 AIR PURGING

starting evacuation, slightly loose theflare nut
of the Lo valve on the gas pipe side and
check that the air is entering(Operation noise
of  the vacuum pump changes and a
compound meter indicates 0 instead of minus)

5. After the evacuation is complete, fully close

the handle Lo of the manifold valve and stop
the operation of the vacuum pump. Make
evacuation for 15 minutes or more and check
that the compound meter indicates

5

-76cmHg  (-1x10 Pa).

6. Turn the stem of the packed valve B about

o

45  counterclockwise for 6~7 seconds after
the gas coming out, then tighten the flare nut
again. Make sure the pressure display in the
pressure indicator is a little higher than the
atmosphere pressure.

7. Remove the charge hose from the Low

pressure charge hose.

8. Fully open the packed valve stems B and A.
9. Securely tighten the cap of the packed valve.
10. If the outdoor unit uses all vacuum valves,

and the vacuum position is at the main valve,
the system is not connected with the indoor
unit must be tightened with a screw nut.
Checking the gas leakage before operation
to prevent leakage.

4. Operate the vacuum pump to evacuate. After

Manifold valve

Compound meter

-76cmHg

Handle Lo

Handle Hi

Charge hose

Charge hose

Vacuum pump

Pressure gauge

Low pressure valve

Fig.

1

8

Fig.

1

9

Perform the electric safe check after
completing installation:
1. Insulated resistance

The insulated resistance must be more than 2M

Ω

.

2. Grounding work

After finishing grounding work, measure the

grounding resistance by visual detection and
grounding resistance tester. Make sure the
grounding resistance is less than 4

Ω

.

3. Electrical leakage check (performing during

test running)
During test operation after finishing installation,
the serviceman can use the electroprobe and
multimeter to perform the electrical leakage
check. Turn off the unit immediately if leakage
happens. Check and find out the solution
ways till the unit operate properly.

Electrical safety check

Safety and leakage check

C

C

D

D

B

B

A

A

Содержание 18k

Страница 1: ...s Split System Heat Pumps Installation Operation Maintenance Manual ECR International Inc 2201 Dwyer Avenue Utica NY 13501 Phone 800 325 5479 Web enviromaster com 18k 27k 36k 45k PN 615000159 REV B 01...

Страница 2: ...manual are subject to change without prior notice for product improvement The actual shape should prevail Contact an authorized service technician for repair or maintenance of this unit The appliance...

Страница 3: ...rnal force will be acted on the terminal If connection or fixing is not perfect it will cause heat up or fire at the connection 7 Wiring routing must be properly arranged so control board cover is fix...

Страница 4: ...door unit to prevent direct sunlight or rain exposure More than 11 8 in 30cm make sure that heat radiation from the condenser is not restricted Ensure that the clearance around the back of the unit is...

Страница 5: ...g Hitch it on the connective cable between indoor unit and outdoor unit after installation Cord protection rubber ring If the cord clamp can not fasten the cord for the small size of the cord please u...

Страница 6: ...Two of the A B and C directions should be free from obstructions INSTALLATION INSTRUCTIONS 6 CAUTIONS One Two One Three One Four More than 4 72 in 12cm Air filter Remote controller Air filter Remote c...

Страница 7: ...supporting should be taken The connection between bracket and wall bracket and the air conditioner should be firm stable and reliable Be sure there is no obstacle to block flow Strong wind Fig 4 Outdo...

Страница 8: ...put them on after flaring work Flare nut Copper tube Fig 9 8 REFRIGERANT PIPE CONNECTION 1 2 Drain joint installation NOTE The drain joint may differ from appliance to appliance Fit the seal into the...

Страница 9: ...ent protection device and disconnect switch should be used for each unit 4 Ensure the air conditioner is grounded well 5 Refer to the attached Electrical Connection Diagram located on panel of outdoor...

Страница 10: ...wires or power cords are connected reliably and correctly or the air conditioner could not run normally Fig 15 CAUTIONS Make sure to connect the indoor unit A B C D E to the Hi and Lo valve and termin...

Страница 11: ...A L B N A N B S A S B Model C TO A POWER POWER POWER POWER POWER POWER TO B L N S L1 L2 S 1 2 3 L1 L2 S 1 2 3 L1 L2 S L1 L2 S L1 L2 S 1 2 3 L1 L2 S 1 2 3 L1 L2 S L1 L2 S L 1 1 2 N S L 1 1 2 N S L N S...

Страница 12: ...L1 A L1 A 1 A L2 A L2 A 2 A S A S A 3 A L1 L1 L1 L2 L2 L2 L1 L2 S 1 2 3 1 2 3 L1 C L1 C 1 C L2 C L2 C 2 C S C S C 3 C L1 B L1 B 1 B L2 B L2 B 2 B S B S B 3 B L1 L2 S 1 2 3 1 2 3 L1 L2 S 1 2 3 1 2 3 L...

Страница 13: ...2 N S TO C L 1 1 2 N S TO D L 1 1 2 N S TO B L 1 1 2 N S TO E L 1 1 2 N S Model C POWER L N L A N A S A L B N B S B L C N C S C L D N D S D L E N E S E Model D TO B TO C TO A TO D W 1 L 2 N S W 1 L 2...

Страница 14: ...as specified in the power source specification 7 Always install an ground fault circuit breaker in a wet or dump area 8 The following would be caused by voltage drop Vibration of a magnetic switch whi...

Страница 15: ...pe length ft m Standard pipe lengthxN More than Standard pipe lengthxN ft m Air purging method Use vacuum pump Use vacuum pump Additional amount of refrigerant to be charged R410A AIR PURGING Air purg...

Страница 16: ...um valves and the vacuum position is at the main valve the system is not connected with the indoor unit must be tightened with a screw nut Checking the gas leakage before operation to prevent leakage...

Страница 17: ...k at the flare nut connections and electrical safety check Check that all tubing and wiring have been properly connected Check that the gas and liquid side service valves are fully open 1 Connect the...

Страница 18: ...Controller at the Indoor Unit for steps 6 and 7 6 Install batteries into Wireless Remote Controller 7 Immediately press and hold MODE FAN and TIMER ON button for 3 seconds until Wireless Remote Contr...

Страница 19: ...NOTES...

Страница 20: ...CS464 I 16122000001504 20150912 The design and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details...

Отзывы: