Check if the cable glands are watertight.
√
Keep the area around the workplace free of obstacles.
19. OPERATION / INSTALLATION MANUAL
19.1 Requirements for the power cable
The power cable must be attached to a separate group in the
distributor / meter cupboard. For an automatic system, this
must be the C or D characteristic or equivalent. Cabling must
be in full conformity with NEN1010.
Exceptions to NEN1010 are:
- Earth distribution resistance < 30 Ohm.
- Installation resistance < 2 Ohm.
19.2 Mounted on a wall or on a special rack
The Homebox should preferably be mounted at a height of +/-
100 centimetres, measured from the lower edge of the
Homebox.
First remove the steel shield by removing the torx screw at the bottom.
Guide the cable into the Homebox and secure the cable using the cable
gland. (The cable can be guided into the system via the back or via the cable
gland opening at the bottom).
Connect the wires in the way indicated on the terminator strip.
Connect the phase wires* to the terminals L1 / L2 / L3.
Connect the neutral wire to the neutral terminal.
Connect the shielding/earthing wire to the neutral terminal.
(*This can be 1-phase or 3-phase, depending on the available power source.
If you want to use 1-phase, connect to Phase 1 and to Neutral and Earth.)
Use the proper screwdriver size for connecting the wires, and tighten the
screws with a torque of at least 3.5Nm. Do not forget to connect the loose
earthing wire from the Homebox to the loose cover.
Use the correct screws included to securely fix the Homebox to the wall or
rack.
When using the special mounting rack, the cable must be guided through
the opening of the structure. The mounting rack must be sunk at least 70
centimetres (max. 90) into the underground and may need to be anchored
in concrete.