge using tee and bushing provided in near boiler piping on supply side See Figure 6 2 Some boiler models may have integral drain valve located inside jacket directly underneath pump...

Страница 38: ...34 FIGURE 6 2 Piping Diagram LWCO Location 6 HYDRONIC PIPING 240013509 REV A 03 15 2022...

Страница 39: ...piping above the minimum height of boiler See Figure 6 2 Piping Diagram Position control in HORIZONTAL piping to assure proper boiler protection upright or 90 rotation For proper operation sensing el...

Страница 40: ...tation and debris from your water supply piping from entering the boiler Debris carried from the water supply will clog DHW water flow sensor potentially resulting in significant operation issues Loca...

Страница 41: ...ure relief valve 30 0 psi 2 1 bar Boiler internal pressure switch will shut boiler off below 7 5 psi 0 5 bar and above 43 5 psi 3 0 bar 6 9 Frost Protection Mode Frost protection mode is integrated in...

Страница 42: ...as meter and supply pipes must be capable of delivering the listed quantity of gas in addition to demand from any other appliances in the house Boiler requires a minimum 3 4 19 5 mm gas supply pipe Su...

Страница 43: ...tallic pipe and Corrugated Stainless Steel Tubing CSST is manufacturer recommended for best performance Use of Gas Appliance Connectors flexible connectors typically used for gas stoves or water heate...

Страница 44: ...68 80 131 153 107 126 207 241 80 60 69 113 132 94 109 178 208 100 54 62 101 118 85 98 159 186 INTENDED USE Pipe Sizing Between Natural Gas Meter or Propane Single or Second Stage Low Pressure Regulat...

Страница 45: ...sive detection fluid or other leak detection method acceptable to authority having jurisdiction Do not use matches candles open flames or other methods that can provide ignition source Correct leaks i...

Страница 46: ...supply Respect the input polarity on terminal block M1 L LINE N NEUTRAL Failure to follow these instructions WILL result in death or serious injury 8 ELECTRICAL CONNECTIONS FIGURE 8 1 Junction Box Le...

Страница 47: ...ch is high voltage 120V 60Hz Fuses 3 15 A are incorporated in the power supply terminal block To check or replace fuse pull out black fuse carrier TERMINAL BLOCK M1 L Live brown N Neutral light blue G...

Страница 48: ...K sensor and instructions supplied with 1K sensor B Setting Kt Climate Curve 1 Boiler automatically recognizes OAS sensor when wired to M2 terminal block Display changes to show current default Kt val...

Страница 49: ...ger increases curves shown on graph become horizontal FIGURE 8 6 Kt Climate Curves 80 Is Default Flow temp Outside temp 80 Is Default Boiler Set Point Temp Boiler Set Point Temp Centigrade C Fahrenhei...

Страница 50: ...ndirect Storage Tank 8 9 Management of 0 10V Input The functions with 0 10V regulator are activated by means of their parameters To enable 0 10V input change P82 4 to P82 3 When P78 1 the input manage...

Страница 51: ...For more information please review the application guide received with your boiler 8 ELECTRICAL CONNECTIONS A field supplied pump relay is necessary for system pumps Thermostat or Endswitch from zone...

Страница 52: ...DCBF 75 100 125 HEATING ONLY WITHOUT OPTIONAL INDIRECT DHW CONNECTION 9 2 Central Heating System Connections Combi DCCF 115 150 205 COMBI 150 shown LEGEND 75 100 115 150 205 A Heating supply connectio...

Страница 53: ...of heat exchanger Open four 4 full turns counterclockwise until steady stream of water is witnessed Close fully turning clockwise with no tools needed See Figure 9 1 Systems using radiators to remove...

Страница 54: ...abled Call a qualified service technician Programming menu Manually resettable fault Boiler information menu Fault in progress Set unit of measurement SI US SYMBOL Key DESCRIPTION DESCRIPTION 00 Secon...

Страница 55: ...he boiler and there are no heat demands in progress During this function ensure there is maximum heat exchange to the system in Heating or DHW mode DHW request to avoid boiler shutting off due to over...

