14
Dimensions of electric boilers/module with three stage control
Tab. 1
Technical characteristics of electric boilers/Module with three stage control
Tab. 2
Technical data
Tab. 3
Cross-section of power supply cables to electric network
Tab. 4
МRТ 6 - 30
kW
6 - 30
height
mm
700
length
mm
385
width
mm
260
Module-T 6 – 30
kW
6 - 30
height
mm
645
length
mm
315
width
mm
270
Maximum power
kW
6, 8
10,12
15,18
22
24,30
Commutations level
pcs
3
3
3
3
3
Boiler body volume
dm
3
8,9
8,9
8,9
8,9
8,9
Supply voltage
V
240/400
240/400
400
400
400
Maximum operating pressure
Bar
2,5
Test pressure
Bar
4,0
Regulation of heat medium temperature
°C
30–90
Room temperature control
°C
5–30
Connection pipes dimensions
G
1”
Efficiency index
%
99,30
Р [ kW]
I
heater
[A]
Cross-section [mm
2
]
I
fuse
[A]
6
8,33
5 x 2,5
10
8
11,11
5 x 2,5
16
10
13.89
( 3 x 2,5 + 1,5 ) + 1 х 4
20
12
16,67
( 3 x 4 + 2,5 ) + 1 х 4
25
15
20,83
( 3 x 4 + 2,5 ) + 1 х 6
32
18
25,00
( 3 x 6 + 4 ) + 1 х 10
40
22
31,25
( 3 x 6 + 4 ) + 1 х 10
50
24
33,33
( 3 x 10 + 6 ) + 1 х 10
50
30
41,67
( 3 x 10 + 6 ) + 1 х 10
63