13
EIHPTC
CEILING FLOOR TYPE
Install the drain joint of the outdoor unit
Fit the seal into the drain joint, then insert the drain joint into
the base pan hole of outdoor, rotate 900 to securely assemble
them. Connect the drain joint with an extension drain hose
(Locally purchased), in case of the condensate draining off the
outdoor unit during the heating mode. (Refer to Fig.8-2)
Outdoor unit is equiped with a drain piping. Its position is
shown figure below
Prepare a polyviny chloride with 21mm inner diameter.
Fasten the tube to the drain hose with an adhesive and the
field-supplied clamp. The drain piping must be performed with
a DOWN-SLOPE pitch of 1/25 to 1/100.
Seal
The base pan hole
of outdoor unit
Drain joint
Seal
The base pan
of outdoor unit
Drain
joint
Fig.8-2
Drain Piping
Fig.8-2
A B
18 24
595 1200
36
624 1381
48 60
646 1385
MODEL
Table 8-1
mm
Connect a siphon, as shown in figure below.
Plug
75
Slope 2 %
Fig.8-3
NOTE
All the figures in this manual are for explanation purpose only.
They may be slightly different from the air conditioner you
purchased.The actual unit shall prevail.
WIRING
9.
The appliance shall be installed in accordance with national
wiring regulations.
The air conditioner should use separate power supply with rated
voltage.
The external power supply to the air conditioner should have
ground wiring, which is linked to the ground wiring of the
indoor and outdoor unit.
The wiring work should be done by qualified persons according
to circuit drawing.
An all-pole disconnection device which has at least 3mm
separation distance in all pole and a residual current device
(RCD) with the rating of above 10mA shall be incorporated in
the fixed wiring according to the national rule.
Be sure to locate the power wiring and the signal wring well to
avoid cross-disturbance.
Do not turn on the power until you have checked carefully after
wiring.
The power cord type designation is H07RN-F.
NOTE
Remark per EMC Directive 2004/108/EC.
For to prevent flicker impressions during the start of the compressor
(technical process) ,following installation conditions do apply.
The power connection for the air conditioner has to be done at
the main power distribution. The distribution has to be of a low
impedance, normally the required impedance reaches at a 32 A
fusing point.
No other equipment has to be connected with this power line.
For detailed installation acceptance please refer to your power
supplier, if restrictions do apply for products like washing machines,
air conditioners or electrical ovens.
1
2
3
For power details of the air conditioner refer to the rating plate of
the product.
For any question contact your local dealer.