Страница 56: ...A If display shows fault E118 low pressure in hydraulic circuit open filling tap on appliance and restore correct pressure B If gas recognition function is interrupted due to fault e g E133 no gas pr...

Страница 57: ...ue of CO2 Use the following procedure 1 Press buttons and together for at least 6 seconds When the function is enabled displays shows On for a few seconds followed by program row 304 alternated with t...

Страница 58: ...eck firing rate again after setting the combustion following steps in section 9 12 9 START UP PROCEDURE NOTICE Important Record any changes made to Parameters on chart found on Page 46 of the Applicat...

Страница 59: ...information P32 P41 Diagnostics See SERVICE Instructions 9 16 Description Of Parameters Factory Settings FACTORY SETTINGS 75 100 125 165 115 150 205 P01 DHW Fast Modulation 00 Standard Modulation on D...

Страница 60: ...50 5700 7250 7200 P72 Minimum Fan Speed Setting 50 50 50 50 55 55 40 25 40 35 43 45 40 45 RPM 1250 1250 1250 1250 1300 1300 1150 1000 1150 1100 1180 1200 1150 1200 To calculate fan speeds P70 x 100 P7...

Страница 61: ...00 24 0 67 53 88 700 26 0 74 59 95 500 28 0 80 65 102 300 30 0 88 71 109 200 32 0 96 75 112 600 33 0 100 80 9 START UP PROCEDURE Btu h kW DCBF 165 DCCF 205 27 400 8 0 0 0 31 300 9 2 4 3 35 800 10 5 7...

Страница 62: ...n comes on at ignition speed closing the air pressure switch if applicable to model allowing power to spark generator and gas valve creating ignition in the combustion chamber 3 Flame sensor acknowled...

Страница 63: ...board monitors boiler water and DHW temperatures and modulates fan speed and gas rate accordingly Call for domestic water heating ends when the aquastat or tank sensor is satisfied Heat Only Boiler 1...

Страница 64: ...Verify proper operation after servicing Note Perform regular service and maintenance by qualified service agency at least once every 12 months to assure safe trouble free operation and maximum efficie...

Страница 65: ...positioning and height of electrodes 7 Check fan impeller is clean and free to rotate WARNING Combustion chamber insulation in this product contains ceramic fiber material Ceramic fibers can be conver...

Страница 66: ...off isolate electrical supply close boiler gas service cock allow boiler to cool drain boiler through onboard drain if available or external drain valve 11 5 Draining the Heating Circuit Follow all s...

Страница 67: ...ing valves Repressurize the system 11 9 Final Assembly Place front jacket in position over boiler Secure in position using screws previously removed If boiler is to be left in service set controls and...

Страница 68: ...C Servicing or replacement of parts shall be carried out by a qualified personnel D Ensure boiler controls and room thermostat if fitted are set to User s requirements E Explain to User an internal fr...

Страница 69: ...adapters included with boiler Model Number CH Input MBH 1 1 2 CH Heating Capacity MBH 1 3 Net AHRI Rating Water MBH 2 AFUE Maximum Minimum DCBF 75 75 16 6 68 2 60 92 0 DCBF 100 93 5 16 6 85 4 74 95 0...

Страница 70: ...120 17 Max CH Supply temp 176 F 80 C for DCBF 125 and DCCF 150 Max DHW temp 140 F 60 C DCCF 150 Max DHW Flow rate 3 5 gpm 13 2 l min DCCF 205 Max DHW flow rate 5 0 gpm 18 9 L min GAS Natural LP Model...

Страница 71: ...d pump fit for installation on any type of single or double pipe heating systems The automatic air valve incorporated in the pump allows quick venting of the heating system Q WATER FLOW RATE MIN Minim...

Страница 72: ...unit Probable short circuit on wiring Check cable between control unit and boiler 109 Pre circulation alarm temporary fault Check correct circulation of water and pump Check supply and return wiring i...

Страница 73: ...nd the combustion levels E70 Flame signal problem micro interruption of the flame signal Check cable and integrity of the sensing electrode verify the continuity between burner and earth E73 Combustio...

Страница 74: ...LOCKOUT C09 FIRST LOCKOUT PHASE STATUS CODES 0 STANDBY 1 PREPURGE 3 INTERPURGE 4 SAFETY TIME 5 RUNNING 6 LOCKOUT 11 INTERURGE 15 POST VENTILATION 16 THERMOSTATIC POST VENTILATION 13 TROUBLE SHOOTING...

Страница 75: ...wood compressed paper plant fibers or other materials capable of being ignited and burned Such material shall be considered combustible even though flame proofed fire retardant treated or plastered C...

Страница 76: ...or servicing of appliances and equipment Experienced in such work Familiar with all precautions required Complies with all requirements of authority having jurisdiction SAFETY RELIEF VALVE Valve desig...

Страница 77: ...73 A 1 MODEL 75 100 Heat Only APPENDIX A WIRING DIAGRAMS 240013509 REV A 03 15 2022...

Страница 78: ...74 A 2 MODEL 125 Heat Only APPENDIX A WIRING DIAGRAMS 240013509 REV A 03 15 2022...

Страница 79: ...75 APPENDIX A WIRING DIAGRAMS A 3 MODEL 165 Heat Only 240013509 REV A 03 15 2022...

Страница 80: ...76 APPENDIX A WIRING DIAGRAMS A 4 MODEL 115 Combi 240013509 REV A 03 15 2022...

Страница 81: ...77 A 5 MODEL 150 Combi APPENDIX A WIRING DIAGRAMS 240013509 REV A 03 15 2022...

Страница 82: ...78 A 6 MODEL 205 Combi APPENDIX A WIRING DIAGRAMS 240013509 REV A 03 15 2022...

Страница 83: ...BTU HR input____________ Installation instructions have been followed Checkout procedure and adjustments performed Maintenance and Service issues reviewed with owner maintenance person Installation bo...

Страница 84: ...tion THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE OF THE FOLLOWING CONDITIONS IS TRUE An external energy management system is installed that reduces the boiler water temperature as the heating l...

Страница 85: ...l 800 325 5479 www ecrinternational com PN 240012875 REV D 03 15 2022 APPLICATION GUIDE FOR USE WITH FLOOR STANDING HEATING ONLY 75F 100F 125F 165F COMBI 115F 150F 205F This manual has been prepared f...

Страница 86: ...Tank Tank T Stat Wiring Dia 19 115F 150F 205F with zone circulators PIPING Diagram 20 115F 150F 205F with zone Circulators Wiring Diagram 21 115F 150F 205F with Zone Valves PIPING Diagram 22 115F 150F...

Страница 87: ...ad this manual and understand all requirements before beginning installation 3 Installation shall conform to requirements of authority having jurisdiction or in absence of such requirements United Sta...

Страница 88: ...densate Drain Connection 1 2 NPT C Gas Shutoff Connection 3 4 NPT D Optional Indirect DHW Connection may exit right or left 3 4 sweat 22 2 mm NA E Heating Return Connection 11 4 sweat 31 8 mm 11 2 swe...

Страница 89: ...A Heating Supply Connection 11 4 sweat 31 75 mm 11 2 sweat 38 1 mm B Domestic Hot Water Outlet 1 2 sweat 12 7 mm 3 4 sweat 22 2 mm C Condensate Drain Connection 1 2 NPT D Gas Shutoff Connection 3 4 NP...

Страница 90: ...CAN CSA B149 1 Manufacturer Requirements Recommendations Manufacturer requires all domestic hot water DHW installations use an anti scald valve Local codes may require additional equipment expansion...

Страница 91: ...boiler pump manifold shall be cut for use as shown on page 24 Increase pipe size to match Buffer tank connections as shown Locate tank as close to boiler as possible The Labor Saver Piping Manifold wh...

Страница 92: ...ter Tank and optional use of a H2O Buffer Tank Reference the zone control manufacturer instruction manual for control operation and priority setting of DHW zones Note DO NOT use 120 V thermostat termi...

