18
5
.
CHEMICAL FEEDER TIME:
Use the
p
UP or
q
DOWN buttons to set the length of time, in
seconds, that the auxiliary output will be turned on.
Then press the SELECT button to accept and
return to the normal run (time of day) screen.
ECOWATER
S Y S T E M S
Features / Options (Softeners & Filters)
SELEC-
TION
NAME
AUXILIARY OUTPUT
FUNCTION
OFF
Off
Remains off indefinitely.
BP
Bypass
On during the entire recharge.
CL
Chlorine
On during the brine draw portion
of the recharge.
FS
Flow
Switch
On when water is flowing past
the turbine*. It will shut off 8
seconds after water flow stops.
CF
Chemical
Feeder
After the set volume of water
has flowed past the turbine*,
turns on for the time set (see
Steps 4 & 5, below, to set vol-
ume and time).
FR
Fast
Rinse
On during the fast rinse por-
tion of the recharge.
The default is OFF. If you wish to change to one of
the other selections shown in the table:
1
. Press and hold the SELECT button until “000 - -”
shows in the display (See Figure 36).
3
. Use the
p
UP or
q
DOWN buttons to display the
desired selection, then press the SELECT button.
If you selected anything other than CF, the display
will return to the normal run (time of day) screen.
If setting to CF (Chemical Feeder), there will be
two additional settings to make for operating the
chemical feeder in Steps 4 and 5, below.
FIG. 37
FIG. 38
FIG. 39
4
.
CHEMICAL FEEDER TRIP VOLUME:
If you have
set the auxiliary output control to CF (Chemical
Feeder), you will need to set the volume of water
which must flow past the turbine* before the auxil-
iary output is turned on. With the alternating
screens in Fig. 38 shown, use the
p
UP or
q
DOWN buttons to set the trip volume, in gal-
lons. Then press the SELECT button to display the
screen shown in Fig. 39.
FIG. 36
2
. Press the SELECT button several times, until “Ctrl"
flashes in the display (See Figure 37).
WIRING SCHEMATIC
FIG. 40
NO
Valve
Motor
Position
Switch
NC
Power Supply
Back of Electronic Controller
(PWA)
Power
In
Pos./Turbine
Motor
24V DC
Auxiliary Output
J4
24V DC
120V AC
60 Hz
C
org
grn
*
A turbine and turbine cable must be added to the system if auxiliary output selections “FS” or “CF” are to be used.