Страница 93: ...ION FILL FLOW CHECK VALVE BYPASS VALVE DIVERTER VALVE T P OR RELIEF VALVE THERMOSTATIC MIXING VALVE DHW INDIRECT TANK INDIRECT TANK AQUASTAT 10K INDIRECT DHW TANK SENSOR TEMPERATURE PRESSURE GAUGE EXP...

Страница 94: ...15 2022 75F 100F 125F W ZONE CIRCULATORS DHW TANK PIPING DIAGRAM 75F 100F 125F W ZONE CIRCULATORS DHW TANK PIPING DIAGRAM 1 Shut off Purge Valve MAGNETIC DIRT SEPARATOR 1 Locate shut off valve after...

Страница 95: ...sensor to a Heating Only Boiler change P03 from 08 to 05 See Section 9 Parameter Settings in Boiler Installation Operation Maintenance Manual for details Reference zone control manufacturer instructio...

Страница 96: ...er Installation Operation Maintenance Manual for details ZONE 1 LINE 24V Vac L C R 115 Vac N L 1 N 115 COM Vac ZR ZC N L 3 N L 2 115 Vac N L 1 L N ZONE CIRCULATOR X X X X X 3 2 1 X NEC Class 2 Low Vol...

Страница 97: ...REV D 03 15 2022 1 Shut off Purge Valve MAGNETIC DIRT SEPARATOR 75F 100F 125F WITH ZONE VALVES DHW TANK PIPING DIAGRAM 75F 100F 125F WITH ZONE VALVES DHW TANK 1 Locate shut off valve after any field...

Страница 98: ...DHW TANK W SENSOR ARGO UZ3 ZONE CONTROL UZ3 If adding an indirect tank with sensor to a Heating Only Boiler change P03 from 08 to 05 See Section 9 Parameter Settings in Boiler Installation Operation M...

Страница 99: ...s 2 Low Voltage 24Vac W R T T C W R T T C PRI PUMP ZC ZR DIGITAL LCD USER DISPLAY Fuse ZONE MODULE TO EXPANSION Transformer PTC 12A 250V Domestic Hot 115 Vac FIELD SUPPLIED POWER PER NEC AND LOCAL COD...

Страница 100: ...PN 240012875 REV D 03 15 2022 1 Shut off Purge Valve MAGNETIC DIRT SEPARATOR 165F WITH ZONE CIRCULATORS PIPING DIAGRAM 1 Locate shut off valve after any field installed LWCO 165F WITH ZONE CIRCULATOR...

Страница 101: ...3 2 1 4 3 2 1 4 3 2 1 NEC Class 2 Low Voltage 24Vac W R T T C W R T T C PRI PUMP ZC ZR DIGITAL LCD USER DISPLAY Fuse ZONE MODULE TO EXPANSION Transformer PTC 12A 250V Domestic Hot 115 Vac FIELD SUPPLI...

Страница 102: ...18 PN 240012875 REV D 03 15 2022 1 Shut off Purge Valve MAGNETIC DIRT SEPARATOR 165F WITH ZONE VALVES 165F WITH ZONE VALVES PIPING DIAGRAM 1 Locate shut off valve after any field installed LWCO...

Страница 103: ...ssary ZONE 1 LINE 24V Vac L C R 115 Vac N L 1 N 115 COM Vac ZR ZC N L 3 N L 2 115 Vac N L 1 L N ZONE CIRCULATOR X X X X X 3 2 1 X NEC Class 2 Low Voltage ZONE 3 ZONE 2 ZONE 1 W R NEC Class 2 Low Volta...

Страница 104: ...875 REV D 03 15 2022 115F 150F 205F WITH ZONE CIRCULATORS 115F 150F 205F WITH ZONE CIRCULATORS PIPING DIAGRAM MAGNETIC DIRT SEPARATOR 1 Shut off Purge Valve 1 Locate shut off valve after any field ins...

Страница 105: ...OR X X X X X 3 2 1 X NEC Class 2 Low Voltage ZONE 3 ZONE 2 ZONE 1 W R NEC Class 2 Low Voltage T T C THERMOSTATS ZONE VALVES ZONE 3 ZONE 2 4 3 2 1 4 3 2 1 4 3 2 1 NEC Class 2 Low Voltage 24Vac W R T T...

Страница 106: ...40012875 REV D 03 15 2022 115F 150F 205F WITH ZONE VALVES 115F 150F 205F WITH ZONE VALVES PIPING DIAGRAM 1 Locate shut off valve after any field installed LWCO 1 Shut off Purge Valve MAGNETIC DIRT SEP...

Страница 107: ...ONE 3 ZONE 2 ZONE 1 W R NEC Class 2 Low Voltage T T C THERMOSTATS ZONE VALVES ZONE 3 ZONE 2 4 3 2 1 4 3 2 1 4 3 2 1 NEC Class 2 Low Voltage 24Vac W R T T C W R T T C PRI PUMP ZC ZR DIGITAL LCD USER DI...

Страница 108: ...fer Tank Piping When installing low mass systems additional water mass may be required to avoid short cycling by the boiler In these applications it is recommended that a buffer tank be installed H2O...

Страница 109: ...Buffer Tank PURGE VALVE CH System Pump Optional Indirect Tank ZONE PUMPS OR ZONE VALVES MAGNETIC DIRT SEPARATOR 1 2 NOTE Acceptable primary pump locations Either 1 or 2 For pump wiring see diagrams on...

Страница 110: ...26 PN 240012875 REV D 03 15 2022 EXTERNAL BUFFER TANK WIRING DIAGRAM Buffer Tank Pump Wiring Controlling A Primary Pump On A Combi Boiler With Zone Valves No Indirect Tank...

Страница 111: ...27 PN 240012875 REV D 03 15 2022 EXTERNAL BUFFER TANK WIRING DIAGRAM Buffer Tank Pump Wiring Controlling A Primary Pump On A Combi Boiler With Zone Pumps Argo ARM 4P Zone Control and A822 II...

Страница 112: ...w Voltage ZONE 3 ZONE 2 ZONE 1 W R NEC Class 2 Low Voltage T T C THERMOSTATS ZONE VALVES ZONE 3 ZONE 2 4 3 2 1 4 3 2 1 4 3 2 1 NEC Class 2 Low Voltage 24Vac W R T T C W R T T C PRI PUMP ZC ZR DIGITAL...

Страница 113: ...268 10 4 5 046 68 0 1 218 12 2 4 804 69 8 1 170 14 0 4 574 71 6 1 125 15 8 4 358 73 4 1 081 17 6 4 152 75 2 1 040 19 4 3 958 77 0 1 000 21 2 3 774 78 8 962 23 0 3 600 80 6 926 24 8 3 435 82 4 892 26 6...

Страница 114: ...and actual outside air temperature Refer to applicable F or C chart pg 30 for setpoint information Select Kt range which will satisfy the desired boiler delivery temperature based on outdoor temperatu...

Страница 115: ...nd Maintenance Manual Parameter PO3 for COMBI boiler factory set at OO requires no change To activate the 0 10v function parameter 82 must be set to 3 There must be at or above 3 V DC present for the...

Страница 116: ...32 PN 240012875 REV D 03 15 2022 CIRCULATOR CONNECTIONS WIRING DIAGRAM SINGLE ZONE CIRCULATOR WIRING USING ARGO AR822 II...

Страница 117: ...33 PN 240012875 REV D 03 15 2022 MODEL 75 100 HEAT ONLY 75 100 HEAT ONLY WIRING DIAGRAM...

Страница 118: ...34 PN 240012875 REV D 03 15 2022 MODEL 125 HEAT ONLY 125 HEAT ONLY WIRING DIAGRAM...

Страница 119: ...35 PN 240012875 REV D 03 15 2022 MODEL 165 HEAT ONLY 165 HEAT ONLY WIRING DIAGRAM...

Страница 120: ...36 PN 240012875 REV D 03 15 2022 115 COMBI WIRING DIAGRAM MODEL 115 COMBI...

Страница 121: ...37 PN 240012875 REV D 03 15 2022 MODEL 150 COMBI 150 COMBI WIRING DIAGRAM...

Страница 122: ...38 PN 240012875 REV D 03 15 2022 MODEL 205 COMBI 205 COMBI WIRING DIAGRAM...

Страница 123: ...R INPUT BTUH ALTITUDE FEET MAC 115 CALCULATEDEFFECTS OF HI ALTITUDE ON BOILER PERFORMANCE DHW MODE HEAT MODE Net Rating Heat Mode MODELS 100 115 40 000 45 000 50 000 55 000 60 000 65 000 70 000 75 000...

Страница 124: ...ATED EFFECTS OF HI ALTITUDE ON BOILER PERFORMANCE DHW MODE HEAT MODE NET RATNG HEAT MODE 60 000 80 000 100 000 120 000 140 000 160 000 180 000 200 000 220 000 0 2 000 4 000 6 000 8 000 10 000 BOILER I...

Страница 125: ...0 215 116 000 14 0 5 6 H2OI50 196 254 151 231 125 000 14 0 6 2 H20I60 231 298 177 244 132 000 14 0 6 4 H20I60L 211 272 157 218 118 000 14 0 5 9 H2OI80 241 306 169 234 127 000 14 0 6 2 H2OI115 291 363...

Страница 126: ...C or Canadian Electrical Code CEC Locate LWCO sensing device in the supply piping above the minimum height of boiler See Figure page 42 Piping Diagram Position control in piping above boiler to assure...

Страница 127: ...nto boiler Illustrations are meant to show system piping concept only Installer is responsible for all equipment and detailing required by authority having jurisdiction Air Vent Supply Gas Boiler Safe...

Страница 128: ...44 PN 240012875 REV D 03 15 2022 LOW WATER CUTOFF LOW WATER CUTOFF DETAIL NO NO YES...

Страница 129: ...round Short Circuit and Polarity with a suitable meter NOTE These checks must be repeated after any servicing or fault finding 5 Ensure all external controls are calling for heat and check all externa...

Страница 130: ...Burner lights YES Error E109 flashing NO Error E11O flashing NO 3 way valve open to central heating circuit YES Burner output modulates to maintain the temperature set YES YES YES YES YES Error E130 f...

Страница 131: ...peed YES Spark at ignition electrodes for up to 5 seconds and for 5 attempts YES NO YES Burner lights YES YES Error E109 flashing NO Error E110 flashing YES NO NO NO NO DHW flow rate more than 21 min...

Страница 132: ...p terminals Blue to Brown See Wiring Diagram NO Replace PCB Fan connections correct at fan and PCB Connectors X11 X23 See Wiring Diagram YES NO 120V between PCB connector x13 pump terminal Blue and PC...

Страница 133: ...49 PN 240012875 REV D 03 15 2022 3 FAULT SOLUTION SECTIONS...

Страница 134: ...pcb connection at connector x22 is there approx 5 V DC between the green and black NO terminals Check flow temperature sensor connections and position Sensors swapped Cold resistance approximately 1Ok...

Страница 135: ...terminals Check the voltage is approximately 5 VDC between the Red and Blue wires See Wiring Diagrams With water running through DHW circuit measure red and white wire for 2 8 VDC for flow triggering...

Страница 136: ...hanged From Changed To Date Reason PARAMETER CHANGE HISTORY All specifications subject to change without notice 2022 ECR International Inc 2201 Dwyer Avenue Utica NY 13501 Tel 800 325 5479 www ecrinte...

Страница 137: ...CTION ASSURE FACTORY SUPPLIED CONVERSION LABEL IS APPLIED TO PRODUCT IF CONVERTING TO LP IMPORTANT Gas type Check Ensure the maximum heat exchange to the system in Heating or DHW mode DHW request in o...

Страница 138: ...imum l installation de chauffage ou de production d ECS afin d viter que la chaudi re ne s teigne suite un probl me de surchauffe INTERRUPTION DE LA FONCTION Si la fonction de d sa ration ou d identif...

Страница 139: ...ver checking combustion chamber Spark Electrode Clean Set gap according to IOM directions Clean electrode with plumbers cloth to remove oxides Flame Sensor Clean sensor Condensate Neutralizer Check co...

Отзывы: